  • Page 1

    Com600 series, version 4.1 iec 61850 proxy server user's manual.

  • Page 3

    Contents: 1. About this manual .................................................................................. 5 1.1. Copyright ........................................................................................ 5 1.2. Disclaimer .................................................................

  • Page 4

    4.1. About this section ......................................................................... 33 4.2. Activating com600 with new configurations ............................... 33 4.3. Diagnostics .................................................................................. 33 4.3.1. Iec 618...

  • Page 5: About This Manual

    About this manual 1. Copyright 1.1. This document and parts thereof must not be reproduced or copied without written per- mission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is fu...

  • Page 6

    Be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment. Conformity 1.3. This product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagn...

  • Page 7

    Operation this section covers the basic operation procedures you can carry out when transferring or activating grid automation controller com600 (later referred to as com600) with new configurations. You are also given instructions on how to monitor and control the iec 61850 proxy server opc client....

  • Page 8

    Use of symbols 1.7. This publication includes warning, caution, and information icons that point out safety- related conditions or other important information. It also includes tip icons to point out useful information to the reader. The corresponding icons should be interpreted as follows. The elec...

  • Page 9

    Description term the data set is the content basis for reporting and logging. The data set contains references to the data and data attribute val- ues. Data set a physical device that behaves as its own communication node in the network, for example, protection relay. Device change of process data o...

  • Page 10

    Description abbreviation application service data unit asdu buffered report control block brcb data access da data message code definition dmcd data object do gateway, component connecting two communication networks together gw human machine interface hmi international electrotechnical commission ie...

  • Page 11

    Related documents 1.10. Mrs number name of the manual 1mrs756125 com600 user's manual document revisions 1.11. History product revision document version/date document created 3.5 a/30.6.2011 document revised 4.0 b/31.5.2012 document revised 4.1 c/13.3.2015 11 com600 series, version 4.1 1mrs757275 ie...

  • Page 12: Introduction

    Introduction 2. General about the com600 series 2.1. The com600 series comprises of substation management units that are deployed together with protection and control relays and other communication devices, such as relion® protection and control relays and remote i/o units, to realize smart substati...

  • Page 13

    Functional overview 2.2. Iec61850_proxy_server_functional_overview.Png figure 2.2-1 functional overview of iec 61850 proxy server iec 61850 proxy server enables iec 61850-8-1 mms clients to access data and services of com600. It also features a goose send functionality for publishing data. With thes...

  • Page 14

    For the iec 61850 proxy server are initiated by iec 61850 service request from an iec 61850 client or by data updates from the connected opc servers. Iec 61850 proxy server features 2.3. The iec 61850 proxy server supports the following features: • opc data access v1.0/2.0 (client for process data, ...

  • Page 15: Configuration

    Configuration 3. About this section 3.1. This section guides you in the configuration tasks required before you can start using the iec 61850 proxy server. For information on the iec 61850 data modeling, refer to com600 user's manual. 1. Select file > open/manage project.... 2. In the open/manage pr...

  • Page 16

    When configuring opc servers the following characters cannot be used in object names: \ ` ' ' #. Also avoid using a space in object names. Overview_proxy.Png figure 3.2-1 example view of sab600 communication structure the configuration work can be divided into two separate tasks: 1. Building an obje...

  • Page 17

    Building object tree 3.3. General about building object tree 3.3.1. The object tree is built in the communication structure of sab600, see figure 3.2-1. It is built by adding objects in a logical order starting from the opc server object. Before the iec 61850 proxy server can be taken into use, you ...

  • Page 18

    2. Select the check-boxes in the first column to add lds to the iec61850 proxy server opc client configuration. 3. Click apply to create the configuration with the selected ieds to the communication structure. Proxy_config_tool.Png figure 3.3.3-1 proxy configuration tool the proxy configuration tool...

  • Page 19

    The data set can be modified with the dataset editor. Open the dataset editor by right- clicking the dataset object and selecting dataset editor. The dataset object has a set of data attributes: • idinst: instance of logical device to which the referenced data set belongs. • prefix: freely configura...

  • Page 20

    ... ... The data set identifies the data set to be created. Lnclass and do are used to determine which ln/dos should be added to the dataset. For example: the statnrml data set contains all alm named sps typed dos under ggio lnclass and all str named acd typed dos under phar lnclass, and so on. Addi...

  • Page 21

    There are buffered and unbuffered report control blocks: • in a buffered report control block (brcb) internal events issue immediate sending of reports, or buffer the events for transmission. This way the values of a data object are not lost due to transport flow control constraints or loss of conne...

  • Page 22

    Description value or value range/default property/parameter controls if the rcb is buffered or unbuffered. True false default: true buffered configuration revision of the data set referenced by this rcb. Every modification in the data set increases the configur- ation revision property by one. 0...2...

  • Page 23

    Description value or value range/default property/parameter data set true false default: false data set entry id true false default: true entry id reason code true false default: true reason code sequence number true false default: true sequence number time stamp true false default: false time stamp...

  • Page 24

    Configuring reporting 3.4.4. Reporting is preconfigured automatically. Data sets for necessary data are created and linked to configured report control blocks. To configure reporting: 1. Create and configure a data set object. Creating_dataset figure 3.4.4-1 creating a new data set 2. Create a repor...

  • Page 25

    Reportclient figure 3.4.4-3 adding reportclient objects 4. Configure the report control block. 5. Configure the data set of the report control block. Data_set_properties figure 3.4.4-4 data set properties goose messaging 3.4.5. The generic object oriented substation event (goose) is used in substati...

  • Page 26

    Iec61850 proxy server supports sending of goose messages. The receiving of goose messages is handled by the iec 61850 opc server. The goose data is sent periodically in 802.1q multicast frames over the local network. When data changes, the goose frame is sent several times in a fast cycle to prevent...

  • Page 27

    Configuring goose publishing 3.4.6. To send goose data, you must first define the sending data set used by the goose control block and then create the control block. 1. Create a new data set. Rename it if you plan to use several different sets of data (see 3.4.2.1, dataset editor). Creating_dataset....

  • Page 28

    Modifying_dataset.Png figure 3.4.6-2 modifying the data set to be sent with goose 3. Create a new goose control block (gocb). Creating_gcb.Png figure 3.4.6-3 creating goose control block 4. Configure the goose control block, see figure 3.4.6-4. • select the created data set. • define appid (applicat...

  • Page 29

    Goose_control_block_properties figure 3.4.6-4 goose control block properties configuring objects 3.5. General about configuring objects 3.5.1. After the objects have been added, configure the object properties. Figure 3.5.1-1 shows an example of how to use sab600 to configure the object properties f...

  • Page 30

    Proxy_object_properties.Png figure 3.5.1-1 example of object properties in the objects properties window 2. Select the property you want to configure. Depending on the property value type, configuring is always done either by: • selecting a predefined value from a drop-down menu, or • entering a tex...

  • Page 31

    Table 3.5.3-1 iec 61850 proxy subnetwork properties description value or value range/ default property / para- meter communication port lan port used by the iec 61850 protocol used for goose sending. Values shown here are default values when no connection to com600 has been made. When the first conn...

  • Page 32

    Configuring iec 61850 proxy device properties 3.5.5. Iec 61850 proxy device does not have any configurable properties. Exporting configuration to other systems 3.6. When iec 61850 proxy configuration is finalized from the com600 point of view, configuration needs to be exported from the iec 61850 pr...

  • Page 33: Operation

    Operation 4. About this section 4.1. This section describes the basic operation procedures you can carry out after the iec 61850 proxy server object properties have been configured. After this, you can, for example, monitor and control the condition of connections in the proxy subnetwork. This is do...

  • Page 34

    Proxy_online_diagnostics.Png figure 4.3.1.1-1 iec 61850 proxy server online diagnostics in online diagnostics dialog box you can: • reset the iec 61850 proxy server opc client • view the event log file • clear the event log file diagnostic ae client 4.3.1.2. Diagnostic events can be monitored and co...

  • Page 35

    Proxy_diagnostic_ae_client.Png figure 4.3.1.2-1 iec 61850 proxy server diagnostic ae client iec 61850 proxy ied 4.3.2. Online diagnostics 4.3.3. The iec 61850 communication activity can be monitored with the online diagnostics function, see figure 4.3.3-1: • in the status information field, you can ...

  • Page 36

    Ied_online_diagnostics.Png figure 4.3.3-1 iec 61850 proxy ied online diagnostics 36 1mrs757275 com600 series, version 4.1 iec 61850 proxy server user's manual.

  • Page 37: Technical Reference

    Technical reference 5. Asci conformance statement 5.1. Acsi conformance statement 5.1.1. Acsi conformance statements shall be used to provide an overview and details about a device claiming conformance with acsi: • 5.1.2, acsi basic conformance statement • 5.1.3, acsi models conformance statement • ...

  • Page 38

    C1 – shall be ‘m’ if support for logical-device model has been declared. O – optional m – mandatory acsi models conformance statement 5.1.3. Table 5.1.3-1 acsi models conformance statement value/comments server/pub- lisher client/sub- scriber if server side (b1) supported supported c2 c2 logical dev...

  • Page 39

    Value/comments server/pub- lisher client/sub- scriber buftm m8-6 intgpd m8-7 gi m8-8 conf-revision m8-9 - o o logging - o o log control m9 intgpd m9-1 - o o log m10 supported m m control m11 if gse (b31/32) is supported supported (send) o o goose o o gsse m13 if svc (41/42) is supported - o o multic...

  • Page 40

    Table 5.1.4-1 acsi service conformance statement value/comments server/pub- lisher client/sub- scriber aa: tp/mc services server supported m tp serverdirectory s1 application association supported m m associate s2 supported m m abort s3 supported m m release s4 logical device supported m m tp logica...

  • Page 41

    Value/comments server/pub- lisher client/sub- scriber aa: tp/mc services buffered report control block (brcb) supported c6 c6 tp report s24 data-change (dchg) s24-1 qchg-change (qchg) s24-2 data-update (dupd) s24-3 supported c6 c6 tp getbrcbvalues s25 supported c6 c6 tp setbrcbvalues s26 unbuffered ...

  • Page 42

    Value/comments server/pub- lisher client/sub- scriber aa: tp/mc services - c9 o tp getgsseelementnumber s42 - o o tp getgscbvalues s43 - o o tp setgscbvalues s44 transmission of sampled value model (svc) multicast svc - c10 c10 mc sendmsvmessage s45 - o o tp getmsvcbvalues s46 - o o tp setmsvcbvalue...

  • Page 43

    Value/comments server/pub- lisher client/sub- scriber aa: tp/mc services t5 (nearest negative power of 2 in seconds) supported timestamp resol- ution t3 c6 – shall declare support for at least one (brcb or urcb). C7 – shall declare support for at least one (querylogbytime or querylogbyentry). C8 – s...

  • Page 44

    Table 5.3.1-1 pics for a-profile support value/comment server client f/s f/s supported c1 c1 client/server a-profile a1 supported c2 c2 goose/gse management a-profle a2 - c3 c3 gsse a-profile a3 - c4 c4 timesync a-profile a4 c1 – shall be ‘m’ if support for any service specified for client/s are dec...

  • Page 45

    All required iec 61850 services for supporting the acsi services stated to be supported are supported by the used mms stack mms-ease light. 45 com600 series, version 4.1 1mrs757275 iec 61850 proxy server user's manual.

  • Page 46

    46.

  • Page 47: Index

    Index a acsi conformance .............................................................................................. 37 basic conformance .......................................................................................... 37 models conformance .................................................

  • Page 48

    I iec 61850 proxy server ...................................................................................... 30 features ......................................................................................................... 14 iec 61850 proxy server opc client adding .............................

  • Page 50

    Contact us 1mrs757275 c/13.3.2015 © copyright 2015 abb. All rights reserved. Abb oy distribution automation p.O. Box 699 fi-65101 vaasa, finland tel. +358 10 22 11 fax. +358 10 224 1094 abb inc. Distribution automation 655 century point lake mary, fl 32746, usa tel: +1 407 732 2000 fax: +1 407 732 2...