ABB ANR96 User Manual

Manual is about: ELECTRICAL MULTIFUNCTION ANALYZER

Summary of ANR96

  • Page 1

    Anr96 e lectrical m ultifunction a nalyzer user manual im 125-u v. 4.4 anr96 im125-u-a v4.4.Doc abb s.P.A. Divisione sace apparecchi modulari viale dell’ industria, 18 20010 vittuone (mi) – italy tel.: 02.9034.1 – telefax: 02.9034.7609 http://bol.It.Abb.Com n etwork a nalyzer ok anr96.

  • Page 2

    Anr96 - user manual -2- information in this document is subject to change without notice and does not represent a commitment on the part of abb spa. This documentation is consigned to the customer to enable the correct and safe operation of the instrument; any other use of documentation is strictly ...

  • Page 3

    Anr96 - user manual -3- index 1) main information _________________________________________________________5 1.1) introduction _________________________________________________________5 1.2) description __________________________________________________________5 1.3) ce conformity and standards ____...

  • Page 4

    Anr96 - user manual -4- 8.4) serial ports ________________________________________________________26 8.4.1) standard serial port ______________________________________________26 8.4.2) rs485 connection not shielded ____________________________________27 8.4.3) rs485 connection shielded _____________...

  • Page 5

    Anr96 - user manual -5- 1) main information 1.1) introduction anr96 was engineered and tested in compliance with iec 348 class 1 standards for operating voltages up to 600 vac rms, considering the vde 0110 group c isolation standards for operating voltages up to 500 vac rms. The present manual conta...

  • Page 6

    Anr96 - user manual -6- 2) technical features 2.1) general specifications power supply/auxiliary voltage 85-265 v 50/60 hz/dc. 20-60 v 50/60 hz/dc (option). Isolation voltage 3700 vac rms x 1 minute. Voltage input 3 inputs, range 10-600vrms between phase-phase. Over voltage up to 750 vac permanent, ...

  • Page 7

    Anr96 - user manual -7- options: - n°2 digital outputs 12-230 vac-dc / 150ma max. The typical resistance with closed contacts is 8 Ω (r onmax = 12 Ω). Maximum frequency pulse emission: 16hz. - n°2 relay outputs the relay specifications are the following: - maximum power: 62,5 va, 30 w - maximum volt...

  • Page 8

    Anr96 - user manual -8- 2.2) measuring method and accuracy measuring range 30-500hz. Measuring method 64 sampling per period for v1 and i1, v2 and i2, v3 and i3. Measuring interval 0,1 second. Instrument accuracy model anr96 model anr96-02 voltage current power energy power factor standard en 62053-...

  • Page 9

    Anr96 - user manual -9- 2.3) measured variables phase voltage (rms) v l1-n - v l2-n - v l3-n line current (rms) i l1 - i l2 - i l3 frequency f l1 (hz) temperature t(°c) 2.4) calculated variables line voltage (rms) v l1-l2 - v l2-l3 - v l3-l1 three-phase system voltage (rms) v three-phase system curr...

  • Page 10

    Anr96 - user manual -10- 2.5) measuring & calculation formulas ( ) dt w li whli ali w li pf li q li w li w li li i lin v lin ali p i li Δ k vlink q li p i lik vlink w li p i lin k i li p v lin k v lin p k p k p k p k ∫ ∞ = = + = ⋅ = ∑ − ⋅ = ∑ ⋅ = = = = = = = ∑ ∑ 0 energy active factor power 2 2 cos ...

  • Page 11

    Anr96 - user manual -11- harmonic analyzes: cooley tukey algorithm. Dt qh Φ qh Φ dt wh Φ wh Φ al al al a Φ q l q l q l q Φ w l w l w l w Φ i i l i l l i Φ v v l v l l v Φ p v lijk v lij dt q li qh li p k ∫ ∞ = ∫ ∞ = + + = + + = + + = + + = + + = = ∫ ∞ = ∑ = 0 3 3 energy reactive 0 3 3 energy active ...

  • Page 12

    Anr96 - user manual -12- 3) instrument description the front panel of the anr96 is described on the following section: 1 display back lighted graphic lcd 50x50mm, 128x128 dot, dot pitch 0.35mm x 0.35mm, dot size 0.32mmx0.32mm, high viewing direction 60°, positive and negative visualization at low re...

  • Page 13

    Anr96 - user manual -13- 4) installation 4.1) safety on receipt of the instrument and prior to installation, make sure it is intact and has not been damaged during shipment. Before installing, make sure the operating voltage and mains voltage are compatible. The instrument power supply must not be e...

  • Page 14

    Anr96 - user manual -14- 4.3) mounting the unit needs to be installed on front panel of mains control/switchboards, wiring and connections must be carried out following the emc (electro-magnetic-compatibility) procedures. Plug in screw terminal blocks are used for appropriate wiring. There is a secu...

  • Page 15

    Anr96 - user manual -15- 5) internal battery to avoid to lose the setup and all storing data, the instrument is equipped of an internal battery (cr2450). 5.1) replacement internal battery only a qualified and authorized technical person can change the internal battery. This operation will delete all...

  • Page 16

    Anr96 - user manual -16- 6) connection 6.1) power supply the instrument doesn’t work without power supply. Before powering the instrument verify always to insert the right value (85-265 vac/dc standard; 20-60 vac/dc option). The instrument is equipped with an internal protection fuse on the power su...

  • Page 17

    Anr96 - user manual -17- 6.2) voltage inputs anr96 can measure voltages up to a maximum 600 vrms between phase-phase, further that value it is imperative to use voltage transformer. When using voltage transformer, make sure to respect the input and output polarities. Use cables with maximum cross-se...

  • Page 18

    Anr96 - user manual -18- l o a d l1 l2 l3 n p1 p2 s1 s2 l1 l2 l3 + + + - - - n l1 l2 l3 inserzione su linea a 4 fili con n°3 ta e n°3 tv inserzione su linea a 4 fili con n°3 ta in bassa tensione l o a d l1 l2 l3 n p1 p2 s1 s2 l1 l2 l3 + + + - - - n l1 l2 l3 network analyzer ok anr96 network analyzer...

  • Page 19

    Anr96 - user manual -19- 7) option boards the options listed below can be mounted alternately with each other (never simultaneously): - 4 digital inputs (instrument model: anr96p) - 2 digital outputs - 2 relays outputs - 1 rs485 port - 1 analog output - 2 analog outputs - 1 ethernet port (instrument...

  • Page 20

    Anr96 - user manual -20- 8) inputs / outputs 8.1) digital inputs the anr96 has 2 opt isolated digital inputs. With the anr96p it’s possible to have additional 4 inputs. For the digital inputs setup please consult the chapter 11.10). 8.1.1) standard digital inputs if long distances must be covered, t...

  • Page 21

    Anr96 - user manual -21- 8.1.2) option digital inputs this option has 4 digital inputs. With this option the instrument will be equipped with 6 digital inputs and 2 digital outputs. 2 3 4 5 6 8 9 10 11 12 7 1 d i1 + d i1 - d i2 + d i2 - a b n l n s1 s2 s1 s2 s1 s2 i1 i2 i3 l1v 2 3 4 5 6 8 9 10 11 12...

  • Page 22

    Anr96 - user manual -22- 8.2) digital outputs the anr96 has 2 digital outputs. At the standard configuration it’s possible to add 2 others photomos or relay digital outputs. Each outputs can be programmed as min/max threshold, external band, always on, pulse emission, remote control and load control...

  • Page 23

    Anr96 - user manual -23- 8.2.2) option digital outputs this option has 2 digital outputs (photomos). With this option the instrument will be equipped with 2 digital inputs and 4 digital outputs. 8.2.3) option relay digital outputs this option has 2 relay outputs. With this option the instrument will...

  • Page 24

    Anr96 - user manual -24- 8.3) option analog output two options are available: one or two analog outputs. The analog outputs are optional and they can be programmed as showed in the chapter 11.11) (0- 20ma or 4-20ma). In this configuration the instrument will be equipped with 2 digital inputs, 2 digi...

  • Page 25

    Anr96 - user manual -25- the anr96 gives a current signal (range 4÷20ma or 0÷20ma) proportional at the measures of the selected parameter. The output is bi-directional: the current can be directly or inversely proportional to reference value programmed. Bi-directional means reversal of reference val...

  • Page 26

    Anr96 - user manual -26- 8.4) serial ports the instrument has a serial port that can be used as rs485 or rs232. Optionally it’s possible to have another rs485 port or a profibus port (anr96prf model) or an ethernet port (anr96lan model) or an ethernet port with a rs485 port. 8.4.1) standard serial p...

  • Page 27

    Anr96 - user manual -27- 8.4.2) rs485 connection not shielded once a rs485 network has been configured; to communicate between the host (computer) and the instrument(s) (anr) a serial interface converter must be wired between pc and instrument(s) as mentioned on the above picture. In serial line ove...

  • Page 28

    Anr96 - user manual -28- 8.4.4) rs232 connection if a rs232 communication line is shorter of 5 mt. And a multidrop network will not use, it’s not necessary to use a serial line converter because the serial output is compatible with the pc, as shown on the above mentioned picture. A rs232 could reach...

  • Page 29

    Anr96 - user manual -29- 8.4.5) modem connection to make the remote connection it needs to program the remote modem (connected to the anr network). To program this modem the user has to use any communication program like hyperterminal. The hayes commands to program a standard modem are the following...

  • Page 30

    Anr96 - user manual -30- 8.4.6) option rs485 port with this option the instrument will be equipped with 2 digital inputs, 2 digital outputs and 2 serial ports. Personal computer modem n l n s1 s2 s1 s2 s1 s2 i1 i2 i3 l1v 2 3 4 5 6 8 9 10 11 12 7 1 l2v l3v t x r x c o m d i1 + d i1 - d i2 + d i2 - a ...

  • Page 31

    Anr96 - user manual -31- 8.5) option profibus port if this option board is installed, the instrument (anr96prf) will be equipped with n°2 digital inputs, n°2 digital outputs, n°1 serial port and a profibus port. Profibus-dp is a multi-master systems. In the networks it’s possible to have up to 126 d...

  • Page 32

    Anr96 - user manual -32- 8.6) option ethernet port for ethernet connection are available two type of option board. - with the first option, the instrument (anr96lan) will be equipped with 2 digital inputs, 2 digital outputs, 1 ethernet port and 1 rs232 (com1) and rs485 (com3) serial port. In this ca...

  • Page 33

    Anr96 - user manual -33- 9) use 9.1) function keys • up & down keys the “up” and “down” keys allows to skip through the real time pages and to select the programming level or to modify values during the input in the setup menu. • left & right keys the “left” and “right” keys allow to visualize the r...

  • Page 34

    Anr96 - user manual -34- 10.1) visualization tree h.I. 10-19 h.I. 20-29 h.I. 30-31 t b energy yesterday p3-p4 t b energy previous month p3-p4 t b energy previous year p3-p4 min/max l1 current min/max 3 ph avg watt h.I 00-09 il3 harmonics t b energy yesterday p1-p2 t b energy previous mont p1-p2 t b ...

  • Page 35

    Anr96 - user manual -35- 10.2) measures visualization variable reading of three - phase system • (v - kv) rms three - phase system voltage [∑ v l-l ] • (a - ka) rms three - phase system current [∑i] • (w - kw - mw - gw) three - phase system active power [Σ w] • (pf) three - phase system power factor...

  • Page 36

    Anr96 - user manual -36- voltage and current wave forms l2 line in the “l2 phase v-c” page are showed the voltage and current wave forms with their peak values and crest factors. The wave form of the current has the lower amplitude. Voltage and current wave forms l3 line in the “l3 phase v-c” page a...

  • Page 37

    Anr96 - user manual -37- variable reading average line, three-phase system and neutral current • (a - ka) rms average three - phase system current [Σ i av ] • (a - ka) rms average current l1 [i 1av ] • (a - ka) rms average current l2 [i 2av ] • (a - ka) rms average current l3 [i 3av ] • (a - ka) rms...

  • Page 38

    Anr96 - user manual -38- variable reading three-phase powers • (w - kw - mw - gw) three - phase system active power [Σp] • (var - kvar - mvar - gvar) three - phase system reactive power [Σq] • (va - kva - mva - gva) three - phase system apparent power [Σs] • (p.F.) three phase system power factor [Σ...

  • Page 39

    Anr96 - user manual -39- variable reading phase power factor • (p.F.) three phase system power factor [Σpf] • (p.F.) power factor l1 [pf 1 ] • (p.F.) power factor l2 [pf 2 ] • (p.F.) power factor l3 [pf 3 ] variable reading phase cos ϕ • (cosϕ) three phase system cosϕ [Σcosϕ] • (cosϕ) cosϕ l1 [cosϕ ...

  • Page 40

    Anr96 - user manual -40- variable reading counters this page shows the 8 counters available. Note: this page appear only if the digital inputs are set like counters. Variable reading consumption of active and reactive energy of the single phases and three-phase system (normal) • (kwh) positive activ...

  • Page 41

    Anr96 - user manual -41- variable reading time-band energy counters (option) note: these pages are displayed only if the option timeband is activated with the access code in the menu general (see par.11.3). 26 pages to display the active energy counters (positive and negative) and reactive (capaciti...

  • Page 42

    Anr96 - user manual -42- variable reading thd of voltage and current (harmonics orders option) note: these pages are displayed only if the option harmonics is activated with the access code in the menu general (see par.11.3). A page shows the total harmonic distortion of voltage and of current: • (t...

  • Page 43

    Anr96 - user manual -43- 10.3) status and information pages the status and/or information pages include: • the displaying of clock and internal calendar • the condition of internal ram memory • the condition of digital i/o • warnings • general info of the instrument clock/calendar • time format: hou...

  • Page 44

    Anr96 - user manual -44- warnings to see “warnings” are available 4 pages. The first page shows the correct connection of the instrument: the current transformer connection for current input and the phases sequence for voltage input. If at least one of current transformer is inverted, the display sh...

  • Page 45

    Anr96 - user manual -45- 11) setup 11.1) setup item general kct kct-pri. (1÷5000) kct-sec. (1;5) kvt kvt-pri. (1÷400000) kvct-sec. (1÷750) mode (4 wires -3 wires -aron) measure time(0 50 sec.) warnings (yes-no) b.Light (0 360) display (positive-negative) defpage time (10 900 sec.) sync. Mode(ext-...

  • Page 46

    Anr96 - user manual -46- 11.2) main menu setup the main menu or setup page is configured in the following way: • general, includes the settings of kct (current ratio), ktv (voltage ratio), mode (4 wires, 3 wires, aron), measure time (time constant of measure filter), warnings, b.Light (backlit on di...

  • Page 47

    Anr96 - user manual -47- 11.3) general the general menu is subdivided in the following sub menu: • kct, allows to set the current transforming ratio setting the primary and secondary values of the ct, if it’s used, in order to show the measured values in primary terms. Primary range: 1÷5000a; second...

  • Page 48

    Anr96 - user manual -48- 11.4) serial comm the serial comm menu allows the programming of the communication parameters of the com1 and the option com2. • address, is the address, node or logic number from 01 to 255 in modbus or from 01 to 128 in ascii or from 1 to 126 in profibus (with profibus opti...

  • Page 49

    Anr96 - user manual -49- 11.6) energy in the energy menu it’s possible to modify the unit of measurement of energies, to set at the initial value the generic and energy counters, to manage on the time-bands. • type, allows to choose the unit of measurement for the energy counter kwh (normal) or mwh ...

  • Page 50

    Anr96 - user manual -50- weekday, defines the days of the week in the selected period in which the tariff programming is active. Use the “left” and “right” keys to select the day of the week and the “up” and “down” keys to enable or disable the day. Time (1 - 12), defines the time of the day in whic...

  • Page 51

    Anr96 - user manual -51- 11.7) load control (option) note: these pages are displayed only if the option load control is activated with the access code in the menu general (see par par.11.3). The load control function allows to switch off the load when the expected average power exceeds the set value...

  • Page 52

    Anr96 - user manual -52- • load power, indicates the rated powers expressed in kw of the all loads. The load 1 corresponds to digital output 1 (do1) and so on… • priority on, indicates the connection priority of each load. The load with 8 priority will be the first to be connected, while the load wi...

  • Page 53

    Anr96 - user manual -53- 11.8) storage the storage menu allows the programming of the data to store. 4 archives of storing exist: - relative minimums and maximums - average powers - harmonic components - counters - samples (only with sw01 software or serial command) the storage is organized as fifo ...

  • Page 54

    Anr96 - user manual -54- • trigger enable, the operator may enable or disable the trigger function. If enable is off the enabled archives store the measures with the relative rate, all of time. If enable is on, the enabled archives store the measures with the relative rate only after the receiving o...

  • Page 55

    Anr96 - user manual -55- 11.9) digital output the digital outputs can be programmed to function like alarm (overload, load management for consumption optimization, etc.), or pulses emission for energy calculation or remote activation using software sw01. If an output is set as alarm the hour counter...

  • Page 56

    Anr96 - user manual -56- 11.10) digital input in the digital input menu it’s possible to program the digital input function for both standards and options. The 2 standards digital input can be programmed how follow: • type, defines the type of operation: - not used: if none input is selected or enab...

  • Page 57

    Anr96 - user manual -57- an item selected in the menu “type” of the digital inputs will be accepted only if the reset of the counters is confirmed. • count. => input, define the correspondence between the index of the counter and the digital input. It’s necessary to set the index of the digital inpu...

  • Page 58

    Anr96 - user manual -58- 11.11) analog output (option) selecting the analog output voice, the following programming page appears: • out index, expresses the number of output to select or program, which are present on the hardware of the instrument. • type, allows to select the value of current outpu...

  • Page 59

    Anr96 - user manual -59- 11.12) reset the reset page allows to cancel some operation or the complete operation of the setup system, reset modes are classified in four groups. Reset measures, reset all values or selected group of measure. In particular: • all, reset all of measures (minimum and maxim...

  • Page 60

    Anr96 - user manual -60- 3ph.Pf three-phase power factor l1 pf l1 phase power factor l2 pf l2 phase power factor l3 pf l3 phase power factor 3 ph.Cos three-phase cos Φ l1 cos l1 phase cos Φ l2 cos l2 phase cos Φ l3 cos l3 phase cos Φ 3ph.Va three-phase apparent power l1 va l1 phase apparent power l2...

  • Page 61

    Anr96 - user manual -61- 13) problems and solutions if you have a problem setting up or using your instrument, you may be able to solve it yourself. Before calling your retailer or nearest distributor you should try the suggested actions that are appropriate to your problem. Problem possible cause s...

  • Page 62

    Anr96 - user manual -62- 14) anr serial communication protocol the electrical multifunction analyzer anr series are disposal with two communication standard protocols: • ascii • modbus-rtu and optional • profibus • tcp/ip ethernet the standard communication protocol has been optimised for the connec...

  • Page 63

    Anr96 - user manual -63- 15) notes warning: abb spa declines all liability for any damage to people or property caused by improper or incorrect use of its products. Abb spa reserves the right to change product specifications without prior notice..

  • Page 64