ABATEMENT AQUATRAP AT100S Instruction Manual

Manual is about: LGR Portable Dehumidifier

Summary of AQUATRAP AT100S

  • Page 1

    1 of 10 the aquatrap tm lgr portable dehumidifier model at100s instruction manual read and save these instructions note: 1. Read and understand all operating instructions before using the at100s aquatrap lgr portable dehumidifier 2. Save this manual for future reference. This instruction manual prov...

  • Page 2

    2 of 10 general information the at100s is a low grain refrigerant (lgr) dehumidifier, which is used to remove moisture from air within a building envelope. The dried air will then extract moisture from wetted building materials and building contents by circulating the dry air. “low grain” refers to ...

  • Page 3

    3 of 10 caution: if the unit has been laid on its back, even for short periods of time, it must be set upright for at least ½ hour before being plugged in and started up. This gives the compressor oil and liquid refrigerant sufficient time to re-distribute. Failure to do so can cause premature compr...

  • Page 4

    4 of 10 check the condition of power cord(s) before using them. Damaged cords can cause fatal electric shock and/or equipment damage. Power cord(s) should never be exposed to water, heat, sharp, or abrasive objects; in addition, they should never be kinked or crushed. Avoid tightly wrapping the cord...

  • Page 5

    5 of 10 warning: pressurized unit. This equipment is factory-charged with refrigerant r-22 and is under pressure. Only qualified personnel should attempt repairs to the refrigeration system. Do not puncture or cut into the refrigeration piping. Warning: the unit should never be operated without the ...

  • Page 6

    6 of 10 fault conditions: blocked drain – the red led will flash, the audible alarm will sound, and the lcd will display “blocked drain”, which indicates the water level in the pump reservoir is abnormally high. This could be due to the following: • kinked or pinched drain hose • excessive lift (dra...

  • Page 7

    7 of 10 access to cleaning periodically, the evaporator coil, condenser coil, air-to-air heat exchanger, drain pan and drain tube will need to be cleaned. The frequency of cleaning is indeterminate and depends on how often the equipment is used and how dirty the operating environment has been. The f...

  • Page 8

    8 of 10 • day 1-180: a unit that fails between 1 and 180 days after sale will be repaired at no cost to the user. This may involve paying for repair services, parts, transportation, and repair consumables, depending on how and where the repair is carried out. • day 181-365: a unit that fails between...

  • Page 9

    9 of 10 ati product, voids all warranties and performance claims. The remedies set forth herein are exclusive. Any replacement parts supplied under warranty will be warranted for the balance of the product’s warranty. Establishing the proof of purchase date for warranty purposes is the responsibilit...

  • Page 10

    10 of 10 troubleshooting guide – lgr commercial dehumidifier warning: some instructions contained herein are for use by qualified personnel only. Troubleshooting may involve fire, shock, explosion, or mechanical injury hazards that can cause personal injury or death. Symptom cause check / correction...