Eaton-Williams Qualitair Installation Manual

Other manuals for Qualitair: Technical Manual & Installation Procedures
Manual is about: ICC COOLING STORAGE UNIT ICC/ICU SYSTEM

Summary of Qualitair

  • Page 1

    0412115 b e e a a t t o o n n - - w w i i l l l l i i a a m m s s l l t t d d installation manual icc cooling storage unit icc/icu system eaton-williams ltd station road – edenbridge – kent – tn8 6eg tel: +44 (0)1732 866066 fax +44(0)1732 866653 www.Eaton-williams.Com.

  • Page 2

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 2 index contents page 1. Installation and safety 3 1.1 installation 3 1.2 handling 3 1.3 application 3 1.4 electrical connection 3 1.5 warranty 3 1.6 safety procedures 3 2. Introduction to units 4 2.1 icc indoo...

  • Page 3

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 3 1. Installation & safety 1.1 installation the units making up the air conditioning system must only be installed by a qualified engineer, following the mandatory and local codes of practice. 1.2 handling care...

  • Page 4

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 4 2. Introduction to units 2.1 icc indoor unit the icc has been designed for installation in areas which require products or produce to be stored in cool conditions (down to 5°c). As standard, the units are sui...

  • Page 5

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 5 3. Location & mounting of indoor unit (icc) ← → icc 25 icc 35 icc 50 icc 60 icc 70 a 475 475 475 525 525 b 390 390 390 440 440 c 805 805 805 865 865 d 450 450 450 525 525 e 680 680 680 740 740 f 680 680 680 6...

  • Page 6

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 6 4. Indoor unit access (icc) ↓ ← ↑ → 4.1 access details/fixings item n° unit component access details / fixing (1) motor / fan remove 4-off screw fittings and disconnect electrical connections. (2) electric se...

  • Page 7

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 7 5. Location & mounting of outdoor unit (icu) figure 5.1 – icu unit positioning figure 5.3 – icu wall bracket fixing table 5.1 – icu wall mount kit fixing icu30 icu40 icu55 icu80 width mm 720 720 800 800 heigh...

  • Page 8

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 8 6. Outdoor unit access (icu) × figure 6.1 – unit internal access 6.1 access details/fixings item no. Unit component access details/fixings (1) fan guard front access set screw fixings (2) fan/motor ((fixed to...

  • Page 9

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 9 7. General service connections figure 7.1 – unit connections and interconnections 7.1 – liquid connections 7.2 – suction connections 7.4 - condensing unit 7.5 – interconnecting cable 7.7 – power cable 7.8 – i...

  • Page 10

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 10 7. General service connections cont table 7.3 – icc refrigerant connections icc25 icc35 icc50 icc60 icc70 liquid connections 1/4” 1/4” 1/4” 3/8” 3/8” suction connections 1/2” 5/8” 5/8” 3/4” 3/4” table 7.4 – ...

  • Page 11

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 11 8. Power & control connections figure 8.1 – electrical interconnecting diagrams n l s c l n e c n l l 3 l 2 l 1 n e c s r power feed pe pe power feed c pe pe h special notes: ensure three phase supply is con...

  • Page 12

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 12 9. Disposal procedures note! All refrigerant, oils and other waste materials must be disposed of in a professional and responsible manner in strict adherence to environmental regulations. Note! The greatest ...

  • Page 13

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 13 10. Refrigerant pipe connections 9.1c 9.1b figure 9.1 – refrigerant pipe connections 10.1 pipe installation run the suction and liquid lines in appropriately sized refrigeration copper tubing as per the deta...

  • Page 14

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 14 system charge weights 5) disconnect the vacuum pump and connect the gauge high pressure port (9) to the discharge line of the outdoor unit shut-off valve (10), ensuring that the gauge central port (3) is clo...

  • Page 15

    Icc / icu system installation manual e\manuals\others\qualitair\icc\0412115 15 11.2 icu – recommended line sizes horizontal or downflow application (suction line) upflow application (suction line) based on 5psi (0.35bar) pressure drop line length (m) max max r407c – kg table a 5 10 15 20 25 30 35 40...

  • Page 16

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115b 16 11.3 example of line sizing from table a horizontal suction to be 7/8” horizontal liquid to be ½” 45m table b not applicable icu80 evap added oil none required added gas 105g x 40m from ta a ble horizontal s...

  • Page 17

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115 17 12. Ancillary service connections figure 11.1 – condensate services ← → ↑ 12.1 condensate removal as standard the condensate is removed by gravity drainage on the bottom of the unit. 12.2 condensate connectio...

  • Page 18

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115 18 13. Final checks check 1) have all options kits been fitted ? 2) have units been mounted level and correct drainage been checked by pouring 2 litres of water into drip tray? 3) has the icu (outdoor) drain bee...

  • Page 19

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115 19 14 wiring diagram numbers this page gives wiring diagram numbers for each type of indoor (icc) and outdoor (icu) unit manufactured by qualitair. The diagrams themselves are supplied with the unit and are loca...

  • Page 20

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115 20 c c e e c c e e r r t t i i f f i i c c a a t t e e eaton-williams air conditioning (eaton-williams ltd) station road – edenbridge - kent - tn8 6eg - england telephone ... 44 (0)1732 866055 telefax ... (0)173...

  • Page 21

    Icc / icu system installation manual january2005: e\manuals\others\qualitair\icc\0412115 21 station road edenbridge kent tn8 6eg tel: (01732) 866066 fax:(01732) 867937 an eaton-williams company as part of the policy of continuous product improvement, we reserve the right to alter specifications with...