AB Quality PowerFlex 700S Quick Start Manual

Summary of PowerFlex 700S

  • Page 1

    Quick start powerflex ® 700s drive introduction this document is designed to guide you through the basic steps needed to install, start-up and program the powerflex 700s drive. The information provided does not replace the user manual and is intended for qualified personnel only. For detailed powerf...

  • Page 2

    2 powerflex® 700s drive emc instructions ce conformity conformity with the low voltage (lv) directive and electromagnetic compatibility (emc) directive has been demonstrated using harmonized european norm (en) standards published in the official journal of the european communities. Powerflex drives ...

  • Page 3

    Powerflex® 700s drive 3 general notes • if the adhesive label is removed from the top of the drive, the drive must be installed in an enclosure with side openings less than 12.5 mm (0.5 in.) and top openings less than 1.0 mm (0.04 in.) to maintain compliance with the lv directive. • the motor cable ...

  • Page 4

    4 powerflex® 700s drive mounting clearances figure 1 minimum mounting clearance requirements operating temperatures powerflex 700s drives are designed to operate in a surrounding air temperature range of 0 ° to 40 ° c. To operate the drive in installations with surrounding air temperature between 41...

  • Page 5

    Powerflex® 700s drive 5 figure 2 powerflex 700s frame 1-3 (frame 1 shown) ➊ weights include him, drivelogix controller with controlnet daughtercard, hi-resolution encoder option, and 20-comm-c controlnet adapter c a d 12.5 (0.49) 7.0 (0.28) typ b e 7.0 (0.28) typ 7.0 (0.28) d dimensions are in milli...

  • Page 6

    6 powerflex® 700s drive figure 3 powerflex 700s bottom view dimensions, frame1 & 2 187.9 (7.40) 190.4 (7.50) 136.1 (5.36) 25.5 (1.00) 108.0 (4.25) 140.9 (5.55) 135.0 (5.31) 161.0 (6.34) 173.5 (6.83) 152.5 (6.00) 132.5 (5.22) 72.5 (2.85) 28.7 (1.13) dia. 3 places 137.7 (5.42) 171.0 (6.73) 201.4 (7.93...

  • Page 7

    Powerflex® 700s drive 7 figure 4 powerflex 700s frame 3 bottom view dimensions 167.9 (6.61) 170.3 (6.70) 159.7 (6.29) 153.9 (6.06) 130.5 (5.14) 87.7 (3.45) 94.0 (37.0) 131.0 (5.16) 162.0 (6.38) 202.2 (7.96) 252.0 (9.92) 162.9 (6.41) 187.3 (7.37) 37.3 (1.47) dia. 2 places 28.7 (1.13) dia. 2 places 22...

  • Page 8

    8 powerflex® 700s drive figure 5 powerflex 700s frame 4 dimensions ➊ weights include him and standard i/o. Frame a (max.) b c (max.) d e approx. Weight ➊ kg (lbs.) drive drive & packaging 4 220.8 (8.69) 758.8 (29.9) 201.8 (7.94) 192.0 (7.56) 741.7 (29.2) 28.4 (62.5) 29.03 (63.9) c e 8.0 (0.31) b 8.0...

  • Page 9

    Powerflex® 700s drive 9 figure 6 powerflex 700s frame 5 dimensions ➊ weights include him and standard i/o. 96.0 (3.77) 159.0 (6.26) 184.0 (7.24) 229.5 (9.04) 62.7 (2.47) dia. 2 places 22.2 (0.87) dia. 2 places 34.9 (1.37) dia. 2 places 110.0 (4.33) 150.0 (5.91) 215.0 (8.46) 280.0 (11.02) 320.0 (12.6...

  • Page 10

    10 powerflex® 700s drive figure 7 powerflex 700s frame 6 dimensions ➊ weights include him and standard i/o. B 126.3 (4.97) 8.5 (0.33) e lifting holes - 4 places 12.7 (0.50) dia. D c a 360.6 (14.20) detail 18.0 (0.71) 8.5 (0.33) 369.0 (14.53) 349.5 (13.76) 8.0 (0.31) 6.50 (0.26) 2 places 466.7 (18.38...

  • Page 11

    Powerflex® 700s drive 11 wiring recommendations since most start-up difficulties are the result of incorrect wiring, take every precaution to assure the wiring is correct. Read and understand all items in this section before beginning installation. Power cable types acceptable for 200-600 volt insta...

  • Page 12

    12 powerflex® 700s drive shielded cable may also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance of shielded cable may help extend the distance the motor can be located from the drive without the addition of motor protective devices ...

  • Page 13

    Powerflex® 700s drive 13 figure 8 power terminal block location br1 b shld shld v/t2 w/t3 pe r/l1 s/l2 t/l3 aux in+ aux out– optional communications module 75c cu wire 6 awg [10mm 2 ] max. 12 in. Lbs. 1.4 n-m } torque wire strip control power br1 br2 dc+ dc– pe u/t1 v/t2 w/t3 r/l1 s/l2 t/l3 use 75c ...

  • Page 14

    14 powerflex® 700s drive table d power terminal block specifications figure 9 power and ground wiring no. Name frame description wire size range (1) torque maximum minimum maximum recommended ➊ power terminal block 1 all power terminals 4.0 mm 2 (10 awg) 0.5 mm 2 (22 awg) 1.7 n-m (15 lb.-in.) 0.8 n-...

  • Page 15

    Powerflex® 700s drive 15 figure 10 power terminal block br1 br2 dc+ dc– pe u (t1) v (t2) w (t3) r (l1) s (l2) t (l3) 240 vac 120 vac 0 vac pe pe w/t3 v/t2 precharge resistor fuse – fwp-15a14f (common bus drives w/precharge only) u/t1 dc– dc+ br1*/ dc+ br2* ps– ps+ 240 vac 120 vac 0 vac pe pe w/t3 v/...

  • Page 16

    16 powerflex® 700s drive table e terminal block designations control wiring important points to remember about i/o wiring: • always use copper wire. • wire with an insulation rating of 600v or greater is recommended. • control and signal wires should be separated from power wires by at least 0.3 met...

  • Page 17

    Powerflex® 700s drive 17 wiring the main control board i/o terminals terminal blocks tb1 and tb2 contain connection points for all inputs, outputs and standard encoder connections. Both terminal blocks reside on the main control board. Remove the terminal block plug from the socket, and make connect...

  • Page 18

    18 powerflex® 700s drive table g tb1 - row t (top) terminals table h tb1 - row b (bottom) terminals terminal signal description related pa ra m et er t11 power supply 24v dc return (-) power and common for pre charge and enable inputs. (1) inputs may sink or source. (2) rating: 100 ma maximum. T10 p...

  • Page 19

    Powerflex® 700s drive 19 table i tb2 - row t (top) terminals table j tb2 - row b (bottom) terminals terminal signal description relat ed pa ra m et er t13 encoder signal a primary encoder interface. 5 or 12v dc switch selectable (1) , nominal current draw per channel @ 12v dc 45 ma, @5v dc 32 ma 222...

  • Page 20

    20 powerflex® 700s drive synchlink synchlink provides high-speed synchronization and communication between multiple powerflex 700s drives (or other products with synchlink capability). Refer to the synchlink design guide (1756-td008) when planning and connecting the synchlink network. Class 1 led pr...

  • Page 21

    Powerflex® 700s drive 21 i/o wiring examples this section provides basic information to wire the powerflex 700s. Table k digital wiring examples the following definitions are used throughout this section: source • apply positive voltage through the device to the input or output. • connect the input ...

  • Page 22

    22 powerflex® 700s drive auxiliary output - relay contact output auxiliary output - sourcing configuration using relay out to annunciate “drive running:” • link the status word to the relay control par 841 [relay out data] (the destination) linked to par 155 [logic status] (the source) • set par 842...

  • Page 23

    Powerflex® 700s drive 23 table l analog wiring examples table m encoder wiring example analog i/o connection example analog inputs - +/-10v dc or +/-1.0v dc (dip switch setable) terminate shields at the analog source if analog common is available used for speed reference and speed trim analog inputs...

  • Page 24

    24 powerflex® 700s drive start-up check list this section describes how you start-up the powerflex 700s. Before applying power to the drive ❏ 1. Confirm that motor wires are connected to the correct terminals and are secure. ❏ 2. Confirm that encoder wires are connected to the correct terminals and ...

  • Page 25

    Powerflex® 700s drive 25 applying power to the drive ❏ 6. Apply ac power and control voltages to the drive. Examine the power (pwr) led. Steady green power has been applied to the drive and no faults are present. ❏ 7. Examine the status (sts) led. Verify that it is flashing green. If it is not in th...

  • Page 26

    26 powerflex® 700s drive table o common start-up faults steady red a fault has occurred. Cycle the power. If the light continues to be steady red, replace the drive. Alternately flashing red/yellow a non-resettable, terminal fault has occurred. The drive needs to be replaced. If any digital input is...

  • Page 27: 0.0

    Powerflex® 700s drive 27 assisted start-up this routine prompts you for information that is needed to start-up a drive for most applications, such as line and motor data, commonly adjusted parameters and i/o. The assisted start-up routine asks simple yes or no questions and prompts you to input requ...

  • Page 28

    28 powerflex® 700s drive note: in 2-wire mode, the drive will start when the him “start” is pressed and stop when the him “start” is released. The recommended mode of use for the start-up rountine is 3-wire control, parameter 153 [control options], bit 8 set to “1”. Powerflex 700s start-up motor con...

  • Page 29

    Powerflex® 700s drive 29 status indicators table p drive status indicator descriptions # name color state description dr ive po w er s tr uc tu re ➊ pwr (power) green steady illuminates when power is applied to the drive. ➋ sts (status) green flashing drive ready, but not running & no faults are pre...

  • Page 30

    30 powerflex® 700s drive troubleshooting see table o on page 26 for typical start up faults. For a complete listing of faults and alarms, refer to the powerflex 700s user manual. A fault is a condition that stops the drive. There are two fault types. Him indication the him also provides visual notif...

  • Page 31

    Powerflex® 700s drive 31 technical support available online you can access the complete powerflex™ 700s user manual online at: http://www.Theautomationbookstore.Com/ powerflex™ 700s and drivelogix™ technical support is available online important: you are encouraged to navigate our free website as pa...

  • Page 32

    Www.Rockwellautomation.Com corporate headquarters rockwell automation, 777 east wisconsin avenue, suite 1400, milwaukee, wi, 53202-5302 usa, tel: (1) 414.212.5200, fax: (1) 414.212.5201 headquarters for allen-bradley products, rockwell software products and global manufacturing solutions americas: r...