Protectowire 2000 FireSystem Operating & Maintenance Manual

Manual is about: FIRE DETECTION CONTROL PANEL

Summary of 2000 FireSystem

  • Page 1

    Fire detection control panel operating & maintenance manual an iso 9001 registered company approved.

  • Page 2

    Important service notice when requesting service assistance, or to order parts for this control panel, you are required to provide the model number , drawing number and serial number . This product information is recorded on the panel identification label located inside the control panel. Please hav...

  • Page 3: Www.Protectowire.Com

    60 washington street, pembroke, ma 02359-1833 usa tel. (781) 826-3878 fax (781) 826-2045 visit us on the world wide web at: www.Protectowire.Com fs2000 series fire detection control panel operating & maintenance manual part number man-2000 revision date: june 1, 2011.

  • Page 4: Table Of Contents

    ~ 1 ~ table of contents page no. Notice 3 system specifications, installation and operation fs2000 series control panel information and specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 standard enclosure mounting...

  • Page 5: Table Of Contents

    Option page no. “h” intrinsic safety barrier for special hazard applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 “h” intrinsic safety barrier field wiring illustration (il-1008) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 “k” int...

  • Page 6: Notice

    Notice testing and maintenance of system controls shall be performed by competent, qualified personnel having jurisdiction over this protective signaling system. This system may contain detection zones which are assigned to trip release solenoids and/or equipment shut- down. As a deterrent to accide...

  • Page 7: System Specifications

    Fs2000 series fire detection deluge/preaction control panel information and specifications the fs2000 series of multiple zone fire protection panels is the latest in fire protection from the protectowire company, inc. The standard model provides, as a minimum, 2 (class a or b) initiating device circ...

  • Page 8

    Fs2000 series fire detection deluge/preaction control panel information and specifications (continued) initiating circuits class a (nfpa style d)/class b (nfpa style a and b) end-of-line resistor 4.7k ohm 1 /2 watt (class b only) maximum feed cable 100 ohms. (elr-hd-4-qc) typical detection circuit f...

  • Page 9

    Fs2000 standard enclosure dimensions (all dimensions in inches) ~ 6 ~ enclosure back box dimension reference table important: the above stated dimensions are for the enclosure back box only and do not account for the overall dimensions of the enclosure with the door installed. To account for the enc...

  • Page 10

    Fs2000 lti2x enclosure dimensions (all dimensions in inches) enclosure dimension reference table type a b c d e rows columns spaces lti2x 17.5” 19.5” 9” 12” 18.85” 2 1 2 note: enclosure shown represents the lti2x only. For lti4 - lti9 dimensions reference the lti4 -lti9 dimensions page of this manua...

  • Page 11

    Enclosure dimension reference table type a b c d e rows columns spaces lti4 35.25” 24” 6.85” 34” 18” 2 2 4 lti6 35.25” 29” 6.85” 34” 23” 2 3 6 lti9 46.25” 29” 6.85” 45” 23” 3 3 9 note: enclosure shown represents the lti4, 6 and 9 only. For lti2x dimensions reference the lti2x dimensions page of this...

  • Page 12: Ds-9066A  Issued 3-1-05

    Fs2000 series alarm circuit installation guide ds-9066a issued 3-1-05 alarm notification appliance circuit wire size estimator to ensure that all alarm notification appliance circuits will be supplied with adequate power to operate, it is necessary to use the correct size feed cable for the distance...

  • Page 13

    Fs2000 series fire alarm control panel battery size calculation sheet use this form to calculate the required battery size for your system. You must first determine the duration the panel will need to function on batteries in hours. The installation wiring diagram for your system includes a factory ...

  • Page 14: Ds-9079B

    Fs2000 series fire alarm control panel typical panel wire routing detail ds-9079b when bringing field wires to and from the control panel you must maintain segregation between power limited and non-power limited wiring. Use the illustration below as a guideline for routing wire within the system enc...

  • Page 15

    Fs2000 series fire detection - preaction/deluge control panel operation installation test and maintenance installation and system power-up. 1. Carefully unpack the system and inspect for any visible damage from shipping. 2. Mount the system in a clean, easily accessible, stable area with four (4) 1/...

  • Page 16

    Fs2000 series fire detection - preaction/deluge control panel operation installation, test and maintenance testing and maintenance quarterly testing is advised to help ensure system controls are functioning properly. Testing should be performed by competent personnel having jurisdiction over the pro...

  • Page 17

    Fs2000 series fire detection - preaction/deluge control panel operation installation test and maintenance operational outline: 1. Normal standby condition a) “ac on” indicator (green) illuminated. 2. Power supervision ac power source failure: a) “ac on” indicator (green) off. B) system trouble buzze...

  • Page 18

    Fs2000 series fire detection - preaction/deluge control panel operation installation test and maintenance operational outline continued: 6. Ground fault detection circuit (not available with option “h”) when undesirable current flows to ground from the system dc power supply, either positive or nega...

  • Page 19

    Fs2000 series fire detection - preaction/deluge control panel operation installation test and maintenance ~ 16 ~ continued on next page basic troubleshooting guide for the fs2000 series fire alarm control panel indicator status fault condition course of action alternate action p r im a r y “a.C. On”...

  • Page 20

    ~ 17 ~ continued from previous page basic troubleshooting guide for the fs2000 series fire alarm control panel indicator status fault condition course of action alternate action detection circuits “a.C. On” indicator out “sys. Alarm” indicator on zone “alarm” indicator on short in zone circuit field...

  • Page 21: Ds-9038 Rev. B

    Fs2000 series fire detection - preaction/deluge control panel part replacement instructions ds-9038 rev. B initial steps 1. Notify the applicable local fire department and/or alarm receiving station that the system is being serviced. 2. Inform all personnel in the facility that testing is in progres...

  • Page 22: Main Board - Mb-91A

    Main board - mb-91a elr-4.7k 1/2 w 1/2 w elr-4.7k n.O. / n.C. Elr-4.7k 1/2 w elr-4.7k 1/2 w or 240vac 50/60hz 0.85 amp. Max. Com. N.O. / n.C. Com. N.O. / n.C. Com. Com. N.C. N.O. Programmable trouble contacts programmable trouble contacts programmable supervisory contacts silenceable alarm contacts ...

  • Page 23: Main Board - Mb-91A/m

    ~ 20 ~ main board - mb-91a/m mb-91a standard main board supporting non-metered class a/b detection circuits mb-91a/m metered main board supporting class a/b detection circuits with alarm point location meter sys. Test system test button: press and hold for a minimum of 3 seconds. This simulates an a...

  • Page 24

    Supervisory e or 240vac 50/60hz 0.85 amp. Max. N.O. / n.C. Com. N.O. / n.C. Com. N.O. / n.C. Com. N.O. Com. N.C. *silenceable non-silenceable silenceable silenceable ~ 21 ~ main board mb-91a/m - field wiring standard class b alarm notification appliance circuits (2) note: polarity of notification ap...

  • Page 25: Initiating Device Circuits

    ~ 22 ~ main board mb-91a/m field wiring initiating device circuits class a (nfpa style d)/class b (nfpa style a and b) use the following compatible devices or devices approved by the protectowire company, inc. - up to 5,000 ft. Of protectowire per circuit. - any combination of normally open contact ...

  • Page 26

    4-wire detector power supervision description - supervision of power to 4-wire detectors is necessary to ensure their operation. Supervision is accomplished by installing a power supervisory relay (psr), model psr-2040 or its equivalent after the last detector. The relay contacts are nor- mally clos...

  • Page 27: Expander Board - Eb-91A/m

    Eb-91a variations: ~ 24 ~ expander board - eb-91a/m the zone expander board can accommodate up to (4) initiating device zones. Two zone cards per expander board with (2) initiating device zones per card. Zones can be implemented as class a/b detection, waterflow or switch supervisory circuits depend...

  • Page 28: Expander Board - Eb-91A/m

    ~ 25 ~ the zone expander board can accommodate up to (4) initiating device zones. Two zone cards per expander board with (2) initiating device zones per card. Zones can be implemented as class a/b detection, waterflow or switch supervisory circuits depending on the jumper configuration of the zc-91a...

  • Page 29: Initiating Device Circuits

    ~ 26 ~ top of eb-91a bottom of eb-91a expander board eb-91a/m field wiring initiating device circuits class a (nfpa style d)/class b (nfpa style a and b) voltage standby 22vdc nominal, power limited current to insure alarm 15ma (1k ohm loop resistance minimum) short circuit current 35ma supervision ...

  • Page 30

    ~ 27 ~ system control switches, lamp indicators and signal monitoring are managed with this module. Plug-in design allows for quick replacement during field repair. Used in conjunction with the main board (mb-91a). Standard control card module is designated as cc-91ant. This card eliminates the poss...

  • Page 31

    ~ 28 ~ system control switches, lamp indicators and signal monitoring are managed with this module. Plug-in design allows for quick replacement during field repair. Used in conjunction with the main board (mb-91a). Standard control card module is designated as cc-91ant. This card eliminates the poss...

  • Page 32

    ~ 29 ~ provides the circuitry required to operate the various class a/b initiating devices. Designed with plug-in package for field repair ease. This card plugs into the main or expander board modules. Zone card modules - zc-91a (for detection applications) zc-91a display panel description: the zone...

  • Page 33

    ~ 30 ~ provides the circuitry required to operate the various class a/b initiating devices. Designed with plug-in package for field repair ease. This board plugs into main control or expander board modules. Applicable for fm approved systems only zone card module - zc-91a (for detection applications...

  • Page 34

    ~ 31 ~ option “a” - pdm-1000-2 protectowire alarm point location meter description: the pdm-1000-2 protectowire digital alarm point location meter is designed to help locate a heat actuated point on a protectowire linear heat detector circuit. This meter identifies the distance in feet or meters (pr...

  • Page 35

    Option “c” - nds-91-16x, 16 zone alarm scanner description: the nds-91-16x sixteen zone alarm scanner identifies the zone number in conjunction with linear alarm point identification of a protectowire heat sensitive cable detection zone. In the automatic (auto) scan mode this device continually step...

  • Page 36

    Waterflow #1 waterflow #2 elr-4.7k zc-91aw display panel zc-91aw field wiring option “d” - waterflow detection card -zc-91aw ~ 33 ~ the zone card zc-91aw provides two class a or class b alarm initiating device circuits for waterflow detection monitoring. Both waterflow alarm circuits are equipped wi...

  • Page 37

    ~ 34 ~ applicable for fm approved systems only waterflow #1 waterflow #2 elr-4.7k zc-91aw field wiring option “d” - waterflow detection card -zc-91aw the zone card zc-91aw provides two class a or class b alarm initiating device circuits for waterflow detection monitoring. Both waterflow alarm circui...

  • Page 38

    ~ 35 ~ supervisory 1 supervisory 2 elr-4.7k 1/2 w sc-91a display panel sc-91a field wiring option “e” - switch supervisory card - sc-91a terminations on expander board terminals te1 or te2 description: the supervisory card sc-91a provides two class a/b alarm initiating supervisory circuits to recogn...

  • Page 39

    Description: the rs-1 solenoid release / initiat- ing device card provides one supervised solenoid output circuit. This circuit electrically energizes the coil of a releasing agent control valve and is equipped with "trouble" and "trip" l.E.D. Indica- tors for complete valve supervision and activati...

  • Page 40

    ~ 37 ~ solenoid release/initiating device card field wiring, electrical specifications & jumper settings rs-1 mj5 mj4 mj7 mj6 mj2 mj3 mj9 mj1 mj8 #1 # a5 a6 elr-4.7k 1/2 w 2 expander board eb-91a/m rs-1 display panel electrical requirements: applicable for ul approved systems only jumper settings: j...

  • Page 41

    Rs-1 mj5 mj4 mj7 mj6 mj2 mj3 mj9 mj1 mj8 ~ 38 ~ releasing circuits -solenoid releasing circuits are power limited unless star “d” (group c) valves are used. Then cir- cuits are considered non-power limited. Maximum (2) conductor feed cable impedance 0.6 ohm= #10 awg - 300 feet #12 awg - 190 feet #14...

  • Page 42

    ~ 39 ~ option factory mutual approved only intrinsic safety barrier stahl 9001/01-280-100-101 input terminals fuse cartridge mounting track field terminals ground terminal panel chassis & barriers must be connected to earth ground. Intrinsic safety barrier stahl 9001/01-280-100-101 zone #1 option “h...

  • Page 43

    ~ 40 ~.

  • Page 44

    ~ 41 ~ 1 4 3 6 5 mtl-5061 8 12 zone #2 zone #1 zone 2 option “k” - intrinsic safety dc isolator for special hazard applications description: in some hazardous area applications, the loss of ground fault detection in non-safe field circuits is unacceptable. Such cases require the implementation of dc...

  • Page 45

    ~ 42 ~.

  • Page 46

    ~ 43 ~ option “l” and “ll” - auxiliary zone alarm relays description: auxiliary zone alarm signaling relays (as) are often needed to provide an interface to other systems for annunciation and/or to pilot electrical shutdown. Also, (as) relays may be used for cross zoning initiating circuits or vario...

  • Page 47

    ~ 44 ~ option “p” - battery charger status meters description: an available numerical indication of battery status may be provided with battery charger status meters. These meters supply an easy-to-read accurate display of both the charger current draw and the charging/standby voltage level. Operati...

  • Page 48

    ~ 45 ~ option “r” - common alarm signaling relay description: the common alarm signaling (cas) relay provides two sets of contacts for interfacing to other control equipment upon the initiation of any alarm condition. This relay is normally non-silenceable but can be field modified to provide silenc...

  • Page 49

    ~ 46 ~ option “rr” - auxiliary relay module - rb-98 description: auxiliary signaling relays are often needed to provide an interface to other systems for annunciation and/or to pilot electrical shut- down. Auxiliary signaling relays may be used for “cross zoning” initiating circuits or other various...

  • Page 50

    ~ 47 ~ option “t” - class a alarm notification appliance circuit adapter description: the am-91 alarm notification appliance circuit adapter module converts the two class b system alarm notification appliance circuits of the main board mb-91 to class a type circuits. This provides 4 wire alarm notif...

  • Page 51

    ~48 ~ 1st last elr 4.7k 1/2w 1st last last 1st alarm enable input #1 alarm enable input #2 alarm enable input #4 alarm enable input #3 aux. Alarm relay drive spare spare aux. Alarm relay drive alarm enable input #3 alarm enable input #4 alarm enable input #2 alarm enable input #1 class b configurati...

  • Page 52

    ~ 49 ~ option “v” - zone voting module description: the zv-91 zone voting module is designed to supply an output signal upon the receipt of multiple zone alarm signals. The standard configuration produces a single output signal after receipt of (2) input signals. The module is also available in a (3...

  • Page 53

    ~ 50 ~ fs2000 series control panel preaction double interlock deluge cross zoning applications data sheet double interlock sprinkler systems are designed to prevent accidental release of water. When the solenoid is energized, depressur- ization of the air filled pipes (loss of air) is required to ob...

  • Page 54

    ~ 51 ~ option “x” - dual temp. Zone card module - zc-95 zc-95 display panel zc-95 description: provides two independent detection zones. Each zone is uniquely configured with two class b initiating circuits along with signal processing circuitry. The zc-95 is specifically designed for use with prote...

  • Page 55

    ~ 52 ~ option “x” - dual temperature zone card - zc-95 field wiring for main board (mb-91) and expander board (eb-91) expander board te1 terminal expander board te2 terminal main board tb3 terminal applicable for fm approved systems only low temp .(+) commo n (-) high t e mp .(+) low temp .(+) commo...

  • Page 56

    ~ 53 ~ option “y” - power conditioning module description: the ps-95 power conditioning module is designed to provide filtered, regulated dc power from a full wave rectified source (fwr). The module can provide 26 vdc power to devices such as uv/ir detectors, gas detectors, fiber optic controllers a...

  • Page 57

    ~ 54 ~ option “z” - external key operated switches description: option “z” consists of four (4) externally mounted key operated switches. These switches are used to duplicate the main control functions normally operated by the push buttons mounted on the control card (cc-91) located inside the fs200...

  • Page 58

    ~ 55 ~ preaction manual release station description: when solenoid releasing is employed, a means of manually activating the solenoid must also be provided for each release circuit as required by underwriters laboratories. The sg-32sk1 non-coded double action manual release station can provide this ...

  • Page 59

    ~ 56 ~ fs2000 series fire alarm control panel instructions release/sw . Supervisory board display main board display expander board display ds-9039c system control switches local service representative system indicators these instructions must be mounted within the system enclosure or framed and mou...

  • Page 60

    ~57 ~ appendix a the following smoke detectors/ solenoids / notification appliance circuits (nac’s) are all approved by ul for use in the fs2000 panel unless solenoid power/ current fm solenoid group size nps asco model: # t8210a107 asco model:# r8210a107 asco model:# 8210a107 asco model: # 8210g207...

  • Page 61

    ~ 58 ~ appendix a (continued) the following 24 volts dc notification appliancel circuits (nacs) are all ul approved for use on the fs2000 fire control panel. Note wheelock synch module dsm-12/24-r must be used for synchronization of horn / strobes. * - indicates field selectable device important: co...

  • Page 62

    ~ 59 ~ appendix a (continued) important: consult manufacture cut-sheet for actual current draw * - indicates field selectable device nac type model / series average current * rsd24-75110 .250 amps * rsd24-153075 * rsb24-153075 rsd24-110 .200 amps temporal module tmp1-3a .025 amps synchronization mod...

  • Page 63

    Man 2000h-0313 (100) the protectowire company, inc. N 60 washington street, pembroke, ma 02359 u.S.A. N p:781-826-3878 n f:781-826-2045 web: www.Protectowire.Com n email: pwire@protectowire.Com special hazard fire detection systems.