Lans ST3200 User Manual

Summary of ST3200

  • Page 1

    User manual 1kva ~ 3kva 220vac.

  • Page 2

    User manual 1-3kva rev. 9 i contents 1.1 general description .............................................................................................. 1 1.2 system configuration...........................................................................................2 ` tower ....................

  • Page 3

    User manual 1-3kva rev. 9 ii important safety instructions save these instructions. This ups unit operates from utility power and contains a number of high current back-up batteries, the information is important to all personnel involved. Please read this manual before installation and operation of ...

  • Page 4

    User manual 1-3kva rev. 9 - page 1 of total 30 - 1. Presentation 1.1 general description the continuity of electrical power is an essential requirement for critical load operations .The uninterruptible power system (ups) is a compact and quiet solution for power protection of computer, server and of...

  • Page 5

    User manual 1-3kva rev. 9 - page 2 of total 30 - 1. Presentation 1.2 system configuration ` tower 1kva: 160w x 220h x 400d mm / 15 kgs 2kva: 200w x 352h x 450d mm / 34 kgs 3kva: 200w x 352h x 450d mm / 35 kgs.

  • Page 6

    User manual 1-3kva rev. 9 - page 3 of total 30 - 1. Presentation ` rack-mount 1kva: 440w x 88h x 465d mm / 15.5 kgs 2kva: 440w x 88h x 465d mm / 35 kgs 3kva: 440w x 88h x 465d mm / 36 kgs.

  • Page 7

    User manual 1-3kva rev. 9 - page 4 of total 30 - 1. Presentation 1.3 front panel 1.3.1 tower ` lcd 1 2 3 4 5 6 7 1. 2-line lcd display 2. Normal led (green) 3. Warning led (yellow) 4. Fault led (red) 5. Select-up button 6. Select-down button 7. Enter button 5-6. Off button 6-7. On button 5-7. Test/s...

  • Page 8

    User manual 1-3kva rev. 9 - page 5 of total 30 - 1. Presentation 1.3.2 rack-mount 1 2 3 4 5 6 7 1. 2-line lcd display 2. Normal led (green) 3. Warning led (yellow) 4. Fault led (red) 5. Select-up button 6. Select-down button 7. Enter button 5-6. Off button 6-7. On button 5-7. Test/silence button.

  • Page 9

    User manual 1-3kva rev. 9 - page 6 of total 30 - 1. Presentation 1.4 rear panel ` tower ○ 1 ○ 6 ○ 1 ○ 6 ○ 7 ○ 7 ○ 1 ○ 6 ○ 2 ○ 8 ○ 2 ○ 8 ○ 7 ○ 9 ○ 9 ○ 2 ○ 8 ○ 9 ○ 10 ○ 3 ○ 4 ○ 4 ○ 4 ○ 5 ○ 5 ○ 5 ○ 3 ○ 3 1kva 2kva 3kva 1. Standard rs232 port 2. Fan 3. External battery slot (option) 4. Input breaker 5. ...

  • Page 10

    User manual 1-3kva rev. 9 - page 7 of total 30 - 1. Presentation ` rack-mount 1kva ○ 1 ○ 2 ○ 3 ○ 4 ○ 5 ○ 6 ○ 7 ○ 8 ○ 9 2kva ○ 4 ○ 3 ○ 6 ○ 2 ○ 5 ○ 9 ○ 7 ○ 1 ○ 8 3/2(long run time)kva ○ 4 ○ 3 ○ 6 ○ 2 ○ 5 ○ 9 ○ 7 ○ 1 ○ 8 ○ 11 ○ 10 1. External battery slot (option) 2. Outlets (iec 10a,germen) 3. Inlet 4...

  • Page 11

    User manual 1-3kva rev. 9 - page 8 of total 30 - 1. Presentation ` external battery bank or module for tower product ranges: for rack-mount product ranges:.

  • Page 12

    User manual 1-3kva rev. 9 - page 9 of total 30 - 2. Installation 2.1 unpacking the st series ups can be supplied in a varied number of boxes depending upon the model ordered. The number of boxes provided should be as follows: model (box 1) battery module (box 2) total boxes st 3200 tower n/a (intern...

  • Page 13

    User manual 1-3kva rev. 9 - page 10 of total 30 - 2. Installation st series 1-3kva rack mount box 1 c defg shipping box includes: 1. Ups 2. User manual 3. Input power cord (german, british, australian) 4. Extension power cord (iec) to pc (for output receptacles “iec” only) 5. 2pcs 19” rack ears (+sc...

  • Page 14

    User manual 1-3kva rev. 9 - page 11 of total 30 - 2. Installation 2.2 installation ` tower optional communication slot standard rs232 to pc as400 rj45 protection for tel/fax/modem/dsl remote control usb to external battery cabinet db9 output to the loads to the wall socket snmp/http ` rack-mount to ...

  • Page 15

    User manual 1-3kva rev. 9 - page 12 of total 30 - 2. Installation 2.3 connection to communication 2.3.1 standard ` rs-232 the communication interface (db9 port) on the back of the ups may be connected to a host computer with specific monitoring software installed. (please contact a sales representat...

  • Page 16

    User manual 1-3kva rev. 9 - page 13 of total 30 - 2. Installation 2.3.2 optional interface cards a variety of interface cards can be installed into optional communication slot such as db9 dry contact card, usb card, as400 card, and snmp/http card. ` usb card ` db9 dry contact card pin definition of ...

  • Page 17

    User manual 1-3kva rev. 9 - page 14 of total 30 - 2. Installation ` as400 card ` snmp/http agent netagent mini allows a user to obtain the status, and issue commands to the ups. The communications protocol includes the megatec/ ppc/ sec 2400 / 9600. Also it is possible to build in your own protocol....

  • Page 18

    User manual 1-3kva rev. 9 - page 15 of total 30 - 3. Operation 3.1 lcd and led display ` lcd display 1 - welcome screen aec star t3 series on-line ups display 2 - input/output voltage and frequency input:220v 50hz identification output:220v 50hz display 3 – ups status ac:fail batt:low no output disp...

  • Page 19

    User manual 1-3kva rev. 9 - page 16 of total 30 - 3. Operation display 5 – battery voltage/ capacity battery voltage 37 vdc battery capacity 100 % display 6 – output power output power 100 % display 7 – inside temperature inside temp 33 ℃ 91 ℉ display 8 – new alarm new ac fail: 1 alm overload: 3 dis...

  • Page 20

    User manual 1-3kva rev. 9 - page 17 of total 30 - 3. Operation ` led 1 6 7 8 9 10 2 3 4 5 1. Line led (green): this indicates the ac power is applied to the ups input. If the led blinks, it means the ac power source is out of tolerance. 2. Battery led (yellow): this indicates the ups is in battery m...

  • Page 21

    User manual 1-3kva rev. 9 - page 18 of total 30 - 3. Operation 3.2 starting up/ shutting down the ups starting up the ups step 1. Plug the ups into an ac wall socket and the ups will enter bypass mode. Step 2. Press the “select-down” & “enter” button simultaneously to switch on ups. The ups will beg...

  • Page 22

    User manual 1-3kva rev. 9 - page 19 of total 30 - 3. Operation 3.3 operating modes normal mode there are two main circuits when ac utility is normal: the ac circuit and the battery charging circuit. The ac output power comes from ac utility input and passes through ac/dc rectifier, dc/ac inverter an...

  • Page 23

    User manual 1-3kva rev. 9 - page 20 of total 30 - 3. Operation bypass mode under the following conditions, the bypass will be enabled: 1. Overload. 2. Inverter failure. 3. Over-temperature.

  • Page 24

    User manual 1-3kva rev. 9 - page 21 of total 30 - 3. Operation 3.4 configuration settings ups must be working on bypass mode in advance for any setting, because the setting function can not be available on normal mode and battery mode. ` output voltage / frequency step 1. In this screen, press the “...

  • Page 25

    User manual 1-3kva rev. 9 - page 22 of total 30 - 3. Operation ` bypass voltage ups must be working on bypass mode in advance for any setting, because the setting function can not be available on normal mode and battery mode. Step 1. To protect the load, the function of bypass auto-transfer is activ...

  • Page 26

    User manual 1-3kva rev. 9 - page 23 of total 30 - 4. Maintenance 4.1 general maintenance the st series ups requires only very simple maintenance. The batteries are sealed, valve-regulated, maintenance-free and enclosed in a fire-retardant pack. The batteries should be kept charged to maintain their ...

  • Page 27

    User manual 1-3kva rev. 9 - page 24 of total 30 - 4. Maintenance 4.2 replacing the new battery this ups contains potentially hazardous voltages. Do not open the ups. There are no user-serviceable parts inside. 4.3 testing the new battery start up the ups with load added. Press the “select-up” & “ent...

  • Page 28

    User manual 1-3kva rev. 9 - page 25 of total 30 - 5. Troubleshooting ` lcd lcd & led status / audible alarms possible cause action fault warning normal y ups in bypass mode. Y the alarm beeps continuously. Ac: ok batt: ok temp fail 1. Fan fail. 2. Temperature is higher than allowed operation tempera...

  • Page 29

    User manual 1-3kva rev. 9 - page 26 of total 30 - 5. Troubleshooting lcd & led status / audible alarms possible cause action fault warning normal y ac utility power is normal but ups is overloaded up to 125%. Y warning led does not fade out and alarm beeps per 0.5 second. Output power 125 % 1. Overl...

  • Page 30

    User manual 1-3kva rev. 9 - page 27 of total 30 - 5. Troubleshooting ` led led status / audible alarms possible cause action y no indication and buzzer alarm even though system is connected to mains power supply. 1. No input voltage 1. Check building wiring socket outlet and input cable. Y line led ...

  • Page 31

    User manual 1-3kva rev. 9 - page 28 of total 30 - 6. Appendix 6.1 specifications ` general specification specifications model no. St3200 (tower) st3200r (rack-mount) st3200 (tower) st3200r (rack-mount) st3200 (tower) st3200r (rack-mount) topology true on - line , double conversion on- battery output...

  • Page 32

    User manual 1-3kva rev. 9 - page 29 of total 30 - 6. Appendix ` battery run time tower run time chart in minutes output load ups model 200 va (140 w) 400 va (280 w) 600 va (420w) 800 va (560w) 1000 va (700 w) 1500 va (1050 w) 2000 va (1400 w) 2500 va (1750 w) 3000 va (2100 w) st3010 60 24 13 8 5 + 1...