    Your partner in maintenance at our premises in wrocław, we have a fully equipped servicing facility. Here we perform all the repair works and test each later sold unit. Our trained employees, equipped with a wide variety of tools and having several testing stands at their disposal, are a guarantee o...

  • Page 3: Hardware Manual

    Acs/acc/acp 601 ac drives 3 to 150 hp (2.2 to 110 kw) act par func drive enter loc rem reset ref acs 600 acs 600 hardware manual this manual includes • safety • installation • maintenance • product information.

  • Page 5: Hardware Manual

    1998 abb industrial systems. All rights reserved. Acs/acc/acp 601 ac drives 3 to 150 hp (2.2 to 110 kw) hardware manual this manual concerns the acs 601, acc 601 and acp 601 ac drives. In the text, they are collectively referred to as acx 601. Acs601-5.0-us-04 3aua 489002b4973 r0101 rev a effective:...

  • Page 7: Safety Instructions

    Acs/acc/acp 601 drives acx=acs/acc/acp iii safety instructions overview this chapter states the safety instructions which must be followed when installing, operating and servicing the acx 600. If neglected, physical injury and death may follow, or damage may occur to the ac drive, the motor and driv...

  • Page 8

    Safety instructions iv acx=acs/acc/acp acs/acc/acp 601 drives installation and maintenance safety these safety instructions are intended for all work on the acx 600. In addition to the instructions given below, there are more safety instructions on the first pages of the appropriate hardware manual....

  • Page 9

    Safety instructions acs/acc/acp 601 drives acx=acs/acc/acp v warning! There are several automatic reset functions in the acx 600. If selected, they reset the unit and resume operation after a fault. These functions should not be selected if other equipment is not compatible with this kind of operati...

  • Page 10

    Safety instructions vi acx=acs/acc/acp acs/acc/acp 601 drives emergency stop devices the person responsible for the overall design and operation of the driven process must make sure that the installation includes emergency stop devices and any other safety equipment that may be needed. Pressing the ...

  • Page 11

    Safety instructions acs/acc/acp 601 drives acx=acs/acc/acp vii voltage of the pulses is approximately 1.35 times the input line voltage with a very short rise time. The voltage of the pulses can be almost double at the motor terminals, depending on the properties of the cable between the drive and t...

  • Page 12

    Safety instructions viii acx=acs/acc/acp acs/acc/acp 601 drives without filter below is a diagram of v pk and dv/dt as a function of cable length when no dv/dt filter is used. With dv/dt filter below is a diagram of v pk and dv/dt as a function of cable length with dv/dt filter at the output of the ...

  • Page 13

    Safety instructions acs/acc/acp 601 drives acx=acs/acc/acp ix 600 make sure that the capacitors and the acx 600 are not charged simultaneously to avoid voltage surges which might damage the unit. Output contactors if a contactor is used between the output of the acx 600 and the motor with dtc contro...

  • Page 14

    Safety instructions x acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 15: Table of Contents

    Acs/acc/acp drives acx=acs/acc/acp xi table of contents safety instructions warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Iii warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 16

    Acs/acc/acp drives acx=acs/acc/acp xii conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 armored cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 17

    Acs/acc/acp drives acx=acs/acc/acp xiii materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-20 disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 18

    Xiv acx=acs/acc/acp acs/acc/acp drives.

  • Page 19: Chapter 1 – Introduction

    Acs/acc/acp 601 drives acx=acs/acc/acp 1-1 chapter 1 – introduction general the acs 600 product family of three phase ac drives includes • the acs 600 (for most applications) • the acp 600 (for positioning, synchronizing and other high-precision control applications) • the acc 600 (for crane drive a...

  • Page 20

    Chapter 1 – introduction 1-2 acx=acs/acc/acp acs/acc/acp 601 drives figure 2-1. Acx 601 nameplate acx 601 type code the meaning of main selections of acx 601 type code characters is given in the table below. Not all selections are available for all types. More information on selections is available ...

  • Page 21

    Chapter 1 – introduction acs/acc/acp 601 drives acx=acs/acc/acp 1-3 inquiries any inquiries about the product should be addressed to the local distributor or abb representative, quoting the type code and the serial number of the unit. If the local abb representative cannot be contacted, inquiries sh...

  • Page 22

    Chapter 1 – introduction 1-4 acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 23

    Acs/acc/acp 601 drives acx=acs/acc/acp 2-1 chapter 2 – mechanical installation the acx 601 should be installed in an upright position with the cooling section mounted against a flat surface. The mounting surface should be as close to vertical as possible and of non-flammable material. Sufficient roo...

  • Page 24

    Chapter 2 – mechanical installation 2-2 acx=acs/acc/acp acs/acc/acp 601 drives installation procedure appendix b contains detailed dimensional drawings showing the overall dimensions of the acx 601 drives and the sizes and locations of the mounting bolt holes or slots. The drives have four mounting ...

  • Page 25

    Chapter 2 – mechanical installation acs/acc/acp 601 drives acx=acs/acc/acp 2-3 a-12 for ambient air. If the air in the cooling duct is not clean the enclosure class of the acx 601 must be ip 54. Note the power ratings of the ip 54 units given on page a-4. To install the acx 601 in a cooling air duct...

  • Page 26

    Chapter 2 – mechanical installation 2-4 acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 27

    Acs/acc/acp 601 drives acx=acs/acc/acp 3-1 chapter 3 – electrical installation warning! The electrical installation described in this chapter should only be carried out by a qualified electrician. The safety instructions on the first pages of this manual must be followed. Negligence of these instruc...

  • Page 28

    Chapter 3 – electrical installation 3-2 acx=acs/acc/acp acs/acc/acp 601 drives be greater than 1 m Ω . 5. Measure the insulation resistance of the motor cable between the phases and between each phase and ground (pe). The insulation resistance must be greater than 1 m Ω . Disconnecting means the acx...

  • Page 29

    Chapter 3 – electrical installation acs/acc/acp 601 drives acx=acs/acc/acp 3-3 connecting cable insulation must accommodate the voltage peaks described under motor insulation requirements on page vi of the safety instructions. For drives that are rated up to 500 v, cables that have a 600 vac insulat...

  • Page 30

    Chapter 3 – electrical installation 3-4 acx=acs/acc/acp acs/acc/acp 601 drives symmetrical grounds is the best type of wiring to provide a good low impedance high frequency ground return path between the motor and the drive. This helps to prevent high frequency ground current from flowing in a poten...

  • Page 31

    Chapter 3 – electrical installation acs/acc/acp 601 drives acx=acs/acc/acp 3-5 the analog and digital input signals should be run in separate, shielded cables. Relay-controlled signals, providing their voltage does not exceed 48 v, can be run in the same cables as digital input signals. It is recomm...

  • Page 32

    Chapter 3 – electrical installation 3-6 acx=acs/acc/acp acs/acc/acp 601 drives cover removal remove the cover as illustrated in figure 3-1 on page 3-6 (frames r2 and r3), figure 3-2 on page 3-7 (frames r4 to r6), or figure 3-3 on page 3-7 (frame r7). Conduit plate attach conduits to the conduit entr...

  • Page 33

    Chapter 3 – electrical installation acs/acc/acp 601 drives acx=acs/acc/acp 3-7 figure 3-2 frames r4 to r6: removal of the cover figure 3-3 frame r7: removal of the cover 1. Remove the control panel. 2. Remove the telephone connector. 3. Remove the two screws at the lower front edge of the unit and r...

  • Page 34

    Chapter 3 – electrical installation 3-8 acx=acs/acc/acp acs/acc/acp 601 drives figure 3-4 a view of the recommended wiring configuration. Figure 3-5 frame r7: ring lugs t2 t3 t1 signals metallic conduit in the r7 frame, bolt connections are provided for connecting wires with ring lugs. Crimp ring lu...

  • Page 35

    Chapter 3 – electrical installation acs/acc/acp 601 drives acx=acs/acc/acp 3-9 figure 3-6 replacing the front cover control panel in remote use connect the control panel cable to terminal x19 of the namc-11, or with namc-03 board to terminal x28 of the nioc board (x300 of the niocp board). Frames r4...

  • Page 36

    Chapter 3 – electrical installation 3-10 acx=acs/acc/acp acs/acc/acp 601 drives pulse encoder insulation (acp 600) the pulse encoder shall be insulated electrically from stator or rotor to prevent forming of current path through the pulse encoder. The usual coupling-type encoder must have an electri...

  • Page 37

    Chapter 3 – electrical installation acs/acc/acp 601 drives acx=acs/acc/acp 3-11 connection examples txd rxd t r fieldbus adapter module acx 600 ch0 txd rxd namc r t nioc/ the terminals for the power supply connection vary. Consult adapter module manual. T r i/o extension module acx 600 namc nioc nio...

  • Page 38

    Chapter 3 – electrical installation 3-12 acx=acs/acc/acp acs/acc/acp 601 drives connection examples txd rxd t r acs 600* namc nioc nioc terminal x23 the terminals for the power supply connection vary. Consult module manual. Ch2 * the acp 600 supports the ntacp double pulse encod- er instead. See nta...

  • Page 39

    Chapter 3 – electrical installation acs/acc/acp 601 drives acx=acs/acc/acp 3-13 braking chopper refer to the braking choppers installation and start-up guide for braking chopper installation and application information. Warning! The brake control terminals (udc+, udc-, r+ and r- terminals) carry a d...

  • Page 40

    Chapter 3 – electrical installation 3-14 acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 41

    Acs/acc/acp 601 drives acx=acs/acc/acp 4-1 chapter 4 – installation checklist installation checklist the acx 600 mechanical and electrical installation should be checked before start-up. It is advisable to go through the checklist below together with another person. Study carefully the safety instru...

  • Page 42

    Chapter 4 – installation checklist 4-2 acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 43: Chapter 5 – Maintenance

    Acs/acc/acp 601 drives acx=acs/acc/acp 5-1 chapter 5 – maintenance the acx 600 requires minimum maintenance. Warning! The safety instructions on the first pages of this manual must be followed. Heatsink the heatsink fins pick up dust from the cooling air. The acx 600 can run into overtemperature war...

  • Page 44

    Chapter 5 – maintenance 5-2 acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 45

    Acs/acc/acp 601 drives acx=acs/acc/acp a-1 appendix a – acs/acc/acp 601 technical data iec ratings for ip2/22 enclosures below are the iec ratings for acs/acc/acp 601 with 50 hz and 60 hz supplies. Acx = acs/acc/acp. The 690 v series is not available for acp 600. Symbols are described following the ...

  • Page 46

    Appendix a – acs/acc/acp 601 technical data a-2 acx=acs/acc/acp acs/acc/acp 601 drives rating table continued pump and fan use (squared load) acx 601 type i 2nsq [a] s n [kva] p n [kw] p n [hp] frame size three-phase supply voltage 380 v, 400 v or 415 v acx 601-0005-3 7.6 5 3 3 r2 acx 601-0006-3 11 ...

  • Page 47

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-3 rating table continued note: the us manufactured units are labeled as -4 types. The information in this manual concerning the corresponding -5 types applies to them. Output current temperature derating the output ...

  • Page 48

    Appendix a – acs/acc/acp 601 technical data a-4 acx=acs/acc/acp acs/acc/acp 601 drives • example 2. If the ambient temperature is 122 °f, the output current for acx 601-0006-3 is first calculated at 104 °f (derating factor 92 % or 0.92 from curve 2) and the result is multiplied by factor 0.65 (see e...

  • Page 49

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-5 acx 601 type fuses a a 2 s v manufacturer type din 43620 size type din 43653 size acx 601-0005-3 acx 601-0006-4 acx 601-0006-5 16 48 660 bussmann 170m1559 000 170m1359 000/80 acx 601-0006-3 acx 601-0009-4 acx 601-...

  • Page 50

    Appendix a – acs/acc/acp 601 technical data a-6 acx=acs/acc/acp acs/acc/acp 601 drives note: fuses from other manufacturers can be used if they meet the ratings given in the table. Only ultra rapid fuses guarantee the proper protection for the rectifier semiconductors. The fuses recommended in the t...

  • Page 51

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-7 external control connections (nioc) external control connections of acs 600 with standard application software (factory macro) are below. External control connections are different with other application macros an...

  • Page 52

    Appendix a – acs/acc/acp 601 technical data a-8 acx=acs/acc/acp acs/acc/acp 601 drives external control connections (niocp) external control connections of acp 600 with niocp board are below. Terminal block x1 function specifications 1 +10 v reference voltage +10 vdc 2 k Ω ≤ r load ≤ 10 k Ω max. 10 ...

  • Page 53

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-9 enclosures, space requirements the cabinets, degrees of protection and free space requirements of acx 600 types are given below. 1) not for acp 601 units 2) the degrees of protection is specified by listing the ie...

  • Page 54

    Appendix a – acs/acc/acp 601 technical data a-10 acx=acs/acc/acp acs/acc/acp 601 drives cooling air flow requirements cooling air flow requirements are given below. Cooling air duct heat dissipations and cooling air flows of acx 601 in a cooling air duct installation are below. Acx 601 flow m 3 /h f...

  • Page 55

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-11 dimensions and weights dimensions and weights of the wall-mounted acs/acc/acp 601 units are given below. Input power connection voltage ( u 1 ): 380/400/415 vac 3- phase ± 10 % for 400 vac units 380/400/415/440/4...

  • Page 56

    Appendix a – acs/acc/acp 601 technical data a-12 acx=acs/acc/acp acs/acc/acp 601 drives u nmotor : rated motor voltage; f nmotor : rated motor frequency scalar control mode (not for acp 600): 0 to 300 hz with du/dt filter (dtc and scalar control modes): 0 to 120 hz frequency resolution: 0.01 hz cont...

  • Page 57

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-13 ambient conditions acx 600 ac drives are to be used in a heated, indoor controlled environment as specified below. 1) at sites over 1000 m (3300 ft) above sea level, the maximum output current is derated 1 % for ...

  • Page 58

    Appendix a – acs/acc/acp 601 technical data a-14 acx=acs/acc/acp acs/acc/acp 601 drives external control connections data of the external control connection boards of the acs 600 product family are given below. Acs/acc/acp 600 nioc-01 board acp 600 niocp-01 board analog inputs the advantage of the d...

  • Page 59

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-15 digital inputs acs/acp 600: six programmable digital inputs (common ground): 24 vdc, -15 % to +20 % acc 600: six digital inputs (common ground): 24 vdc, -15 % to +20 % logical thresholds: “0”, > 12 vdc “1” input ...

  • Page 60

    Appendix a – acs/acc/acp 601 technical data a-16 acx=acs/acc/acp acs/acc/acp 601 drives encoder signals characteristic of incremental encoder signals in applications using the incremental encoder (for clockwise rotation, viewed from the drive end) is presented below. Encoder input one encoder input:...

  • Page 61

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-17 application program various application programs are available for the acs 600 ac drives. In the tables of this section, the acs 600 product family program selections are referred to with the following abbreviati...

  • Page 62

    Appendix a – acs/acc/acp 601 technical data a-18 acx=acs/acc/acp acs/acc/acp 601 drives languages languages and application macros included in the acx 600 software are shown below. Not all selections are available for all types. *this selection is for the north american market. The default parameter...

  • Page 63

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-19 protection features application program dependent features of the acx 600 are listed below. Available as standard, optional preprogrammed warnings: acs 600 temperature, motor identification run, drive identificat...

  • Page 64

    Appendix a – acs/acc/acp 601 technical data a-20 acx=acs/acc/acp acs/acc/acp 601 drives applicable standards the acs 600 complies with the following standards: • en 60204-1: 1992 + corr. 1993 (iec 204-1). Safety of machinery. Electrical equipment of machines. Part 1: general requirements. Provisions...

  • Page 65

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-21 the emc directive defines the requirements for immunity and emissions of electrical equipment used in european economic area. The emc product standard en 61800-3 covers the requirements stated for drives. The acx...

  • Page 66

    Appendix a – acs/acc/acp 601 technical data a-22 acx=acs/acc/acp acs/acc/acp 601 drives use of the acx 600 in second environment without emc filtering (en 61800-3: second environment includes all establishments other than those directly connected to a low- voltage power supply network which supplies...

  • Page 67

    Appendix a – acs/acc/acp 601 technical data acs/acc/acp 601 drives acx=acs/acc/acp a-23 ul acs 600 is suitable for use in a circuit capable of delivering not more than 65 ka rms symmetrical amperes at 480 v maximum (500 v units), and at 600 v maximum (690 v units). Acs 600 provides overload protecti...

  • Page 68

    Appendix a – acs/acc/acp 601 technical data a-24 acx=acs/acc/acp acs/acc/acp 601 drives performance or breach hereof shall expire unless brought within one year of the time of accrual thereof. In no event, regardless of cause, shall abb assume responsibility for or be liable for penalties or penalty...

  • Page 69: Dimensional Drawings

    Acs/acc/acp 601 drives acx=acs/acc/acp b-1 appendix b – acs/acc/acp 601 dimensional drawings the following drawing package is effective from 5/10/98. Gland plate holes (iec units) frame r2 acx = acs/acc/acp r3 acx = acs/acc/acp r4 acx = acs/acc/acp r5 acx = acs/acc/acp r6 acx = acs/acc/acp r7 acx = ...

  • Page 70

    Appendix b – acs/acc/acp 601 dimensional drawings b-2 acx=acs/acc/acp acs/acc/acp 601 drives frame r2 air out main air out air out air in air in type (acx = acs/acc/acp) weight acx 601-0005-3 14 kg acx 601-0006-3 14 kg acx 601-0009-3 14 kg acx 601-0006-5 14 kg acx 601-0009-5 14 kg acx 601-0011-5 14 ...

  • Page 71

    Appendix b – acs/acc/acp 601 dimensional drawings acs/acc/acp 601 drives acx=acs/acc/acp b-3 frame r2 flange mounting frame r3 flange mounting.

  • Page 72

    Appendix b – acs/acc/acp 601 dimensional drawings b-4 acx=acs/acc/acp acs/acc/acp 601 drives frame r3 type (acx = acs/acc/acp) weight acx 601-0011-3 17.5 kg acx 601-0016-3 17.5 kg acx 601-0016-5 17.5 kg acx 601-0020-5 17.5 kg acx 601-0009-6/0011-6 17.5 kg acx 601-0009-6/0020-6 17.5 kg air out air in...

  • Page 73

    Appendix b – acs/acc/acp 601 dimensional drawings acs/acc/acp 601 drives acx=acs/acc/acp b-5 frame r4 type (acx = acs/acc/acp) weight acx 601-0020-3 25 kg acx 601-0025-3 25 kg acx 601-0025-5 25 kg acx 601-0030-5 25 kg acx 601-0025-6 25 kg acx 601-0030-6 25 kg.

  • Page 74

    Appendix b – acs/acc/acp 601 dimensional drawings b-6 acx=acs/acc/acp acs/acc/acp 601 drives frame r4 flange mounting frame r5/r6 flange mounting.

  • Page 75

    Appendix b – acs/acc/acp 601 dimensional drawings acs/acc/acp 601 drives acx=acs/acc/acp b-7 frame r5/r6 type (acx = acs/acc/acp) weight l1 acx 601-0030...0050-3 35 kg 190.5 acx 601-0040...0060-5 35 kg 190.5 acx 601-0040-6/-0060-6 35 kg 190.5 acx 601-0060...0070-3 50 kg 262.5 acx 601-0070...0100-5 5...

  • Page 76

    Appendix b – acs/acc/acp 601 dimensional drawings b-8 acx=acs/acc/acp acs/acc/acp 601 drives frame r7 type (acx = acs/acc/acp) weight acx 601-0100-3/-6 88 kg acx 601-0120-3 88 kg acx 601-0120-5/-6 88 kg acx 601-0140-5 88 kg.

  • Page 77

    Appendix b – acs/acc/acp 601 dimensional drawings acs/acc/acp 601 drives acx=acs/acc/acp b-9 conduit plates (usa version) the following figures show the conduit plate (bottom view) of the different size acs 600 units: at least three separate rigid metallic conduits must be used; one each for input p...

  • Page 78

    Appendix b – acs/acc/acp 601 dimensional drawings b-10 acx=acs/acc/acp acs/acc/acp 601 drives figure 2-1 conduit entry plates, r5- r7 usa version r7 r5 3/4” 1-1/4” 1-1/4” 1-1/4” r6 3/4” 1-1/2” 1-1/2” 1-1/4” 2-1/2” 2-1/2” 2-1/2”.

  • Page 79

    Appendix b – acs/acc/acp 601 dimensional drawings acs/acc/acp 601 drives acx=acs/acc/acp b-11 acp 601 control cable connections the deliveries include a bag with four clamps, screws and copper tape (frame size r4 also an assembly plate). Clamp the control and encoder cables as explained below. If mo...

  • Page 80

    Appendix b – acs/acc/acp 601 dimensional drawings b-12 acx=acs/acc/acp acs/acc/acp 601 drives acp 601 frame r4 clamp assembly plate stripped part of cable grounding rail encoder cable screw for encoder cable grounding.

  • Page 81

    Appendix b – acs/acc/acp 601 dimensional drawings acs/acc/acp 601 drives acx=acs/acc/acp b-13 acp 601 frame r5/r6 clamp stripped part of cable grounding rail encoder cable screw for encoder cable grounding.

  • Page 82

    Appendix b – acs/acc/acp 601 dimensional drawings b-14 acx=acs/acc/acp acs/acc/acp 601 drives.

  • Page 83

    Acs/acc/acp 601 drives acx=acs/acc/acp c-1 appendix c – iec installation iec installations this appendix is a supplement to chapter 3 – electrical installation. It contains additional information to be used in iec installations. For installations requiring ce compliance, refer also to the section en...

  • Page 84

    Appendix c – iec installation c-2 acx=acs/acc/acp acs/acc/acp 601 drives motor cable shield to effectively supress radiated and conducted radio-frequency emissions, the shield conductivity must be at least 1/10 of the phase conductor conductivity. One way of evaluating the effectiveness of the shiel...

  • Page 85

    Appendix c – iec installation acs/acc/acp 601 drives acx=acs/acc/acp c-3 earthing, power, and motor cable connections 1. Lead the power cable through the input cable entry, and the motor cable through the output entry into the unit. Frame r7: remove the rubber grommets from the input and output entr...

  • Page 86

    Appendix c – iec installation c-4 acx=acs/acc/acp acs/acc/acp 601 drives the grounding rail next to the nioc/niocp board. Components connected to digital/ analog inputs warning! Iec 664 requires double or reinforced insulation between live parts and the surface of accessible parts of electrical equi...

  • Page 88