Barnett Engineering 1272M001 Instruction Manual - 1.  Operations Overview

Manual is about: Barnett Engineering Alarm System Instruction Manual

Summary of 1272M001

  • Page 1

    &hooxodu $58 3ur7don instruction manual 1272m001 manual revision: 7 - july 2002.

  • Page 2: Contents

    Contents 1. Operations overview cv2 capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 what constitutes an alarm? . . . . . . . . . . . . . . . . . 1-1 how are alarms processed? . . . . . . . . . . . . . . . . . 1-2 what actions should occur when an alarm is detected? . . . . . ....

  • Page 3: 1.  Operations Overview

    Operations overview 1-1 b1272m001 barnett engineering ltd. Protalk cv2 1. Operations overview the purpose of this chapter is to provide an overview of the cv2 capabilities. Chapter topics are organized in the same order that you would follow in setting up the system. Read this chapter carefully befo...

  • Page 4

    Operations overview 1-2 b1272m001 barnett engineering ltd. Protalk cv2 hardware inputs 8 inputs 8 outputs points up to 30 inputs or outputs group 1 telephone port hardware outputs group 6 directory a directory f dialout commands control commands figure 1 cv2 block diagram analog inputs convert the v...

  • Page 5

    Operations overview 1-3 b1272m001 barnett engineering ltd. Protalk cv2 the hardware input and output ports are activated in the points section to become part of the monitoring and control process. There are 30 points which can be referenced to any of the i/o ports. This allows an analog input to be ...

  • Page 6

    Operations overview 1-4 b1272m001 barnett engineering ltd. Protalk cv2 for example, to call four telephone numbers, the directory would appear as: 1. [dial]2458829 [voice] 2. [dial]2336700 [voice] 3. [dial]9842121 [voice] 4. [dial]9843316 [voice] if you want an alert tone to precede the voice messag...

  • Page 7

    Operations overview 1-5 b1272m001 barnett engineering ltd. Protalk cv2 1.6 what if an alarm is not acknowledged? When the last line in the directory has been completed without receipt of an acknowledge code, a two-stage timer is used to determine when the directory sequence is repeated again. This t...

  • Page 8

    Operations overview 1-6 b1272m001 barnett engineering ltd. Protalk cv2 1.9 indicators the cv2 has four led indicators to show the operation of the unit and assist in troubleshooting. When the cv2 is initially powered up, the four leds will do the following: & all will turn on for approximately one s...

  • Page 9

    Operations overview 1-7 b1272m001 barnett engineering ltd. Protalk cv2 are the inputs connected properly? For digital inputs that are programmed for standard digital operation, create an alarm condition on the input and confirm that the alarm led comes on. Make sure the input is applied long enough ...

  • Page 10: Installation

    Installation 2-1 b1272m001 barnett engineering ltd. Protalk cv2 figure 3 packaged cv2 2 installation the cv2 can be installed before or after the configuration has been transferred from the pc to the unit. If the cv2 is configured in the shop before it is installed in the field, all of the programme...

  • Page 11

    Installation 2-2 b1272m001 barnett engineering ltd. Protalk cv2 figure 3 stand-alone cv2 figure 4 ground closure input wiring 2.2.2 stand-alone model the stand-alone cv2 can be mounted on a flat surface. Make sure that there is enough room around the unit to make connections. The environment should ...

  • Page 12

    Installation 2-3 b1272m001 barnett engineering ltd. Protalk cv2 figure 5 +12 volt input wiring figure 6 +5 vdc input wiring figure 8 analog (unfiltered) input wiring figure 7 analog (filtered) input wiring 2.3.2 +12 volt alarm signal the input will accept an alarm signal that switches between 0 and ...

  • Page 13

    Installation 2-4 b1272m001 barnett engineering ltd. Protalk cv2 figure 9 output wiring figure 10 serial cable 2.4 output port connections the output ports are open collector drivers that can sink up to 500 ma through a load connected to a voltage of up to +50 vdc. If an inductive load such as a rela...

  • Page 14

    Installation 2-5 b1272m001 barnett engineering ltd. Protalk cv2 figure 11 stand-alone cv2 figure 12 packaged cv2.

  • Page 15: Configuration Using The Pc

    Configuration using the pc 3-1 b1272m001 barnett engineering ltd. Protalk cv2 3 configuration using the pc this chapter describes how to install the programming software and configure the operation of the cv2. When the configuration is complete, it can be viewed through the summary command found on ...

  • Page 16

    Configuration using the pc 3-2 b1272m001 barnett engineering ltd. Protalk cv2 3.4.1 file operations file open if you do not want to edit the default database, use the file open button to select a different configuration file. This will bring up the standard windows file open dialog box where you can...

  • Page 17

    Configuration using the pc 3-3 b1272m001 barnett engineering ltd. Protalk cv2 3.4.6 directories when an alarm is detected, the cv2 will perform a specific sequence of events determined by the entries in the directory. Six directories are available, providing different actions for different groups. 3...

  • Page 18

    Configuration using the pc 3-4 b1272m001 barnett engineering ltd. Protalk cv2 debounce times, use the seconds timer to avoid the inaccuracy introduced by the one minute resolution. Default debounce time: 0.05 sec a digital input port can also be used to perform special functions in the cv2. In the g...

  • Page 19

    Configuration using the pc 3-5 b1272m001 barnett engineering ltd. Protalk cv2 analog input setting the input port type to analog allows measurement of voltages between 0 and +5 volts. As with the other input types, the definition of an analog input is completed in the points section where the range,...

  • Page 20

    Configuration using the pc 3-6 b1272m001 barnett engineering ltd. Protalk cv2 each point can be placed into one of the six groups. If a port is used for one of the special functions, the group section sets the ports. To access a point for configuration, select the points button to bring up the summa...

  • Page 21

    Configuration using the pc 3-7 b1272m001 barnett engineering ltd. Protalk cv2 enabled when a point is enabled, alarm activities will be reported and it can be interrogated for its current status. A disabled point does not produce alarms and cannot be interrogated. Changing the enable flag does not a...

  • Page 22

    Configuration using the pc 3-8 b1272m001 barnett engineering ltd. Protalk cv2 when the message is spoken, the digits to the left of the decimal (represented by x) and the digits to the right of the decimal (represented by y) are spoken with the word ‘point’ between them. The format with the decimal ...

  • Page 23

    Configuration using the pc 3-9 b1272m001 barnett engineering ltd. Protalk cv2 calibrate calibration of an analog allows the conversion of the input voltage reading to a value that is expressed in engineering units. Setpoints are then assigned to the actual corresponding measurement, and when the poi...

  • Page 24

    Configuration using the pc 3-10 b1272m001 barnett engineering ltd. Protalk cv2 0 as the minimum, 10 as the maximum, with units set to read ‘thousand’ as the prefix before gallons. Once the range of the decimal scale has been entered, then the high and low setpoints can follow. Both setpoints can be ...

  • Page 25

    Configuration using the pc 3-11 b1272m001 barnett engineering ltd. Protalk cv2 dtmf off code when the cv2 receives the dtmf off code, it sets the output port to the off state. After the off code has been received and the output port cleared, the cv2 announces the current status of the output. This c...

  • Page 26

    Configuration using the pc 3-12 b1272m001 barnett engineering ltd. Protalk cv2 conditions. If a different type of activity is required, such as after hours or weekends, the change can be quickly made by using another shift to control the cv2 operation. There are also a number of special function set...

  • Page 27

    Configuration using the pc 3-13 b1272m001 barnett engineering ltd. Protalk cv2 enable ack request at the completion of an alarm announcement sequence, the cv2 will query the called party with the phrase “enter acknowledge code’. If this prompt is not required, clear the enable setting. Default ack r...

  • Page 28

    Configuration using the pc 3-14 b1272m001 barnett engineering ltd. Protalk cv2 special function outputs outputs can be assigned to indicate certain conditions within the cv2. The three special function outputs are: alarm active this control allows any one of the eight output ports to be used as an i...

  • Page 29

    Configuration using the pc 3-15 b1272m001 barnett engineering ltd. Protalk cv2 only digital inputs can be used for this purpose. The selection shown in the list box is restricted to inputs that are set to digital in the hardware section. To use this feature, the input must be selected in the points ...

  • Page 30

    Configuration using the pc 3-16 b1272m001 barnett engineering ltd. Protalk cv2 auto ack if enabled for the group using this directory, the auto ack command causes the cv2 to automatically acknowledge its alarms without receipt of any other code or signal. This command is used when it is anticipated ...

  • Page 31

    Configuration using the pc 3-17 b1272m001 barnett engineering ltd. Protalk cv2 signal if a dtmf tag is programmed for a point and the signal command is set, then only the dtmf tag for this point will be sent and the voice message will not be spoken. Signal must be preceded by a dial command; it cann...

  • Page 32

    Configuration using the pc 3-18 b1272m001 barnett engineering ltd. Protalk cv2 programming is always available if there is no access code in the unit. This code can be 1 to 7 digits in length and may use any of the 16 dtmf digits including a, b, c, and d. Default access code: an empty string. Shift ...

  • Page 33

    Configuration using the pc 3-19 b1272m001 barnett engineering ltd. Protalk cv2 operational. Data is transferred in four-kilobyte packets at 9600 baud. The configuration database will take two packets to transfer; the number of packets in a voice data transfer will vary depending on how many points a...

  • Page 34

    Voice storage and configuration with the telset 4-1 b1272m001 barnett engineering ltd. Protalk cv2 4 voice storage and configuration with the telset 4.1 setup after the configuration database has been transferred to the cv2, it is ready to accept the voice messages that will be used in the alarm rep...

  • Page 35

    Voice storage and configuration with the telset 4-2 b1272m001 barnett engineering ltd. Protalk cv2 directory menu. The choices at this point are: 0 uu - speak the directory codes these codes correspond to buttons found in the directory editor dialog box used for pc programming. They are used to ente...

  • Page 36

    Voice storage and configuration with the telset 4-3 b1272m001 barnett engineering ltd. Protalk cv2 if a sequence is entered without a voice command, the cv2 will add the word “warning” when it speaks the line. 3 uu delete current entry cv2: “beep” this command will remove the selected line from the ...

  • Page 37

    Voice storage and configuration with the telset 4-4 b1272m001 barnett engineering ltd. Protalk cv2 pauses between words may cause the recording to terminate. If the message is acceptable, press uu to advance to the next voice. If it is not, keep using 2 uu and repeat the message until it is satisfac...

  • Page 38

    Voice storage and configuration with the telset 4-5 b1272m001 barnett engineering ltd. Protalk cv2 8 uu - received signal strength cv2: “code eight is one, one, two, one, ...” the cv2 speaks a number from one to thirteen. Each increment corresponds to approximately 5 dbm, with 0 representing roughly...

  • Page 39

    Voice storage and configuration with the telset 4-6 b1272m001 barnett engineering ltd. Protalk cv2 cv2: "enter program code" cv2: "enter directory code" edit directories speak directory codes cv2: speaks the list of directory codes described previously , ... Cv2: "directory one line one is dial 2559...

  • Page 40

    Voice storage and configuration with the telset 4-7 b1272m001 barnett engineering ltd. Protalk cv2 exit cv2: "group one is electrical" cv2: "beep" record cv2: "group one is mechanical" accept cv2: "beep" enable groups "electrical on" or "electrical off" disable this group cv2: "electrical off" accep...

  • Page 41

    Voice storage and configuration with the telset 4-8 b1272m001 barnett engineering ltd. Protalk cv2 query nam cv2: "code four is one" or "code four is two" - call placed query min cv2: "code five is two three eight ..." query esn cv2: "code six is nine four four..." query rssi cv2: "code eight is one...

  • Page 42: 5  Specifications

    Specifications 6-1 b1272m001 barnett engineering ltd. Protalk cv2 5 specifications 5.1 general alarm inputs • 8 inputs: analog or digital, latching or momentary; plug in screw terminal block. • analog: 0 to 5 vdc, 100k input impedance • digital: normally open or normally closed, ground closure or +1...

  • Page 43

    Specifications 6-1 b1272m001 barnett engineering ltd. Protalk cv2 alarm groups • alarms can be assigned to one of 8 groups. All alarms in a group use the same directory when calling out. Shifts • up to 4 shifts can be used. The current setting of the shift instructs a group to use one of the six dir...

  • Page 44: 6 Warranty

    Specifications 6-1 b1272m001 barnett engineering ltd. Protalk cv2 6 warranty barnett engineering ltd. Warrants that all equipment supplied shall be free from defects in material or workmanship at the time of delivery. Such warranty shall extend from the time of delivery for a period of one year. Buy...