Intermatic T174CR Supplementary Manual
MODEL: T174CR
24 HR DIAL TIME SWITCH WITH “SKIPPER
®
”
AND SPRING-WOUND CARRY-OVER MOTOR
DOUBLE POLE SINGLE THROW (DPST)
IN TYPE 3R RAINPROOF ENCLOSURE,
40 AMP. RESISTIVE, EACH POLE 120-480 VOLT A.C. 40 AMP INDUCTIVE, OR
TUNGSTEN OR 1000 VA. PILOT DUTY EACH POLE - 120V -277V AC;
2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.
WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid
or stranded COPPER only wire with insulation to suit installation. See
gauge selection table for normal service applications. To make power
connections remove 1/2 inch of insulation from wire ends. Insert bare
ends of wire under the pressure plate of terminals. Use 3/16 or larger
screwdriver to tighten terminal screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
PROGRAMMING INSTRUCTIONS
1.
TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of
CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF
operations are desired, tighten tripper screws firmly. For additional
tripper pairs on
CLOCK-DIAL order 156T1978A.
2.
TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either
direction and align the exact time-of-day on the
CLOCK-DIAL (the
time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER.
3.
TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING
SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s)
is/are NOT required. Tighten screws firmly. Move
MANUAL LEVER to
“OFF” and rotate SKIPPER WHEEL to locate correct day-of-week
opposite
DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER
has not yet advanced wheel
“TODAY” if it has.
OPERATING INSTRUCTIONS
•
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below
CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE
SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO
ON/CUTOUT TRIPPER SWITCHING.
•
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to
proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10930
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V.
240 V.
14
12
10
8
15
20
30
40
60
60
60
75
1/2
1
2
-
2
2 1/2
3
5
N/A
N/A
TIME
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON/CUTOUT
TRIPPER
DAY
ARROW
SKIPPER
WHEEL
SKIPPING
SCREW
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
CLOCK
MOTOR
GROUND
A
1
2
277 480 VOLT CONNECT MOTOR LEADS TO TERMINALS
“A” AND 2 AND SUPPLY NEUTRAL TO TERMINAL “A”.
TO
LOAD
GRD
LINE 1
WIRING
DIAGRAM
3
4
LINE 2
240V
SUPLY
LR3730
Project1 7/27/04 4:30 PM Page 1