ABB ControlMaster CM10 User Manual

Other manuals for ControlMaster CM10: Communications Supplement, User Manual
Manual is about: Universal process controllers

Summary of ControlMaster CM10

  • Page 1

    User guide – basic functionality im/cm/b–en rev. H controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din the company we are an established world force in the design and manufacture of instrumentation for industrial process control, flow measurement, gas and liq...

  • Page 2

    Refer to section 7.2, page 38 refer to section 7.3, page 41 refer to section 7.4, page 49 see back cover refer to section 6, page 28 refer to section 7.1, page 35 loop 1 setpoints local setpoint 1 (4) rsp ratio rsp bias ramp mode ramp rate loop 1 control on/off hysteresis mode autotune pid loop 1 ti...

  • Page 3

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din contents im/cm/b–en rev. H 1 contents 1 safety .......................................................................... 3 1.1 electrical safety ..................................................... 3 1.2 s...

  • Page 4

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din contents 2 im/cm/b–en rev. H 5 operator level menus .............................................. 23 5.1 diagnostic status bar .......................................... 25 5.2 diagnostic view ................

  • Page 5

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 1 safety im/cm/b–en rev. H 3 1 safety information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any other purpose is specifically...

  • Page 6

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 1 safety 4 im/cm/b–en rev. H 1.3 health & safety health and safety to ensure that our products are safe and without risk to health, the following points must be noted: the relevant sections of these instruct...

  • Page 7

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 2 introduction im/cm/b–en rev. H 5 2 introduction this manual provides details for the controlmaster cm10 ( 1 / 8 din), cm30 ( 1 / 4 din) and cm50 ( 1 / 2 din) controllers with basic functionality. 2.1 ec di...

  • Page 8

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 3 displays, overview 6 im/cm/b–en rev. H 3 displays, overview 3.1 cm10 operator page, icons & keys fig. 3.1 controlmaster cm10 display and icons pv value setpoint value icons access level manual control mode...

  • Page 9

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 3 displays, overview im/cm/b–en rev. H 7 3.2 cm30 and cm50 operator page, icons & keys the controlmaster cm30 and cm50 displays and icons are shown in fig. 3.2. Fig. 3.2 controlmaster cm30 and cm50 displays ...

  • Page 10

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 3 displays, overview 8 im/cm/b–en rev. H the controlmaster cm30 and cm50 front panel keys are shown in fig. 3.3. Fig. 3.3 controlmaster cm30 and cm50 front panel keys b d e a c a navigation (left) / operator...

  • Page 11

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 9 4 installation 4.1 siting and environmental requirements fig. 4.1 siting and environmental requirements + cm30 cm30 cm30 cm30 cm30 at eye level close to the sensor avoid vi...

  • Page 12

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 10 im/cm/b–en rev. H 4.2 dimensions dimensions in mm (in.) fig. 4.2 controlmaster cm10 and cm30 dimensions cm10 cm30 panel cut-out dimensions 97 (3.8) 97 (3.8) 121 (4.8) 141 (5.5) 91.8 (3.6) 2...

  • Page 13

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 11 dimensions in mm (in.) fig. 4.3 controlmaster cm50 dimensions controllers can be close-stacked to din 43835 144 (5.6) 123 (4.9) 146 (5.7) 138 (5.4) 23 (0.9) 138 (5.4) 30 (...

  • Page 14

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 12 im/cm/b–en rev. H 4.3 mounting controlmaster is designed for panel mounting. For nema4x protection, a panel thickness of 2.5 mm (0.1 in.) is required. To panel-mount the controller: 1. Cut ...

  • Page 15

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 13 4.4 jumper links for relay outputs the factory-set default for relay action is n/o. 4.4.1 removing the controller from its case the controlmaster inner assembly must be re...

  • Page 16

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 14 im/cm/b–en rev. H 4.4.2 resetting jumper links 1. The links associated with the relay outputs are shown in fig. 4.6. 2. If necessary, move the link to select the relay action required (n/o ...

  • Page 17

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 15 4.5 electrical connections warning. The instrument is not fitted with a switch therefore a disconnecting device such as a switch or circuit breaker conforming to local saf...

  • Page 18

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 16 im/cm/b–en rev. H 4.5.1 controlmaster cm10 electrical connections fig. 4.7 controlmaster cm10 electrical connections 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 + + + + + 19 20 21 22 23 24...

  • Page 19

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 17 4.5.2 controlmaster cm30 electrical connections fig. 4.8 controlmaster cm30 electrical connections 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 + + + + + 29 30 31 32 33 34...

  • Page 20

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 18 im/cm/b–en rev. H 4.5.3 controlmaster cm50 electrical connections fig. 4.9 controlmaster cm50 electrical connections + 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 + + + 24 25 26 27 28 29 3...

  • Page 21

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 19 4.5.4 analog inputs fig. 4.10 standard analog inputs (1 and 2) + + 1 2 3 4 + + + tx 5 + tx + + ma mv v digital input milliamps* thc cj** thc*** 3-lead rtd ma, mv, v, digit...

  • Page 22

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 20 im/cm/b–en rev. H fig. 4.11 controlmaster cm30 and cm50 optional analog inputs (3 and 4) + + 24 25 26 27 + + + tx 28 + tx + + 29 30 31 32 33 * using internal transmitter power supply. ** fi...

  • Page 23

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation im/cm/b–en rev. H 21 4.5.5 frequency / pulse input 4.5.6 digital input / output note. This input is designed primarily for use with flowmeters. Fig. 4.12 frequency / pulse input note. Digital ...

  • Page 24

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 4 installation 22 im/cm/b–en rev. H fig. 4.13 digital input and open collector digital output connections +ve –ve load digital input/output + external cm10: terminal 21 cm30: terminal 43 or 35 cm50: terminal...

  • Page 25

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 5 operator level menus im/cm/b–en rev. H 23 5 operator level menus operator level menus are used to adjust setpoint(s) and output(s), select setpoints, select the view and to enter basic and advanced modes (...

  • Page 26

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 5 operator level menus 24 im/cm/b–en rev. H autotune used to start or stop an autotune routine. This menu is enabled only if autotune mode is on – see page 30. Adjust enables a value to be adjusted using the...

  • Page 27

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 5 operator level menus im/cm/b–en rev. H 25 5.1 diagnostic status bar fig. 5.1 controlmaster diagnostic status bar (controlmaster cm30 shown) pv 1 failed controlmaster pv sp 99.5 175.0 32.5 op deg c % pv 1 f...

  • Page 28

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 5 operator level menus 26 im/cm/b–en rev. H 5.2 diagnostic view the diagnostic view can be selected from the operator / view select menu. All currently active diagnostic alarm states are displayed in the dia...

  • Page 29

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 5 operator level menus im/cm/b–en rev. H 27 5.4 access level level access logout displayed after basic or advanced level are accessed. Logs the user out of basic or advanced level. If passwords are set, a pa...

  • Page 30

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level 28 im/cm/b–en rev. H 6 basic level the basic menu provides access to the tunable control settings and setpoint values. Loop 1 setpoints local setpoint 1(4) the local setpoint value required. If...

  • Page 31

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level im/cm/b–en rev. H 29 …basic / …loop 1 setpoints ramp mode the ramping setpoint facility can be used to prevent a large disturbance to the control output when the setpoint value is changed. The ...

  • Page 32

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level 30 im/cm/b–en rev. H …basic / …loop 1 control mode turns the autotune functionality on or off. When set to on, an autotune can be started from the operator level menus – see page 23. Autotune n...

  • Page 33

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level im/cm/b–en rev. H 31 …basic / …loop 1 control / …autotune autotune operation the autotune sequence is shown in the following figure: a b c d sp pv 1 set the first step value and dynamics requir...

  • Page 34

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level 32 im/cm/b–en rev. H …basic / …loop 1 control / …autotune first step defines the maximum size of the first output step in the autotuning process. Autotune adjusts the output step magnitude acco...

  • Page 35

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level im/cm/b–en rev. H 33 …basic / …loop 1 control / …pid manual reset when the integral time is off, the manual reset parameter is activated. When the process variable is equal to the control setpo...

  • Page 36

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 6 basic level 34 im/cm/b–en rev. H …basic loop 1 time prop the active time of the output pulse is proportional to the value of the control output. With 100% output the pulse is active for the complete cycle ...

  • Page 37

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 35 7 advanced level 7.1 device setup provides access to standard setup parameters to determine the type of control / indication required. Also provides the ability to creat...

  • Page 38

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 36 im/cm/b–en rev. H …device setup / …basic setup loop 1 split o/p these types of outputs split the control (pid) output signal (see page 32) into 2 signals. The linear relationship between ...

  • Page 39

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 37 …device setup security setup 2 security access levels are provided, each protected by a password of up to 6 alphanumeric characters. Note. Passwords are not set at the f...

  • Page 40

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 38 im/cm/b–en rev. H 7.2 display used to setup the operator page, displayed language and display hardware settings. Language selects the language on the controller's local display. Operator ...

  • Page 41

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 39 …display operator functions autoscroll when enabled (on), operator pages are scrolled continuously at intervals of 10 seconds per page. Soft key function assigns a dedic...

  • Page 42

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 40 im/cm/b–en rev. H …display /…operator enable functions auto manual enable turns on / off the ability for auto / manual control mode to be changed in operator level. Local remote enable tu...

  • Page 43

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 41 7.3 input/output allows analog and digital inputs / outputs and relays to be configured. Analog inputs analog input 1(4)* input type input types comprise: millivolts, mi...

  • Page 44

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 42 im/cm/b–en rev. H … input/output / …analog input 1(4) elect. Low sets the required electrical range. Note. Applicable only to millivolts, milliamps, volts and ohms. Linear inputs standard...

  • Page 45

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 43 … input/output / …analog input 1(4) eng units the selected units are used by the linearizer and displayed in the operator pages – see page 23. Not applicable for pulse i...

  • Page 46

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 44 im/cm/b–en rev. H … input/output / …analog input 1(4) broken sensor if an input failure occurs, the input value can be configured to drive in a set direction. None no action taken. Automa...

  • Page 47

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 45 …input/output analog outputs the analog outputs can be configured to retransmit any analog value and have a configurable range from 0 to 24 ma. Output 1 can also be conf...

  • Page 48

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 46 im/cm/b–en rev. H …input/output / …analog outputs / …analog output 1 (2) auto eng range* if enabled (on) the eng high and eng low values for the output are set to the engineering range va...

  • Page 49

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 47 …input/output digital i/o digital io 1(to 6) type sets the digital io to operate as an output or an input. Off no action taken. Output the digital io operates as an outp...

  • Page 50

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 48 im/cm/b–en rev. H …input/output / …digital i/o / …digital io 1(to 6) polarity sets the polarity of the output signal. Positive for an output, the output is high if the source is active. F...

  • Page 51

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 49 7.4 control enables the setpoints, control functions and outputs to be configured. Loop 1 setpoints the controller can configure independent local setpoint values, remot...

  • Page 52

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 50 im/cm/b–en rev. H …control / …loop 1 setpoints track mode the local (internal) setpoint can track another value according to the setpoint tracking mode selected. Off no tracking. Local th...

  • Page 53

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 51 …control / …loop 1 setpoints rsp fault action the action required when a fault occurs with the remote setpoint. No action no fault action. Local selects the local (inter...

  • Page 54

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 52 im/cm/b–en rev. H …control / …loop 1 setpoints / select sources lsp1 (to 4) select the source required to select local setpoint 1 (lsp1) as the current local setpoint. Selection is made o...

  • Page 55

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 53 …control loop 1 control configures the basic type of control required and the pid (see page 32) and autotune (see page 30) settings. Control type selects the basic type ...

  • Page 56

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 54 im/cm/b–en rev. H …control loop 1 output used to set the output limits, tracking rates, slew rates and output action on power failure or process variable failure. Limits note. When used w...

  • Page 57

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 55 …control / …loop 1 output / …failure actions / …power recovery man – default manual control mode with output set to default value. Auto mode auto control mode with integ...

  • Page 58

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 56 im/cm/b–en rev. H …control / …loop 1 output a/m select sources the selection of a/m (auto / manual) control modes of operation can be controlled by digital signals; either from internal d...

  • Page 59

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 57 …control / …loop 1 output / …a/m select sources manual 1(2) config o/p used when manual 1(2) output is set to config value. A/m toggle the source required to toggle betw...

  • Page 60

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 58 im/cm/b–en rev. H …control / …loop 1 output slew rate the output slew rate – restricts the maximum rate of change of the control output. Function selects if the output slew rate function ...

  • Page 61

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 59 …control / …loop 1 output tracking enables the control output to be configured to follow a tracking signal when in auto control mode. When in manual control mode, the ou...

  • Page 62

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 60 im/cm/b–en rev. H …control loop 1 split o/p* the split output facility enables the pid control output (see page 32) to be split into 2 separate outputs. This enables heat / cool and other...

  • Page 63

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 61 7.5 process alarm used to configure up to 8 independent process alarms. Process alarm menu process alarm high and low process alarm action trip point process variable al...

  • Page 64

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 62 im/cm/b–en rev. H …process alarm alarm 1 (8) type alarm types comprise: high process, low process, high latch, low latch. (deviation alarms are configured using a high or low process alar...

  • Page 65

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 63 7.6 communication …process alarm / … alarm 1 (to 8) hysteresis hysteresis trip level in engineering units. Activated at the alarm trip level but deactivated only when th...

  • Page 66

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 64 im/cm/b–en rev. H 7.7 diagnostics used to view diagnostic data – see section 7.7.1, page 66 for description of diagnostic messages and recommended corrective action(s). Diagnostic history...

  • Page 67

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 65 …diagnostics source analysis analog sources enables the current value of any analog source to be viewed. Analog source selects the analog signal to be viewed – see secti...

  • Page 68

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 66 im/cm/b–en rev. H 7.7.1 diagnostic messages icon number / message possible cause suggested action 242.004 (240.005) adc 1(2) failed temporary or permanent failure of analog to digital con...

  • Page 69

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 67 234.008 (232.009) pfb 1(2) failed problem with input assigned to loop 1 (2) position feedback. Broken sensor leads, defective input source or input signal out of permitt...

  • Page 70

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 68 im/cm/b–en rev. H 208.020 nv error comm bd failure of non-volatile memory on communications board or permanent corruption of its data. Acknowledge error. Check communications board is cor...

  • Page 71

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level im/cm/b–en rev. H 69 086.036 (082.037) oscillation 1(2) abnormal oscillations in the control loop. Check process. Perform new manual or autotune. 094.034 (090.035) valve 1(2) sticking motori...

  • Page 72

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 7 advanced level 70 im/cm/b–en rev. H 7.8 device info used to display read-only factory-set parameters for the controller. Instrument type the controller's model number (for example, cm30). I/o build the inp...

  • Page 73

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 8 templates and functionality im/cm/b–en rev. H 71 8 templates and functionality 8.1 single loop / single loop with remote setpoint this template provides basic feedback control using three-term pid or on/of...

  • Page 74

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 9 pc configuration 72 im/cm/b–en rev. H 9 pc configuration in addition to local configuration via the front panel keys, the controller can be configured from a pc via the infrared port. The infrared port is ...

  • Page 75

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification im/cm/b–en rev. H 73 10 specification operation display color 1 / 4 vga tft, liquid crystal display (lcd) with built-in backlight language english, german, french, italian and spanish operat...

  • Page 76

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification 74 im/cm/b–en rev. H setpoints autotune on-demand calculation of control settings process alarms acknowledgement via front panel keys or digital signals analog inputs universal process input...

  • Page 77

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification im/cm/b–en rev. H 75 other linearizations x, x 3/2 , x 5/2 , digital filter programmable 0 to 60 s display range –9999 to 99999 update rate 125 ms common mode noise rejection >120 db at 50/...

  • Page 78

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification 76 im/cm/b–en rev. H rtd maximum range °c (°f) accuracy (% of reading) pt100 –200 to 600 (–325 to 1100) 0.1 % or ±0.5 °c (0.9 °f) linear inputs standard analog input accuracy (% of reading) ...

  • Page 79

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification im/cm/b–en rev. H 77 outputs controls / retransmission outputs relays digital input / output 2-wire transmitter power supply number 2 (1 standard, 1 optional) type configurable as analog or ...

  • Page 80

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification 78 im/cm/b–en rev. H communications for modbus and ethernet communications see separate user guide (im/cm/c–en). Infrared port emc emissions & immunity meets requirements of iec61326 for an ...

  • Page 81

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din 10 specification im/cm/b–en rev. H 79 electrical supply ranges 100 to 240 v ac ± 10 % (90 v min. To 264 v max.) 50 / 60 hz 10 to 36 v dc (optional) power consumption 10 w max. Power interruption protection n...

  • Page 82

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix a – digital and analog sources 80 im/cm/b–en rev. H appendix a – digital and analog sources a.1 digital sources a.2 analog sources note. Numbers in brackets indicate additional parameters, for examp...

  • Page 83

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix b – configuration error codes im/cm/b–en rev. H 81 appendix b – configuration error codes configuration errors are generated when a signal assigned as a source for something has failed. Configuratio...

  • Page 84

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix b – configuration error codes 82 im/cm/b–en rev. H 70 analogue input fail state a1 71 analogue input fail state a2 72 analogue input fail state b1 73 analogue input fail state b2 74 analogue input f...

  • Page 85

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix b – configuration error codes im/cm/b–en rev. H 83 155 alarm state 8 156 alarm ack state 8 157 time prop state 1 158 time prop state 2 159 time prop state 3 160 time prop state 4 161 control o/p aut...

  • Page 86

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix c – analog input (engineering) units 84 im/cm/b–en rev. H appendix c – analog input (engineering) units unit description % % % sat % saturation %do2 % dissolved oxygen %hci % hydrochloric acid %n2 %...

  • Page 87

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix c – analog input (engineering) units im/cm/b–en rev. H 85 mgal/d (uk) imperial mega gallons per day mgal/d (us) us mega gallons per day mho conductance ml/d, ml/h megaliters per day, hour. Ml/h, ml/...

  • Page 88

    Controlmaster cm10, cm30 and cm50 universal process controllers, 1 / 8 , 1 / 4 and 1 / 2 din appendix d – output type assignments 86 im/cm/b–en rev. H appendix d – output type assignments output type ao 1 ao 2 dio 1 dio 2 rly1 rly2 rly3 rly4 analog op pv alm 1 alm 2 alm 3 alm 4 time proportioning pv...

  • Page 89

    Refer to section 7.6, page page 63 refer to section 7.7, page page 64 refer to section 7.8, page page 70 refer to section 7.5, page page 61 alarm 1 (8) type tag source trip hysteresis time hysteresis display enable acknowledge source enable source process alarm menu exit select refer to im/cm/c-en f...

  • Page 90

    Contact us im /c m /b – e n r e v. H 0 8.201 2 customer support we provide a comprehensive after sales service via a worldwide service organization. Contact one of the following offices for details on your nearest service and repair centre. Uk abb limited tel: +44 (0)1480 475321 fax: +44 (0)1480 217...