A.O. Smith BTH 120 Service Handbook - Make-Up Air
Other manuals for BTH 120:
Service handbook
Manual is about: COMMERCIAL GAS HIGH EFFICIENCY WATER HEATERS BTH 120 THRU 500
SERIES 200/201
of
65
A. O. Smith Water Products Company
Service Handbook
Irving, Texas 2000©
Training Department
8
MAKE-UP AIR
HORIZONTAL DUCTS
When the heater is installed in an interior room with no roof access for vertical ducts, horizontal make-up
ducts should be installed. When using horizontal ducts, two openings are required - within
12 inches (30 cm.) of the top of the enclosure and one within 12 inches (30 cm.) of the bottom of the enclo-
sure. Each opening shall have a free area of not less than 1 square inch per 2000 BTUH of the total input of all
appliances within the enclosure.