Galleon 10KRT User Manual

Manual is about: 6K/10K Rack/Tower Online UPS

Summary of 10KRT

  • Page 1

    6k/10k rack/tower online ups uninterruptible power supply system version: 1.2 user manual.

  • Page 2: Carefully.

    Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully..

  • Page 3: Table of Contents

    Table of contents 1. Safety and emc instructions .................................................................... 4 1-1. Transportation and storage ........................................................... 4 1-2. Preparation ........................................................................

  • Page 4

    1. Safety and emc instructions please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1-1. Transportation and storage please transport the ups system only in the original package to protect against shock and impact. The ups must be s...

  • Page 5

    1-4. Connection warnings • there is no standard backfeed protection inside, please isolate the ups before working according to this circuit. The isolation device must be able to carry the ups input current. • this ups should be connected with tn earthing system. • the power supply for this unit must...

  • Page 6

    Time since this would cancel the protective earth of the ups system and of all connected loads. If the external battery cabinet is connected, the ups output anderson connector may be electrically live even if the ups system is not connected to the building wiring outlet. In order to fully disconnect...

  • Page 7

    2. Installation there are two types: standard and long-run models. Please refer to the following model table. Model type model type 6krt standard model 6krtl long-run model 10krt standard model 10krtl long-run model 2-1. Unpacking and inspection unpack the package and check the package contents. The...

  • Page 8

    Diagram 3: battery pack rear panel 1. Rs-232 communication port 2. Usb communication port 3. Epo (emergency power off) connector 4. Share current port (for parallel function) 5. Parallel port (for parallel function) 6. Intelligent slot 7. Embs (external maintain bypass switch) port 8. Cooling fan 9....

  • Page 9

    2-3. Rack/tower installation 2-3-1 tower installation the ups system is shipped with two sets of feet and 6 extensions (2 short extensions plus 4 long extensions) that can be used to tower install the ups module in 3u or ups module with one battery bank in 6u. Install ups module in 3u assemble two f...

  • Page 10

    2-3-2 rack installation please follow below steps to mount ups into 19” rack or rack enclosure. Step 1: attach mounting ears to the side mounting holes of ups using the screws provided and the ears should face forward. Please refer to chart 1. Chart 1 step 2: lift the ups module and slide it into ra...

  • Page 11

    Regulations. Warning: ● for standard battery pack, there are one dc breaker to disconnect the battery pack and the ups. But for other external battery pack, make sure a dc breaker or other protection device between ups and external battery pack is installed. If not, please install it carefully. Swit...

  • Page 12

    3. Operations 3-1. Operating mode/status description mode/status description ups power on when ups is powered on, it will enter into this mode for a few seconds for initializing the cpu and system. Ac mode when the input voltage is within acceptable range, and the ups is turned on (the inverter is r...

  • Page 13

    There are 4 buttons on front panel. 3-3. Led indicators there are 4 leds on front panel to show the ups working status: mode led bypass line battery fault ups power on bypass mode ● ○ ○ ○ ac mode / converter mode ○ ● ○ ○ battery mode ○ ○ ● ○ fault mode ○ ○ ○ ● battery test mode ○ ● ● ○ eco mode ● ● ...

  • Page 14

    Move the arrow to “yes” by up or down button, then press “on/enter”, the ups will be starting up with beeping once. You could also enter the “control menu” to select the instruction “turn on” to startup the ups. Please refer to the section of “lcd operation”. 3) a few seconds later, the ups will ent...

  • Page 15

    Prolong the backup time. If there is no more load to be taken off at that time, you have to shut down all loads as soon as possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure; 2) in battery mode, if buzzer sounds annoying, you could enter ”control->m...

  • Page 16

    3-5-9. Changing battery quantity (number) the default battery (12v) quantity of this ups system is 20 (for one series), but 18, 19 could also be applied in this system. However, before changing the battery quantity, the ups should be fully shutdown and the cabinet cover should be removed, and the ju...

  • Page 17

    3-7. Lcd operation the entire lcd structure is demonstrated as diagram below: main interface control measurement information setting alarm page 1: input page 2: output page 3: battery page 4: bypass page 5: charger turn on batt test mute para unlock page 1: bypass page 2: eco page 3: output page 4:b...

  • Page 18

    3) when the front panel is not operated for 10 minutes, the display page will return back to home page; 4) press the “up” or “down” button to enter the operation menu (see 3-7-2-1); 5) when it displays home page in lcd, if ups is in bypass, you could press the “on/enter” button to turn on the ups to...

  • Page 19

    → → note: you may simply turn on ups by pressing “on/enter” button in home page. It’s not necessary to enter control menu to turn on the ups. B) on ac mode or converter mode or eco mode or battery mode, it will display “turn off” in control menu. If it is selected and confirmed, the ups will transfe...

  • Page 20

    → → 4) para unlock it’s to allow ups startup with parallel function. It only appears when the lcd shows the warning of “3f: para protect”. It means the parallel system is in protection and could not startup because of parallel communication failure. Before restart the parallel system, please confirm...

  • Page 21

    3-7-2-4. Information information displays all parameter setting value and status. Press “up” or “down” to explore the pages. 3-7-2-5. Setting this menu is used to configure the parameter settings or do the calibrations. Note: some settings will be only available in some operation modes. If the setti...

  • Page 22

    1) bypass setting interface description 1. Status (only available in bypass / ac mode) 1.1 open/forbid: open: bypass allowed. When selected, ups will run at bypass mode depending on bypass enabled/disabled setting. Forbid: bypass not allowed. When selected, it’s not allowed for running in bypass mod...

  • Page 23

    3) output setting (only available or effective on bypass mode) interface description 1. Volt: 208: presenting the rated output voltage with 208vac 220: presenting the rated output voltage with 220vac 230: presenting the rated output voltage with 230vac 240: presenting the rated output voltage with 2...

  • Page 24

    5) calibration interface description 1. Batt: calibrate the battery voltage measurement. Calibration range is from 0v to 5.7v. The default value is 0v. It is available on all operation modes. 2. Inv: adjust the inverter output voltage; the adjustable range is from 0v to 6.4v, the default value is 0v...

  • Page 25

    Backup time parameters setting: batt groups: set the number of battery group ranging from 1 to 6. The default value is 1 group; batt cap: set the battery capacity such as 7ah, 9ah, 10ah, 12ah, 17ah, 26ah, 40ah, 65ah, 100ah and so on. The default value is 9ah. Factor: calibrate the displayed backup t...

  • Page 26

    3-7-2-6. Alarm page this page records and displays the faults or warning events happened in history..

  • Page 27

    4. Trouble shooting 4-1. Warning status when fault led flashes and the buzzer beeps once every second, it means that there are some problems with ups. Users can see the warning code from lcd panel and refer to the trouble shooting table to check what problem probably happen. 4-2. Fault mode 1) when ...

  • Page 28

    Warning 0d: over temp the internal temperature is too high and reach the warning level: 1) maybe the environment is hot; 2) maybe the fan is blocked or failed; 3) maybe ventilation is blocked by the wall or other goods. 4) load is too heavy. 1) make sure ambient temperature not over 40ºc. 2) make su...

  • Page 29

    Fault 04: bus unbalance 1) the load is special or abnormal, so the internal positive and negative dc bus voltages are unbalanced. 2) the internal converter failed. Contact the dealer. Fault 11: inv start fail the internal inverter failed, so the inverter voltage could not start up correctly. Contact...

  • Page 30

    5. Storage and maintenance 5-1. Storage before storing, charge the ups at least 7 hours. Store the ups covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: storage temperature recharge frequency charging duration -25°c - 40°c every...

  • Page 31

    6. Specifications model 6krt(l) 10krt(l) capacity* 6000 va / 5400 w 10000 va / 9000 w input voltage range low line loss 110 vac ± 3 % at 50% load; 176 vac ± 3 % at 100% load low line comeback low line loss voltage + 10v high line loss 300 vac ± 3 % high line comeback high line loss voltage - 10v fre...