ABB ACH580-07 User Manual - page 18
18 Option description and instructions
Start-up and acceptance test
You need the Drive composer PC tool or a control panel to perform the start-up and
acceptance test.
Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of
the drive start-up procedure. See the hardware manual.
Action
WARNING!
Obey the
, page 7. If you ignore them, injury or death, or
damage to the equipment can occur.
Checks and settings with no voltage connected
If any connections of the emergency stop circuit have been done on site (such as wiring of additional
emergency stop buttons, connection of shipping splits of large drives, etc.), check the connections
against the appropriate circuit diagrams.
Drives with R8i inverter modules: Check that the STO OUT output on the inverter control unit [A41] is
chained to the STO inputs of all inverter modules. The STO circuit is disabled in spare part modules.
Check that the hardware settings relevant to the safety function are set as defined in section
on page
.
Settings with voltage connected
Check that the parameters relevant to the safety function are set as defined in section
on page
.
Acceptance test
Ensure that the motor can be run and stopped freely during the test.
We recommend that you monitor these signals with the Drive composer PC tool:
• 01.01 Motor speed used
(rpm)
• 01.02 Motor speed estimated
(rpm)
•
01.07 Motor current
(A)
• 01.10 Motor torque
(%)
• 23.01 Speed ref ramp input
(rpm)
• 23.02 Speed ref ramp output
(rpm)
• 90.01 Motor speed for control
(rpm)
• 90.10 Encoder 1 speed
(rpm) (if you use an encoder)
Start the drive and ensure that the motor is running. If possible, use a motor speed close to the
maximum speed of the application.
Push the emergency stop button [S61].
Ensure
that the drive stops the motor by coasting and displays a related warning. See section
on page
.
Ensure that the indication lamp [P62] switches on.
Drives with R8i inverter modules: Make sure that “STO hardware failure” (5090) is not generated.
Ensure that you cannot switch the power on with the operating switch.
Ensure that you cannot start the drive and motor from any control location: Ensure that the motor
does not start even if you switch the start signal off and on or push the start key of the panel.
Turn the emergency stop button [S61] until it releases and returns to the up position.