Safewatch QuickConnect Plus Programming Manual

Summary of QuickConnect Plus

  • Page 1

    Safewatch quickconnect plus security system programming guide bypass record test function status volume play code chime escape add delete select 1 2 4 5 7 9 8 0 armed ready off away stay 3 6 aux 800-03859-4v2 11/10 rev. A.

  • Page 2

    -2- table of contents data fields ................................................................................................................................................................3 ✻ 56 enhanced zone programming ............................................................................

  • Page 3

    - 3 - to initialize download id and subscriber account number for downloading: ✻ 96 resets all subscriber account numbers and csid in preparation for an initial download. To load a default set: ✻ 97 enter a number 1-4 corresponding to the selected default table (see the installation instructions for...

  • Page 4

    - 4 - data field display function& programming options [ ] = programmed table 1 default values zone sounds and timing (✻31– ✻39) 31 31 31 31 single single single single alarm alarm alarm alarm snd snd snd snd single alarm sounding/zone ul installations = 0 † [0] 0 = alarm sounding per zone will be t...

  • Page 5

    - 5 - data field display function& programming options [ ] = programmed table 1 default values 39 39 39 39 cross zone timer cross zone timer cross zone timer cross zone timer cross zone timer † [0] value time window value time window 0 = no cross zoning 8 = 2 minutes 1 = 15 seconds 9 = 2 minute, 15 ...

  • Page 6

    - 6 - data field display function& programming options [ ] = programmed table 1 default values 46 46 46 46 follow me phone follow me phone follow me phone follow me phone # “follow me” reminder phone number enter up to 24 digits; do not fill unused spaces. If fewer than 24 digits entered, pressing ✻...

  • Page 7

    - 7 - data field display function& programming options [ ] = programmed table 1 default values 51 51 51 51 period period period period t tt test est est est rep rep rep rep periodic test report (enter test code in field ✻64) † [0] 0 = none; 1 = 24 hours; 2 = weekly; 3 = 30 days 52 52 52 52 test test...

  • Page 8

    - 8 - data field display function& programming options [ ] = programmed table 1 default values system status report codes (✻59–✻68) 59 59 59 59 exit exit exit exit error error error error rep rep rep rep exit error report code [1] 60 60 60 60 trouble trouble trouble trouble rep rep rep rep code code...

  • Page 10

    - 10 - data field display function& programming options [ ] = programmed table 1 default values 90 90 90 90 evnt log options evnt log options evnt log options evnt log options event logging note: system messages are logged when any non-zero selection is made. [3] 0 = none; 1 = alarm/alarm restore; 2...

  • Page 11

    - 11 - ✻ ✻ ✻ ✻ 56 enhanced zone programming procedure this interactive menu mode is used to program zone numbers, zone types, alarm and report codes, and to identify the type of loop input device and can be used for entering 5800 series transmitter serial numbers. Press ✻ 56 while in programming mod...

  • Page 12

    - 12 - ✻ ✻ ✻ ✻ 56 enhanced zone programming procedure 1111al al al al a094 a094 a094 a094----4129 4129 4129 4129 enroll mode enroll mode enroll mode enroll mode enroll loop number or loop & serial number via rf learning (continued) the serial number of the device that has been learned will be displa...

  • Page 13

    - 13 - ✻ ✻ ✻ ✻ 56 enhanced zone programming procedure 1111c c c c zone descriptor zone descriptor zone descriptor zone descriptor voice descriptor 0 = skip to next zone (a) 1 = enter descriptor mode (existing zone descriptor will be announced, then descriptor 1 will be repeated) 1111d note: system d...

  • Page 14

    - 14 - ✻ ✻ ✻ ✻ 56 enhanced zone programming worksheet fill in the required data on this worksheet, then follow the programming procedure. Zones on control: see explanation of headings (defaults shown are for table 1) zone zone no. Zone alarm rpt code vocabulary description (a 01) type (zt) (hex) (rc...

  • Page 16

    - 16 - ✻ ✻ ✻ ✻ 80 device programming use this mode to program powerline carrier devices or zone lists for chime by zone feature. It is also used to program the remote services multi-mode (e-mail) event triggers. Press ✻ 80 while in programming mode. Note: entering a number other than the one specifi...

  • Page 17

    - 17 - ✻ ✻ ✻ ✻ 81 zone lists use this mode to define zone lists for powerline carrier devices and/or for the chime by zone feature. Press ✻ 81 while in programming mode. Note: entering a number other than the one specified may give unpredictable results. 81 81 81 81 zone zone zone zone lists lists l...

  • Page 18

    - 18 - powerline carrier devices worksheet for ✻ ✻ ✻ ✻ 80 and ✻ ✻ ✻ ✻ 81 applicable only if powerline carrier devices are to be used, or chime-by-zone feature is used. Ul powerline carrier devices have not been evaluated by ul. ✻ 80 output devices fill in the required data on the worksheet on below ...

  • Page 19

    - 19 - ✻ ✻ ✻ ✻ 83 enhanced sequential mode use this mode to enter transmitter serial numbers. Press ✻83 while in programming mode. 83 83 83 83 enhancd enhancd enhancd enhancd seq seq seq seq mode mode mode mode enhanced sequential mode 0 = exit mode, upon which this prompt blinks. 1 = enter mode a a...

  • Page 20

    - 20 - ✻ ✻ ✻ ✻ 84 assign zone voice descriptors use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when the system announces any event involving a zone number. Press ✻ 84 while in programming mode. Note: entering a number other than the one specifie...

  • Page 21

    - 21 - ✻ ✻ ✻ ✻ 85 record custom voice descriptors use this mode to record up to 5 custom voice descriptors for use with zone announcements. Press ✻ 85 while in programming mode. Note: entry of a number other than one specified will give unpredictable results. 85 85 85 85 rec rec rec rec voice voice ...

  • Page 22

    - 22 - 5800 series loop numbers loop 1 5806/5806w3/5807 5808/5808lst/5808w3 enroll as "rf" loop 1 5809 enroll as "rf" 5 8 1 8 enroll as "rf" loop 1 loop 1 5814 enroll as "rf" 5800-002-v0 loop 1 (motion) 5897 enroll as "rf" 5 8 9 0 / 5 8 9 0 p i enroll as "rf" loop 1 loop 1 5 8 0 2 m n enroll as "ur"...

  • Page 23

    - 23 - safewatch quickconnect plus control defaults by activating *96, field 43, and 44 will be changed to 15, 15, 15, 15. Function default *20 installer code 6321 *21 quick arm enable 1 *22 keypad backlight timeout 0 *23 forced bypass 1 *24 rf house id code 0,0 *25 powerline carrier device house co...

  • Page 24

    85db siren disable switch u l i n s ta l l a t io n s t h e m in im u m w ir e s iz e u s e d f o r t e l e p h o n e in s ta l l a t io n s m u s t b e # 2 6 g a g e w a r n in g t o p r e v e n t r is k o f s h o c k , d is c o n n e c t t e l e p h o n e l in e a t t e l e c o m j a c k b e f o r...