ABB REF601 Applications Manual

Manual is about: Feeder/Motor protection and control

Summary of REF601

  • Page 1

    Relion ® 605 series relion ® 605 series feeder protection and control / feeder protection ref601 / rej601 application manual relion ® 605 series.

  • Page 3

    Document id: 1mdu07212-yn issued: 2012-09-28 revision: revision: a product version: 2.1 © copyright 2012 abb. All rights reserved.

  • Page 4

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and ...

  • Page 5

    Disclaimer the data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intende...

  • Page 6

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents ref601 / rej601 1 application manual table of contents section 1 general .................................................................. 5 1.1 this manual ................................................................................................ 5 1.2 intended audience ......

  • Page 8

    Table of contents 2 ref601 / rej601 application manual 4.2 earth fault protection ..................................................................................14 4.2.1 functionality .........................................................................................14 4.2.2 principle of op...

  • Page 9

    Table of contents ref601 / rej601 3 application manual 5.2.8 menu – test ......................................................................................... 36 5.2.9 access level ........................................................................................ 40 5.2.10 version informat...

  • Page 11

    1mdu07212-yn rev. A section 1 general ref601 / rej601 5 application manual section 1 general 1.1 this manual this manual contains application and functionality descriptions and connection diagrams, input and output signals, setting parameters and technical data. The manual can be used as a technical...

  • Page 12

    Section 1 1mdu07212-yn rev. A general 6 ref601 / rej601 application manual 1.4 document symbol and conventions this publication includes the following icons that point out safety-related conditions or other important information: safety indication symbols the information icon alerts the reader to im...

  • Page 13

    1mdu07212-yn rev. A section 2 ref601/rej601 overview ref601 / rej601 7 application manual section 2 ref601/rej601 overview 2.1 overview ref601/rej601 is a dedicated feeder protection relay, intended for the protection of utility substations and industrial power systems, in primary and secondary dist...

  • Page 14

    Section 2 1mdu07212-yn rev. A ref601/rej601 overview 8 ref601 / rej601 application manual 2.3 operation functionality 2.3.1 relay functions ref601/rej601 offers pre-configured functionality which facilitates easy and fast commissioning of switchgear. To emphasize the simplicity of relay’s usage, onl...

  • Page 15

    1mdu07212-yn rev. A section 2 ref601/rej601 overview ref601 / rej601 9 application manual 2.4 other functions 2.4.1 self-supervision the ied is provided with an extensive self-supervision system which continuously supervises the software and the electronics. It handles run-time fault situations and ...

  • Page 16

    Section 2 1mdu07212-yn rev. A ref601/rej601 overview 10 ref601 / rej601 application manual 2.4.2 fault record and trip counter the relay stores records of analog values for last five trip events in non-volatile memory. The fault recording is triggered by the trip signal of a protection function. Eac...

  • Page 17

    1mdu07212-yn rev. A section 2 ref601/rej601 overview ref601 / rej601 11 application manual table 3: list of event types and related description sr. No. Event type description data considered 1 power supply presence unit ready contact activation will be stored as an event. This unit ready contact is ...

  • Page 18

    Section 2 1mdu07212-yn rev. A ref601/rej601 overview 12 ref601 / rej601 application manual 2.4.5 access control to protect the relay from unauthorized access and to maintain the integrity of information, the relay is armed with a three level, role-based user authentication system with individual pas...

  • Page 19

    1mdu07212-yn rev. A section 3 technical data ref601 / rej601 13 application manual section 3 technical data for detailed technical data please refer the product guide. Section 4 protection and control function 4.1 three phase overcurrent protection 4.1.1 functionality the three-phase overcurrent pro...

  • Page 20

    Section 4 1mdu07212-yn rev. A protection and control function 14 ref601 / rej601 application manual table 5: setting ranges non-directional overcurrent protection, high stage 3i>>, 50-1 description value setting range of pick-up current i>> 0.5...25 x in in steps 0.001, infinite operation mode defin...

  • Page 21

    1mdu07212-yn rev. A section 4 protection and control function ref601 / rej601 15 application manual 4.2.3 setting range of earth fault overcurrent protection table 7: setting ranges non-directional earth fault protection, low stage io>, 51n description value nominal value of earth current 1 a or 5a ...

  • Page 22

    Section 4 1mdu07212-yn rev. A protection and control function 16 ref601 / rej601 application manual 4.4 protection characteristics 4.4.1 time / current characteristics relay offers three-stage overcurrent and two stage earth-fault protection functions. The low-set stage of overcurrent protection and...

  • Page 23

    1mdu07212-yn rev. A section 4 protection and control function ref601 / rej601 17 application manual 4.4.3 ri type characteristic the ri-type characteristic is a special characteristic used mainly in combination with existing mechanical relays. The characteristic is based on the following mathematica...

  • Page 24

    Section 4 1mdu07212-yn rev. A protection and control function 18 ref601 / rej601 application manual by default all binary outputs are no (normally open). During non-availability of power, binary output configured as inverted will open and its status will be restored only after availability of power....

  • Page 25

    1mdu07212-yn rev. A section 4 protection and control function ref601 / rej601 19 application manual 3. Circuit breaker command: binary inputs bi2 to bi4 can be configured to provide external (remote) breaker open or breaker close command. For routing circuit breaker opening or closing command from b...

  • Page 26

    Section 4 1mdu07212-yn rev. A protection and control function 20 ref601 / rej601 application manual figure 3: application diagram of tcs function when the circuit breaker is open, tcs measure the voltage across the trip contact through rext (external shunt resistance shown in below figure) and trip ...

  • Page 27

    1mdu07212-yn rev. A section 4 protection and control function ref601 / rej601 21 application manual 4.9 signal diagram the figure below schematically illustrates the analogue input, binary input / output and led indications. Figure 4: signal diagram of relay ref601/rej601 table 13: analog inputs l1,...

  • Page 28

    Section 4 1mdu07212-yn rev. A protection and control function 22 ref601 / rej601 application manual table 15: led indications (on relay front) ) trip (red) common trip led for overcurrent and earth fault trip indication trip ip (red) trip led for overcurrent faults (i>, i>> and i>>>) trip io (red) t...

  • Page 29

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 23 application manual section 5 use of lhmi 5.1 overview figure 5: local hmi of relay ref601/rej601 the local hmi of the relay contains following elements: led indicators lcd display navigation buttons / keys the lhmi is used for setting, mon...

  • Page 30

    Section 5 1mdu07212-yn rev. A use of lhmi 24 ref601 / rej601 application manual 5.1.2 lcd display the lhmi includes 2 x 16 character lcd display. The measurement, recorded data, events, settings etc. Can be viewed in the display. 5.1.3 navigation the lhmi keypad consists of push buttons which are us...

  • Page 31

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 25 application manual 5.1.4 authorization within ref601/rej601 three user categories with predefined user rights are provided. During access of the main menu the selection of user category is handled with an own password (two key combinations...

  • Page 32

    Section 5 1mdu07212-yn rev. A use of lhmi 26 ref601 / rej601 application manual 5.1.5 configuration status at default view, whenever any key is pressed, for 3 second the configuration status screen appears followed by a password request screen. Following figure shows configuration status screen: fig...

  • Page 33

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 27 application manual 5.2.2 main menu the main menu appears after entering the password with the user rights depended on the entered password. Following view shows the main menu of the relay. Figure 9: main menu of relay ref601/rej601.

  • Page 34

    Section 5 1mdu07212-yn rev. A use of lhmi 28 ref601 / rej601 application manual 5.2.3 menu – measurement submenu measurement shows analogue input values as primary or as secondary values according to primary and secondary current of current transformer selected in the submenu configuration – setting...

  • Page 35

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 29 application manual 5.2.4 menu – fault record submenu fault record shows under recorded current the fault records for the last five protection trips and the values for trip counters segregated in phase fault trips and earth fault trips. For...

  • Page 36

    Section 5 1mdu07212-yn rev. A use of lhmi 30 ref601 / rej601 application manual 5.2.6 menu – setting submenu settings and respective submenus shows and allows depending on the user right to change all protection parameters and communication parameters. Remark: to modify settings needs user rights of...

  • Page 37

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 31 application manual i> settings i> curve:xxxxxxx xx i> i> :xx.Xxx in i> k :xx.Xx i> t> :xx.Xx s or i>> i>> i>> :xx.Xxx in i>> t>> :xx.Xx s i>>> i>>> i>>> :xx.Xxx in i>>> t>>> :xx.Xx s i0> i0> curve:xxxxxxx xx i0> i0> :xx.Xxx in i0> k :xx.Xx...

  • Page 38

    Section 5 1mdu07212-yn rev. A use of lhmi 32 ref601 / rej601 application manual 5.2.7 menu – configuration submenu configuration and respective submenus shows and allows depending on the user right to change blocking of particular protection stage or remote trip activation relay configuration settin...

  • Page 39

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 33 application manual.

  • Page 40

    Section 5 1mdu07212-yn rev. A use of lhmi 34 ref601 / rej601 application manual.

  • Page 41

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 35 application manual blocking configuration bi configuration bo configuration settings model name xxxxxxxx earth type xxxxxxxx primary ct xxxx com admin level yyy frequency xx hz iec; read only parameter internal; external 20….9999 no; yes 5...

  • Page 42

    Section 5 1mdu07212-yn rev. A use of lhmi 36 ref601 / rej601 application manual 5.2.8 menu – test submenu test and respective submenus shows and allows depending on the user right to perform several kind of tests to verify the ied functionality: test -> hardware: enables internal hardware tests, whi...

  • Page 43

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 37 application manual 5.2.8.1 menu – hardware following functionalities can be tested through this menu. Lcd test keyboard test led test during each test wherever confirmation from user is asked to continue test sequence, if no selection from...

  • Page 44

    Section 5 1mdu07212-yn rev. A use of lhmi 38 ref601 / rej601 application manual figure 17: hardware test menu of relay ref601/rej601 with its submenu (continue).

  • Page 45

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 39 application manual test continue yes:up no:down toggle leds select ‘yes’ with: confirm with: no or timeout to confirm will lead to exit test led test test continue yes:up no:down led test figure 17: hardware test menu of relay ref601/rej60...

  • Page 46

    Section 5 1mdu07212-yn rev. A use of lhmi 40 ref601 / rej601 application manual 5.2.8.3 submenu – functional test submenu functional test allows performing simulation of each protection function by giving a test current to the selected protection function. Test hardware :yyy test test bo test functi...

  • Page 47

    1mdu07212-yn rev. A section 5 use of lhmi ref601 / rej601 41 application manual 5.2.10 version information this menu provides information regarding the product type selected, software version being presently loaded into the product, model name, nominal current value selected, and the type of trip ci...

  • Page 48

    Section 6 1mdu07212-yn rev. A installation 42 ref601 / rej601 application manual section 6 installation 6.1 unpacking and inspecting the device ref601/rej601 products, although of robust construction, require careful handling prior to installation on site. The delivered products should always be exa...

  • Page 49

    1mdu07212-yn rev. A section 6 installation ref601 / rej601 43 application manual 6.4 relay wiring the connection wiring to the relay should be made by using single strand wire or stranded wire with the use of insulated crimp terminal to maintain the insulation requirements. The wire with below indic...

  • Page 50

    Section 6 1mdu07212-yn rev. A installation 44 ref601 / rej601 application manual figure 23: panel mounting details of ref601/rej601 press fit mechanism 4.0 152 ± 0.5 panel door.

  • Page 51

    1mdu07212-yn rev. A section 6 installation ref601 / rej601 45 application manual relay connection diagram figure 24: connection diagram of relay ref601 /rej601.

  • Page 52

    Section 6 1mdu07212-yn rev. A installation 46 ref601 / rej601 application manual 6.6 relay ordering information the relay type and serial number label identifies the protection relay. An order number label is placed on the side of the relay. The order number consists of a string of codes generated f...

  • Page 53

    1mdu07212-yn rev. A section 6 installation ref601 / rej601 47 application manual 6.8 setting table table 20: settings parameter actual value default value unit range resolution 3i> / 51 1.500 in 0.2...25 ; infinite 0.001 t> 1.00 sec 0.04...64 0.01 curve dt - dt, ni, vi, ei, li, ri - k 0.5 - 0.1...1....

  • Page 54

    Section 6 1mdu07212-yn rev. A installation 48 ref601 / rej601 application manual table 22: binary input / output configuration binary input connected to signal bi1 bi2 bi3 bi4 input behavior: inversion (-) (-) (-) (-) block : i> / 51 block : i>> / 50-1 block : i>>> / 50-2 block : io> / 51n block : i...

  • Page 56

    Contact us 1mdu 072 12-yn a © copyright 2012 abb. All r ights res erved . Abb ltd, distribution automation maneja works vadodara-390013, india phone: +91 265 2604386 fax: +91 265 2638922 www.Abb.Com/substationautomation.