Galleon 1.5K User Manual - page 2

Manual is about: Rackmount Online UPS

Summary of 1.5K

  • Page 1

    Rackmount online ups 1k/1.5k/2k/3k uninterruptible power supply system version: 1.1 user manual.

  • Page 2

    Table of contents 1. Important safety warning ....................................................................... 1 1-1. Transportation ................................................................................. 1 1-2. Preparation ..............................................................

  • Page 3

    1 1. Important safety warning please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating i...

  • Page 4

    2 1-5. Maintenance, service and faults  the ups system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.  caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the ups sys...

  • Page 5

    3 2. Installation and setup note: before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. Note: there are two different types of online ups: standard and long-run models. Please refer to the fo...

  • Page 6

    4 7. Usb communication port 8. Rs-232 communication port 9. Snmp intelligent slot 10. External battery connector (only available for long-run models) 11. Output circuit breaker 2-2. Install the ups for safety consideration, the ups is shipped out from factory without connecting battery wires. Before...

  • Page 7

    5 step 3: communication connection communication port: usb port rs-232 port intelligent slot to allow for unattended ups shutdown/start-up and status monitoring, connect the communication cable one end to the usb/rs-232 port and the other to the communication port of your pc. With the monitoring sof...

  • Page 8

    6 2-4 battery replacement notice: this ups is equipped with internal batteries and user can replace the batteries without shutting down the ups or connected loads.(hot-swappable battery design) replacement is a safe procedure, isolated from electrical hazards. Caution!! Consider all warnings, cautio...

  • Page 9

    7 2-5 battery kit assembly (option) notice: please assemble battery kit first before installing it inside of ups. Please select correct battery kit procedure below to assemble it. 2-battery kit step 1: remove adhesive tapes. Step 2: connect all battery terminals by following below chart. Step 3: put...

  • Page 10

    8 4-battery kit step 1: remove adhesive tapes. Step 2: connect all battery terminals by following below chart. Step 3: put assembled battery packs on one side of plastic shells. Step 4: cover the other side of plastic shell as below chart. Then, battery kit is assembly well. 6-battery kit step 1: re...

  • Page 11

    9 3. Operations 3-1. Button operation button function on/mute button  turn on the ups: press and hold on/mute button for at least 2 seconds to turn on the ups.  mute the alarm: after the ups is turned on in battery mode, press and hold this button for at least 3 seconds to disable or enable the al...

  • Page 12

    10 display function backup time information indicates the estimated backup time. H: hours, m: minute, s: second configuration and fault information indicates the configuration items, and the configuration items are listed in details in section 3-5. Indicates the warning and fault codes, and the code...

  • Page 13

    11 3-3. Audible alarm battery mode sounding every 5 seconds low battery sounding 2 seconds overload sounding every second fault continuously sounding 3-4. Lcd display wordings index abbreviation display content meaning ena enable dis disable esc escape hls high loss lls low loss bat battery bah batt...

  • Page 14

    12  01: output voltage setting interface setting parameter 3: output voltage for 200/208/220/230/240 vac models, you may choose the following output voltage: 200: presents output voltage is 200vac 208: presents output voltage is 208vac 220: presents output voltage is 220vac 230: presents output vol...

  • Page 15

    13  06: eco voltage range setting interface setting parameter 1 & 2: set the acceptable high voltage point and low voltage point for eco & aeco mode by pressing down key or up key. Hls: high loss voltage in eco & aeco mode in parameter 2. For 200/208/220/230/240 vac models, the setting range in par...

  • Page 16

    14  09: bypass frequency range setting interface setting parameter 1 & 2:set the acceptable high frequency point and acceptable low frequency point for bypass mode by pressing the down key or up key. Hls: bypass high frequency point for 50hz output frequency models: 51-55hz: setting the frequency l...

  • Page 17

    15  13: battery total ah setting interface setting parameter 2: set up the battery total ah of the ups. 7-999: setting the battery total capacity from 7-999 in ah. Please set the correct battery total capacity if external battery bank is connected.  14: maximum charger current setting interface se...

  • Page 18

    16 3-6. Operating mode description operating mode description lcd display online mode when the input voltage is within acceptable range, ups will provide pure and stable ac power to output. The ups will also charge the battery at online mode. Eco mode energy saving mode: when the input voltage is wi...

  • Page 19

    17 3-8. Warning indicator warning icon (flashing) alarm low battery sounding every 2 seconds overload sounding every second battery is not connected sounding every 2 seconds over charge sounding every 2 seconds site wiring fault sounding every 2 seconds epo enable sounding every 2 seconds over tempe...

  • Page 20

    18 4. Troubleshooting if the ups system does not operate correctly, please solve the problem by using the table below. Symptom possible cause remedy no indication and alarm even though the main is normal. The ac input power is not connected well. Check if input power cord firmly connected to the mai...

  • Page 21

    19 symptom possible cause remedy fault code is shown as 43 and the icon is lighting on lcd display and alarm is continuously sounding. The ups shut down automatically because of overload at the ups output. Remove excess loads from ups output and restart it. Fault code is shown as 14 and alarm is con...

  • Page 22

    20 model 1k 1.5k 2k 3k capacity* va/w 1000 va / 900 w 1500 va / 1350 w 2000 va / 1800 w 3000 va / 2700 w input voltage range low line transfer 80 vac/70 vac/60 vac/55 vac ± 5 % or 160 vac/140 vac/120 vac/110 vac ± 5 % (based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0) low line comeback ...