ABB 4234 600 Instruction Manual

Manual is about: Power Supply Unit

Summary of 4234 600

  • Page 1

    4234 600 series power supply unit instruction manual models 4234 600 & 4234 601.

  • Page 2

    Abb limited the company abb ltd. Is an established world force in the design and manufacture of instrumentation for industrial process control, flow measurement, gas and liquid analysis and environmental applications. As a part of abb, a world leader in process automation technology, we offer custom...

  • Page 3

    1 1.1 general this instruction manual describes the installation and operation of the 4234 600 series power supply unit (psu), designed to provide a stabilised (optional 500, 400, 350, 250 or 180 ma) d.C. Supply for operation of a single katharometer unit and an auxiliary 10 v d.C. Supply for kathar...

  • Page 4

    2 supply: model 4234600 ............... 230 v a.C., 50/60 hz model 4234601 ............... 115 v a.C., 50/60 hz power consumption katharometer .................. 3.5 w maximum katharometer with temperature control ..... 13 w maximum fuse ratings: l & n ................................ 250 ma (20 x 5...

  • Page 5

    3 fig. 3.1 psu dimensions fig. 3.2 typical identification labels and locations 3 mechanical installation a b b l i m i t e d oldends lane, stonehouse, glos. England gl10 3ta code 4234/600xx serial no voltage 230 vac watts year manuf. Manufactured by: n4006 ✔ the psu must be mounted in a clean, dry, ...

  • Page 6

    4 4 electrical installation or 1– +2 c501 4 – 1+ 8 – 3 – 2+ - + power supply unit 4234600/601 katharometer types 6515 6517 6518 6520 6522 6524 7 + - + ma o/p 10v o/p for temperature controlled katharometer block type 6518, 6520, 6524 mains in 4234 600 – 230 v a.C. Or 4234 601 – 115 v a.C. 4689 displ...

  • Page 7

    5 to gain access, remove the four screws and lift off the cover. Fig. 4.2 psu cover removal tb1 t1 f2 f3 6 8 10 230 v 115 v l n e 115 v a.C. Or 230 v a.C. Supply see caution opposite tighten cable gland m5 earth stud fig. 4.4 connecting outputs fig. 4.3 connecting to a.C. Supply 4 electrical install...

  • Page 8

    6 5 servicing 5.1 fuse replacement there are no serviceable components in these psu's other than to replace the fuses – see fig. 5.1. These fuses must be replaced only with those stated in the specification. If a fault occurs the psu should be returned to the nearest abb service centre, or returned ...

  • Page 9

    7 notes.

  • Page 10

    8 …notes.

  • Page 11

    Products & customer support products automation systems • for the following industries: – chemical & pharmaceutical – food & beverage – manufacturing – metals and minerals – oil, gas & petrochemical – pulp and paper drives and motors • ac and dc drives, ac and dc machines, ac motors to 1kv • drive s...

  • Page 12

    Im/4234600 issue 1 the company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. Printed in uk (01.02) © abb 2002 abb ltd. Oldends lane, stonehouse gloucestershire, gl10 3ta uk tel: +44 (0)1453 826 661 fax: +44 (0)1...