A&D AD-8923-CC Instruction Manual - Error Status Flag
21
Requesting initialization from the master station
When requesting the initial data setting to the AD-8923-CC from the master
station, turn the request flag of initial data setting (RY0019) ON while the
remote READY flag (RX001B) is active.
The AD-8923-CC turns the remote READY flag (RX001B) OFF and
performs initial data settings. When initial data settings are complete, the
reply flag of initial data setting (RX0019) is turned ON.
Turn OFF the request flag of initial data setting (RY0019) in the master
station.
Performance of request flag of initial data setting
Error status flag
When an error occurs to the AD-8923-CC, the remote READY flag
(RX001B) becomes inactive and the error status flag (RX001A) becomes
active to inform the master station of the error occurrence.
The master station requests to reset the error status flag, by activating the
request flag of error reset (RY001A).
Resetting the error status flag
Request flag of initial data setting (RY0019)
Remote READY flag (RX001B)
Reply flag of initial data setting (RX0019)
When the remote READY flag
(RX001B) is ON, the request flag
of initial data setting (RY0019) is
turned ON.
When the reply flag of initial data
setting (RX0019) is ON, the
request flag of initial data setting
(RY0019) is turned OFF.
When the reply flag of initial data
setting (RX0019) is OFF, the remote
READY flag (RX001B) is turned ON
again.
Remote READY flag (RX001B)
Error status flag (RX001A)
Request flag of error reset (RY001A)
Error code (RWr0002)
Error code (RWr0002) and
Error sub-code (RWr0003)
will be cleared to 0.
Error sub-code (RWr0003)