1 printed in u.S.A. 2526 0501 copper boilers for hydronic heating and hot water supply caution text printed or outlined in red contains information relative to your safety. Please read thoroughly before installing and using this appliance. Part no. 211257-000 rev. 0 a division of a. O. Smith corpora...
2 rough-in dimensions figure 1. Important! Refer to "installation clearances" section of manual (page 7) for recommended service clearances prior to boiler placement. Top view left side table 2. Rough - in dimensions a b c d e f model inches c m inches c m inches c m inches c m inches c m inches c m...
3 table 4: heat exchanger pressure drop gb models-flow, head loss and temperature rise 20 deg. F rise 30 deg. F rise 40 deg. F rise maximum flow rate minimum flow rate gpm pd-ft gpm pd-ft gpm pd-ft gpm pd-ft deg. F gpm pd-ft deg. F model head head head head rise head rise gb - 1000 83.16 5.1 55.4 2....
4 precautions if the unit is exposed to the following, do not operate until all corrective steps have been made by a qualified serviceman: 1. Exposure to fire. 2. If damaged. 3. Firing without water. 4. Sooting. If the boiler has been exposed to flooding, it must be replaced. Liquid petroleum models...
5 example: a genesis boiler is rated at 1,300,000 btu/hr. Input at sea level. At an altitude of 5,000 (1500m), the prejet orifices will decrease the input rate by 20% (= 4% x 5) to a new rating of 1,040,000 btu/hr. (= 80% x 1,300,000 btu/hr.) the input reduction is achieved by the prejet orifices th...
6 probe is not supplied with the gb models. A tank probe can be used as an option to control loop temperature and unit staging. Additionally, the inlet temperature probe can be used as the loop thermostat in some heating (gb) applications. These types of controls connect to designated wires in the j...
7 • the boiler must not be installed on carpeting. • the boiler should not be located in an area where it will be subject to freezing. • the boiler should be located near a floor drain. • the boiler should be located in an area where leakage from the boiler or connections will not result in damage t...
8 provided for proper combustion and ventilation in accordance with the national fuel gas code, ansi z223.1 or can/csa-b149.1 and .2 (latest editions) or applicable provisions of the local building codes. An insufficient supply of air may result in a yellow, luminous burner flame, carboning or sooti...
9 1. Seal any unused opening in the common venting system. 2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other unsafe condition. 3. Isolate the space containing the appliance(s) remaining connected...
10 standard vent - vertical (category i) important! Vent pressure must be maintained between -0.02" w.C. And -0.04" w.C. At 24" (61.0 cm) above boiler collar. • connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for category i app...
11 table 8. Standard horizontal venting (category iii) standard vent - horizontal (category iii) warning: no substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants. • a maximum of two elbows can be used on inlet and outle...
12 direct vent - vertical (category i) table 9. Direct vent (vertical exhaust configurations) • connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for category i appliances shall be determined per the latest edition of the nationa...
13 direct vent - horizontal (category iii) warning: no substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants. • a maximum of two elbows can be used on inlet and outlet vent piping respectively. Each elbow is equal to 10 ...
14 standard (vertical) venting, category i this boiler may be vented according to table 7 (also see figure 5). At least type b venting must be used with the standard venting option (thru-the-roof) using the national fuel gas code vent tables.* type b vent pipe cannot be used if the boiler is vented ...
15 conventional space heating installation modern fin type boilers are exceptionally fast heating units. The low water volumes in relation to firing rates require special attention to water flow rates for smooth, efficient operation. These considerations for the a. O. Smith copper heat exchanger boi...
16 figure 10. Single or multiple boiler installation diagram the circuits should be spaced on the header at a minimum of 3" (7.6 cm) center to center. Install a balancing cock in each return line. Manifold headers are recommended for split systems with or without zone valves and also those installat...
17 mandatory but offers smooth, efficient operation of a modern system. Normal use of flow control valves is required to prevent cross circulation of zones as with any multiple pump system. Large systems with multiple boilers should include main water temperature controls (with or without outdoor re...
18 one genesis (model gw) hot water supply boiler with horizontal tank figure 12. Tank probe installation. Pressure relief valve rating should not exceed pressure capacity of any component in the system. Piping should conform to local codes. Ball valves are shown for servicing boiler. However, local...
19 one genesis (model gw) hot water supply boiler with vertical tank figure 13. Single boiler with vertical tank. Pressure relief valve rating should not exceed pressure capacity of any component in the system. Piping should conform to local codes. Ball valves are shown for servicing boiler. However...
20 t able 13. Suggested pipe size for multiple gas appliances (natural) t able 14. Suggested pipe size for multiple gas appliances (prop ane gas) length of pipe in feet (metres) maximum cap acity of pipe in btu/hr and kw for gas pressures of 14 in. W .C. (0.5 p si) or less and a pressure drop of 0.5...
21 gas connections warning this boiler is not intended to operate at gas supply pressure other than shown on the rating plate. Exposure to higher gas supply pressure may cause damage to gas valves which can result in fire or explosion. If overpressure has occurred such as through improper testing of...
22 wiring connections all electrical work must be installed in accordance with the most recent version of the national electrical code/canadian electrical code and must conform to local regulations. An electrical ground is required to reduce risk of electric shock or possible electrocution. Make the...
23 purging of gas line gas line purging is required with new piping or systems in which air has entered. Caution purging should be performed by persons experienced in this type of gas service to avoid risk of fire or explosion. Purge discharge must not enter confined areas or spaces where ignition c...
24 lighting instructions for the g(b/w) 1000 through 2500 models a. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. Before lighting: smell all around the appliance area for gas. Be sure to ...
25 lighting instructions for the g(b/w) 1000 through 2500 models for your safety read before operating operating instructions to turn off gas to appliance warning: if you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life...
26 control system description of multi-stage firing system the central control board (ccb) is responsible for staging the ignition control boards (icb) and monitoring safety limit devices, control of circulation pump, power vent, alarm output and iri gas valves (only on iri models). The thermostat a...
27 switch "d" on the central control board is placed in the "on" position, it will show the temperature at the tank probe. (see figure 14.) the push buttons on the display board allow the user to program and view several system parameters described in the following text. The display board is connect...
28 figure 16. Display board high gas fail: gas pressure at manifold too high lwco: low water cutoff activated. Not enough water. Power vent fail: not enough air to close switch stage one: failure on stage one stage two: failure on stage two stage three: failure on stage three stage four: failure on ...
29 1. Press the select push-button on the display board until both the set-pt led and inlet water temperature led (see figure 16) are illuminated. 2. The led display will show the current set-point temperature. 3. Press and hold the adjust push-button. The displayed temperature will either increase ...
30 procedure for setting pump delay the controller is factory set with a 45 second post circulate function. With the display board, the user has the capability to choose between a 45, 90, or 180 second post circulate time period, or turn the pump on continuously. This provides flexibility in selecti...
31 drop out first followed by stages three, two and one. To achieve maximum efficiency, stages will reignite if the system water temperature drops below the stage set point minus the set point differential. Note: once a stage is satisfied, the blower associated with that stage will allow a 25 second...
32 with this boiler should receive periodic (every six months) inspection to assure proper operation. A low water cutoff device of the float type should be flushed every six months. Periodic checks, at least twice a year, should be made for water and/or gas leaks. More frequent inspections may be ne...
33 caution if heat exchanger maintenance requires tubing replacement, special provisions shall be taken to ensure that the damaged tubes are carefully removed. Replacement tubes must be properly installed and expanded into the rolled tube tub. Over-rolling, misalignment of tubes or improper tighteni...
34 for additional information please refer to the user’s manual supplied with the boiler or contact: a.O. Smith technical services 7 a.M. To 7 p.M. Central time at: 1-800-527-1953 our internet site is another source of information 24 hours a day. Http://www.Hotwater.Com table 19. Error code chart ge...
35 new boiler limited warranty a. O. Smith corporation, the warrantor, extends the following limited warranty to the owner of this hydronic boiler: 1. If within ten years after initial installation of the boiler, the heat exchanger shall prove upon examination by the warrantor to be defective in mat...