RLE Technologies MONITORING F110 User Manual

Manual is about: Falcon Car Satellite Radio System User Manual

Summary of MONITORING F110

  • Page 1

    Monitoring f110 user guide.

  • Page 2

    Rletech.Com 2 970.484.6510 copyright notice ©2010 rle technologies. All rights reserved. No part of this publication may be reproduced or distributed in any form or by any means, or stored in a database or retrieval system, without the prior written permission of rle technologies. Trademark notices ...

  • Page 3

    970.484.6510 3 rletech.Com product registration product registration helps rle technologies inform owners of: • product upgrades • firmware enhancements • new products and technologies • special offers available only to registered users access and submit product registration information from the f11...

  • Page 4

    Rletech.Com 4 970.484.6510 notes:.

  • Page 5

    Contents rletech.Com 5 970.484.6510 1 system overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 product description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 fro...

  • Page 6

    970.484.6510 6 rletech.Com notes:.

  • Page 7

    Figures rletech.Com 7 970.484.6510 1 system overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 figure 1.1 f110 font panel indicators and controls . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 figure 1.2 f110 terminal block designati...

  • Page 8

    Rletech.Com 8 970.484.6510 notes:.

  • Page 9

    Tables rletech.Com 9 970.484.6510 b modbus registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 table b.1 read output registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 table b.2 family code (register 4...

  • Page 10

    970.484.6510 10 rletech.Com notes:.

  • Page 11: Ystem

    Www.Rletech.Com 11 970.484.6510 c h a p t e r c hapter 0 s ystem o verview 1.1. Product description the f110 monitoring system is a comprehensive system which provides equipment protection by monitoring critical operating parameters in enterprises, remote network facilities, communication rooms, and...

  • Page 12: 1.2.

    Www.Rletech.Com 12 970.484.6510 1 system overview 1.2. Front panel indicators and controls figure 1.1 f110 font panel indicators and controls power led – green (on) if power is on. Network link – green (on) if a network connection is found. Network activity led – green (on) if network communication ...

  • Page 13: 1.3.

    Www.Rletech.Com 13 970.484.6510 1 system overview 1.3. Terminal block designations figure 1.2 f110 terminal block designations rear panel switch sensor port 1 digital input 1 switch sensor port 2 digital input 2 switch sensor port 3 digital input 3 switch sensor port 4 digital input 4 switch sensor ...

  • Page 14

    Www.Rletech.Com 14 970.484.6510 1 system overview notes:.

  • Page 15: Etting

    Www.Rletech.Com 15 970.484.6510 c h a p t e r c hapter 0 g etting s tarted 2.1. Installation the f110 comes in a 4.5”w x 1.25”h x 2.5”d desktop enclosure. Mount or place the unit in the desired location. A 19 inch (.48m) rack mount enclosure is available from rle. 2.2. Communication the f110 default...

  • Page 16: 2.2.1 Search

    Www.Rletech.Com 16 970.484.6510 2 getting started 2.2.1 search select the search button to scan the network for the f110 hardware devices. If an f110 is physically attached to your network anywhere it will be located in this scan. Note if the device discovery utility can not find the f110, reset the...

  • Page 17: 2.2.6 Update

    Www.Rletech.Com 17 970.484.6510 2 getting started 2.2.6 update click the update button to update the firmware installed on the selected f110. Updated firmware files provided by rle, add new features and enhance the web browser interface. These firmware updates are available from rle if firmware repl...

  • Page 18

    Www.Rletech.Com 18 970.484.6510 2 getting started 2.3.2 rj45 ethernet connection the f110 has an internal 10/100baset ethernet port used to configure and monitor the f110. The ethernet port supports web browser access, email (smtp), modbus, and snmp. The following figures show the physical connectio...

  • Page 19: F110 W

    Www.Rletech.Com 19 970.484.6510 c h a p t e r c hapter 0 f110 w eb i nterface 3.1. F110 web interface overview the f110’s web interface provides a convenient way to check the f110’s status and reconfigure basic settings from any internet enabled computer. Enter the ip address of the f110 into your w...

  • Page 20: 3.3. Settings

    Www.Rletech.Com 20 970.484.6510 3 f110 web interface color based upon where the temperature or humidity is in relation to the established high and low thresholds. If the temperature or humidity is between the high and low thresholds and more than five (5) degrees from either threshold, the status ic...

  • Page 21: 3.3.1 Network

    Www.Rletech.Com 21 970.484.6510 3 f110 web interface note there is no user name or no password from rle. Password can be assigned to the unit later in the configuration menu. There is no user name that can be configured at this time. 3.3.1 network the network tab stores settings to control how the f...

  • Page 22: 3.3.2 Email

    Www.Rletech.Com 22 970.484.6510 3 f110 web interface 3.3.2 email the email tab stores settings for the f110 to send email alert notifications when alert thresholds are exceeded. In order to enable email alerting from the f110's web server interface, your mail server must have smtp relay enabled for ...

  • Page 23: 3.3.3 Snmp

    Www.Rletech.Com 23 970.484.6510 3 f110 web interface note many email servers block smtp email by default. To use smtp email with the f110, be sure the f110 ip address is added to the list of allowed smtp relay hosts on the email server you are using for email. Note after you make a field change, cli...

  • Page 24

    Www.Rletech.Com 24 970.484.6510 3 f110 web interface 3.3.4 channel 2, channel 3 and channel 4 the channel 2, channel 3 and channel 4 tabs are used to configure sensor labels and to set temperature thresholds, temperature/humidity thresholds and/or alarm states for the sensors connected to sensor cha...

  • Page 25: 3.3.6 Security

    Www.Rletech.Com 25 970.484.6510 3 f110 web interface figure 3.6 sensor settings 3.3.5 switched sensor alarm configuration the channel 1 tab is used to configure sensor labels and alarm states (normally open or closed) for the eight (8) switch sensor ports (dry contact inputs) on the back of the f110...

  • Page 26: 3.3.7 Advanced

    Www.Rletech.Com 26 970.484.6510 3 f110 web interface figure 3.7 security settings 3.3.7 advanced the advanced tab is used to configure the temperature scale configuration, time & date configuration by connecting to a ntp server and provides a trace configuration for diagnostics when communicating to...

  • Page 27: 3.3.8 Reset Defaults

    Www.Rletech.Com 27 970.484.6510 3 f110 web interface temperature scale conversion: you can select how the f110 displays the temperature output on the status page, either being fahrenheit or celsius. Time & date configuration: enter an ip address of a ntp server for the f110 to synchronize with for d...

  • Page 28: 3.3.9 Help Screen

    Www.Rletech.Com 28 970.484.6510 3 f110 web interface 3.3.9 help screen the help screen displays the current firmware on the f110 unit. There are hyperlinks available for contacting rle technologies, rle technical support, and web site link for viewing other rle products and information. Figure 3.10 ...

  • Page 29: Odbus

    Www.Rletech.Com 29 970.484.6510 a p p e n d i x c hapter 0 m odbus c onfiguration v ia t elnet a.1. F110 modbus capabilities by default, the f110 is enabled to listen on tcp port 502 for modbus requests. The modbus module can be enabled or disabled, the tcp port can be changed, and a list of ip addr...

  • Page 30

    Www.Rletech.Com 30 970.484.6510 a modbus configuration via telnet enable modbus? (n)? Enter y to enable modbus and n to disable it. When modbus is disabled, the f110 will not actively listen on the modbus tcp port for modbus requests. Modbus port: (502) by default, the f110 listens for modbus reques...

  • Page 31: Odbus

    Www.Rletech.Com 31 970.484.6510 a p p e n d i x c hapter 0 m odbus r egisters table b.1 read output registers register name description units range 40002 fc family code (8 switch sensors) none 0-65535 40003 ss switch status (8 switch sensors) none 0-65535 40004 sc current alarm setting (8 switch sen...

  • Page 32

    Www.Rletech.Com 32 970.484.6510 b modbus registers 40026 tl low temperature (external sensor 3) celsius x100 0-65535 40027 hc current humidity (external sensor 3) % relative humidity 0-65535 40028 hh high humidity (external sensor 3) % relative humidity 0-65535 40029 hl low humidity (external sensor...

  • Page 33

    Www.Rletech.Com 33 970.484.6510 b modbus registers 07 switch sensor 8 status; 1 = on, 0 = off 08-15 spare table b.4 status flags (register 40004: sc) bit status flag 00 switch sensor 1 alarm on: 1 = closed, 0 = open 01 switch sensor 2 alarm on: 1 = closed, 0 = open 02 switch sensor 3 alarm on: 1 = c...

  • Page 34

    Www.Rletech.Com 34 970.484.6510 b modbus registers notes:.

  • Page 35: Echnical

    Www.Rletech.Com 35 970.484.6510 a p p e n d i x c hapter 0 t echnical s pecifications table c.1 technical specifications power 5vdc @ 800ma max.; wall adaptor included wall adapter input 110/240vac 50/60hz inputs temperature/humidity 3 digital temperature or digital temperature/humidity sensor input...

  • Page 36

    Www.Rletech.Com 36 970.484.6510 c technical specifications operating environment temperature -40°f to 185°f (-40°c to 85°c) humidity 5% to 85% rh, non-condensing altitude 15,000ft (4,572m) max. Storage environment -40°f to 185°f (-40°c to 85°c) dimensions box enclosure 4.56"w x 1.25"h x 2.25"d (115....