ABB CoriolisMaster FCM2000 Operating Instructions Manual

Other manuals for CoriolisMaster FCM2000: Operating instruction
Manual is about: Coriolis Mass Flowmeter for Simultaneous Measurement of Mass, Density and Temperature

Summary of CoriolisMaster FCM2000

  • Page 1

    Operating instruction d184b111u02 mass flowmeter coriolismaster fcm2000 pos: 1 /titelblätter / copyright/ba-ia/durchfluss/fcm2000 @ 6\mod_1171653775140_3101.Doc @ 67895 @ standard software d699g001u01 b.3x d699g001u02 a.1x d699g001u03 a.1x p r o f i b u s process field bus Ž pos: 2 /======= seitenum...

  • Page 2

    Blinder text 2 coriolismaster fcm2000 d184b111u02 pos: 3 /titelblätter / copyright/copyright-seite @ 0\mod_1138781938968_3101.Doc @ 3122 @ mass flowmeter coriolismaster fcm2000 operating instruction d184b111u02 12.2008 rev. 07 manufacturer: abb automation products gmbh dransfelder straße 2 d-37079 g...

  • Page 3

    Contents d184b111u02 coriolismaster fcm2000 3 1 safety....................................................................................................................................................................6 1.1 general information and notes for the reader ..................................

  • Page 4

    Contents 4 coriolismaster fcm2000 d184b111u02 4.4 installation of the field-mount housing / compact unit ..................................................................................32 4.4.1 inspection.................................................................................................

  • Page 5

    Contents d184b111u02 coriolismaster fcm2000 5 6.4 additional parameter descriptions................................................................................................................88 6.4.1 submenu display ...................................................................................

  • Page 6

    Safety 6 coriolismaster fcm2000 d184b111u02 pos: 5.1 /Überschriften/1/s - u/sicherheit @ 0\mod_1129703894050_3101.Doc @ 3168 @ 11 1 safety pos: 5.2 /Überschriften/1.1/1-spaltig/a - c/allgemeines und lesehinweise @ 22\mod_1222689360552_3101.Doc @ 219103 @ 22 1.1 general information and notes for the ...

  • Page 7

    Safety d184b111u02 coriolismaster fcm2000 7 pos: 5.7 /sicherheit/durchfluss/allgemein/bestimmungswidrige verwendung (durchfluss) @ 0\mod_1129705865785_3101.Doc @ 3239 @ 2 1.3 improper use the following uses of the device are prohibited: • operation as a flexible adapter in piping, e. G., to compensa...

  • Page 8

    Safety 8 coriolismaster fcm2000 d184b111u02 pos: 5.11 /sicherheit/allgemein/zulässige messstoffe @ 0\mod_1129715285861_3101.Doc @ 3271 @ 2 1.5 allowed fluids when measuring fluids, the following points must be observed: • fluids may only be used if, based on state-of-the-art technology or the operat...

  • Page 9

    Safety d184b111u02 coriolismaster fcm2000 9 pos: 5.14 /Überschriften/1.1/1-spaltig/s - u/schilder und symbole @ 0\mod_1129721947139_3101.Doc @ 3204 @ 22 1.7 plates and symbols pos: 5.15 /Überschriften/1.1/1-spaltig/s - u/symbole und signalwörter @ 7\mod_1172821912687_3101.Doc @ 70104 @ 22 1.8 symbol...

  • Page 10

    Safety 10 coriolismaster fcm2000 d184b111u02 pos: 5.18 /Überschriften/1.1.1/1-spaltig/typenschild / fabrikschild @ 0\mod_1129720923978_3101.Doc @ 3228 @ 33 1.8.1 name plate / factory tag pos: 5.19 /sicherheit/durchfluss/fcm2000/typenschilder fcm2000 (durchfluss) @ 6\mod_1171654472250_3101.Doc @ 6797...

  • Page 11

    Safety d184b111u02 coriolismaster fcm2000 11 converter with atex approval x abb automation products gmbh 37070 göttingen – germany fcm2000 mc27 0032 ~ – g00353 2 1 3 4 5 6 7 8 9 10 11 tÜv 99 atex1443 x ii 2d t115°c…tmed ip 67 ii 2g eex emd [ib] iic t6 tmed = 150°c at tamb = 40°c tmed = 140°c at tamb...

  • Page 12

    Safety 12 coriolismaster fcm2000 d184b111u02 pos: 5.21 /sicherheit/durchfluss/fcm2000/fabrikschilder fcm2000 (durchfluss) @ 8\mod_1178194332703_3101.Doc @ 88383 @ 1.8.1.2 factory plates the factory plate is located on the flowmeter primary housing. If the pressure equipment is subject to the ped (se...

  • Page 13

    Safety d184b111u02 coriolismaster fcm2000 13 pos: 5.23 /Überschriften/1.1/1-spaltig/v - z/zielgruppen und qualifikationen @ 22\mod_1222689902850_3101.Doc @ 219227 @ 22 1.9 target groups and qualifications pos: 5.24 /sicherheit/allgemein/zielgruppen und qualifikationen @ 22\mod_1222689951319_3101.Doc...

  • Page 14

    Safety 14 coriolismaster fcm2000 d184b111u02 pos: 5.28 /sicherheit/allgemein/entsorgung @ 22\mod_1222691515053_3101.Doc @ 219400 @ 23 1.11 disposal abb automation products gmbh actively promotes environmental awareness and has an operational management system that meets the requirements of din en is...

  • Page 15

    Safety d184b111u02 coriolismaster fcm2000 15 pos: 5.32 /sicherheit/durchfluss/allgemein/sicherheitshinweise zum betrieb (durchfluss) @ 0\mod_1129734381309_3101.Doc @ 3263 @ 1.14 operating safety information during operation with hot fluids, contact with the surface may result in burns. Aggressive or...

  • Page 16

    Safety 16 coriolismaster fcm2000 d184b111u02 corrective maintenance work may only be performed by trained personnel. • depressurize the device and adjoining lines or containers before removing the device. • check whether hazardous materials are used as materials to be measured before opening the dev...

  • Page 17

    Design and function d184b111u02 coriolismaster fcm2000 17 pos: 7 /Überschriften/1/a - c/aufbau und funktion @ 0\mod_1129797620733_3101.Doc @ 3140 @ 11 2 design and function pos: 8 /aufbau und funktion/durchfluss/fcm2000/aufbau @ 6\mod_1171654750218_3101.Doc @ 68021 @ 2 2.1 design the abb automation ...

  • Page 18

    Design and function 18 coriolismaster fcm2000 d184b111u02 movement of the pipes inward no flow direction of the coriolis force with flow when the tubes are moving outward g00356 g00357 → → f c → f c → f c → → → f c → movement of the pipes outward, no flow direction of the coriolis force with flow wh...

  • Page 19

    Design and function d184b111u02 coriolismaster fcm2000 19 pos: 11 /Überschriften/1.1/1-spaltig/g - i/geräteausführungen @ 0\mod_1129798599740_3101.Doc @ 3187 @ 22 2.3 device designs pos: 12 /technische daten / datenblatt/durchfluss/fcm2000/Übersichten/Übersicht aufnehmer und messumformer @ 5\mod_116...

  • Page 20

    Design and function 20 coriolismaster fcm2000 d184b111u02 pos: 14 /Überschriften/1.1/1-spaltig/g - i/geräteübersicht fcm2000 • atex @ 8\mod_1177071585640_3101.Doc @ 85693 @ 22 2.4 model overview atex pos: 15 /technische daten / datenblatt/durchfluss/fcm2000/Übersichten/geräteübersicht dn 1,5 ... Dn ...

  • Page 21

    Design and function d184b111u02 coriolismaster fcm2000 21 pos: 17 /Überschriften/1.1/1-spaltig/g - i/geräteübersicht fcm2000 • fm, csa @ 11\mod_1183449774687_3101.Doc @ 109473 @ 22 2.5 model overview fm, csa pos: 18 /ex-technische daten/durchfluss/fcm2000/fm installationsklassen @ 5\mod_116792542581...

  • Page 22

    Transport 22 coriolismaster fcm2000 d184b111u02 pos: 20.1 /Überschriften/1/s - u/transport @ 0\mod_1129815340342_3101.Doc @ 3170 @ 11 3 transport pos: 20.2 /Überschriften/1.1/1-spaltig/p - r/prüfung vor montage @ 0\mod_1140617479671_3101.Doc @ 3202 @ 22 3.1 inspection pos: 20.3 /transport/allgemein/...

  • Page 23

    Installation d184b111u02 coriolismaster fcm2000 23 pos: 22 /Überschriften/1/g - i/installation @ 0\mod_1129814872309_3101.Doc @ 3152 @ 11 4 installation pos: 23 /==== wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.Doc @ 3828 @ change from one to two columns pos: 24.1 /Überschriften/1.1...

  • Page 24

    Installation 24 coriolismaster fcm2000 d184b111u02 • care should be exercised to ensure that any dissolved gases, which may be present in many liquids, do not outgas. The back pressure at the outlet should be at least 0.2 bar (2,9 psi). • ensure that operation below the vapor pressure cannot occur w...

  • Page 25

    Installation d184b111u02 coriolismaster fcm2000 25 pos: 24.10 /technische daten / datenblatt/durchfluss/fcm2000/einbaubedingungen/mc2/horizontale einbaulage, selbstleerend @ 5\mod_1166448894656_3101.Doc @ 52608 @ 5 horizontal installations, self draining g00304 fig. 16: horizontal installations, sel...

  • Page 26

    Installation 26 coriolismaster fcm2000 d184b111u02 pos: 24.15 /Überschriften/1.1.1/1-spaltig/installationshinweise fcm2000-ms2 @ 11\mod_1168423213250_3101.Doc @ 57797 @ 33 4.1.3 installation notes fcm2000-ms2 pos: 24.16 /technische daten / datenblatt/durchfluss/fcm2000/einbaubedingungen/ms2/einbaula...

  • Page 27

    Installation d184b111u02 coriolismaster fcm2000 27 pos: 24.21 /technische daten / datenblatt/durchfluss/fcm2000/einbaubedingungen/ms2/drehwinkel-mehrfachstecker, vertikal @ 22\mod_1219396788593_3101.Doc @ 210027 @ 5 angle multi-connection plug, vertical a specific orientation of the connection box i...

  • Page 28

    Installation 28 coriolismaster fcm2000 d184b111u02 pos: 27 /Überschriften/1.1/1-spaltig/m - o/montage @ 0\mod_1129875293961_3101.Doc @ 3199 @ 22 4.2 installation pos: 28.1 /Überschriften/1.1.1/1-spaltig/allgemeine hinweise zur montage @ 8\mod_1177424551999_3101.Doc @ 86297 @ 33 4.2.1 general informa...

  • Page 29

    Installation d184b111u02 coriolismaster fcm2000 29 pos: 28.4 /montage/durchfluss/fcm2000/druckabbauventil @ 11\mod_1174897337000_3101.Doc @ 74295 @ 3 4.2.2 pressure relief valve pressure reduction valve. The pressure values are approximations. An exact specification of the absolute value at which a ...

  • Page 30

    Installation 30 coriolismaster fcm2000 d184b111u02 pos: 28.6 /montage/durchfluss/fcm2000/displaydrehung / gehäusedrehung @ 7\mod_1171887969671_3101.Doc @ 68600 @ 4.3 display / housing rotation 4.3.1 housing rotation depending on the installation position, the housing or display can be rotated to ena...

  • Page 31

    Installation d184b111u02 coriolismaster fcm2000 31 4.3.2 display rotation warning - general hazards! When the housing is open, emc protection is impaired and protection against contact is suspended. Before opening the housing, switch off power to all connecting cables. G00382 1 2 fig. 27: converter ...

  • Page 32

    Installation 32 coriolismaster fcm2000 d184b111u02 pos: 28.8 /Überschriften/1.1/1-spaltig/m - o/montage feldgehäuse / kompaktgerät @ 11\mod_1174474615000_3101.Doc @ 74027 @ 22 4.4 installation of the field-mount housing / compact unit pos: 28.9 /Überschriften/1.1.1/1-spaltig/Überprüfung @ 11\mod_117...

  • Page 33

    Installation d184b111u02 coriolismaster fcm2000 33 pos: 28.14 /montage/durchfluss/fcm2000/anschlussraum kompaktgerät @ 11\mod_1176714645218_3101.Doc @ 82516 @ 3 4.4.3 connection area for compact unit internal view of the cover a schematic interconnection diagram is located on the inside of the cover...

  • Page 34

    Installation 34 coriolismaster fcm2000 d184b111u02 pos: 28.16 /montage/durchfluss/fcm2000/anschlusskopf ms2 @ 11\mod_1178613502265_3101.Doc @ 90084 @ 3 4.4.4 connection head ms2 for remote installation attach the adapter (if not yet installed) to the top of the flowmeter primary interface. When atta...

  • Page 35

    Installation d184b111u02 coriolismaster fcm2000 35 pos: 30 /Überschriften/1.1/1-spaltig/d - f/elektrischer anschluss @ 0\mod_1132739463468_3101.Doc @ 3182 @ 22 4.5 electrical connection pos: 31.1 /elektrischer anschluss/durchfluss/fcm2000/konfektionierung des signal- und erregerstromkabels @ 7\mod_1...

  • Page 36

    Installation 36 coriolismaster fcm2000 d184b111u02 g00397 fig. 31 4.5.2 positioning the shield drain wire and foil shield g00455 fig. 32: insulating the signal cable and positioning the shield drain wire 1. Remove cable insulation as described in fig. 30. 2. Cut the woven shield to a length of appro...

  • Page 37

    Installation d184b111u02 coriolismaster fcm2000 37 observe the following items when routing cables: • the signal cable carries a voltage signal of only a few millivolts and therefore must be routed the shortest distance possible. The maximum permissible signal cable length is 50 m (164 ft.). • avoid...

  • Page 38

    Installation 38 coriolismaster fcm2000 d184b111u02 pos: 31.3.1 /technische daten / datenblatt/durchfluss/fcm2000/elektrischer anschluss/anschlussbeispiele @ 5\mod_1167922333234_3101.Doc @ 56359 @ 5555535 4.5.3 interconnection examples for peripherals dc outputs (incl. Hart) active passive g00326 +31...

  • Page 39

    Installation d184b111u02 coriolismaster fcm2000 39 profibus pa / foundation fieldbus g00248 2 ff- ff+ r c 1 97 pa- r c pa+ 98 97 98 i e i e the resistance r and condenser c form the bus termination. They must be installed when the device is connected to the end of the entire bus cable. R = 100 Ω; c ...

  • Page 40

    Installation 40 coriolismaster fcm2000 d184b111u02 pos: 31.3.3 /Überschriften/1.1.1/1-spaltig/anschlusspläne messumformer an durchflussaufnehmer @ 11\mod_1176713325500_3101.Doc @ 82454 @ 33 4.5.4 connection diagrams for transmitter to flowmeter sensor pos: 31.3.4 /technische daten / datenblatt/durch...

  • Page 41

    Installation d184b111u02 coriolismaster fcm2000 41 pos: 31.3.6 /Überschriften/1.1.1/1-spaltig/anschlusspläne messumformer an peripherie @ 11\mod_1176713598968_3101.Doc @ 82495 @ 33 4.5.5 connection diagrams for transmitter to peripherals pos: 31.3.7 /technische daten / datenblatt/durchfluss/fcm2000/...

  • Page 42

    Installation 42 coriolismaster fcm2000 d184b111u02 pos: 31.3.9 /technische daten / datenblatt/durchfluss/fcm2000/elektrischer anschluss/ein- / ausgangssignale me2 / ms2 @ 8\mod_1176817364515_3101.Doc @ 83873 @ 5 input and output signals, supply power me2/ms2 g00390 51 52 81 82 41 42 31 32 33 34 3 7 ...

  • Page 43

    Installation d184b111u02 coriolismaster fcm2000 43 pos: 31.3.11 /technische daten / datenblatt/durchfluss/fcm2000/elektrischer anschluss/profibus pa/foundation fieldbus @ 5\mod_1167922688843_3101.Doc @ 56380 @ 5 profibus pa / foundation fieldbus, supply power g00348 97 98 n 2- l 1+ 2 3 3 3 1 97 98 2...

  • Page 44

    Installation 44 coriolismaster fcm2000 d184b111u02 pos: 31.5 /Überschriften/1.1/1-spaltig/d - f/ex-technische daten @ 5\mod_1167982710593_3101.Doc @ 56635 @ 22 4.6 explosion protection data pos: 31.6 /Überschriften/1.1.1/1-spaltig/sicherheitstechnische daten der ein- und ausgänge @ 24\mod_1227712824...

  • Page 45

    Installation d184b111u02 coriolismaster fcm2000 45 pos: 31.7.5 /ex-technische daten/durchfluss/fcm2000/hinweise zu isolation @ 6\mod_1169211927484_3101.Doc @ 61924 @ 3 4.6.2 isolation: mc26.., mc27.. The pipeline and the flowmeter sensor insulation should be installed as shown. The max. Insulation t...

  • Page 46

    Installation 46 coriolismaster fcm2000 d184b111u02 pos: 31.7.8 /==== wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.Doc @ 3828 @ change from one to two columns pos: 31.7.9 /ex-technische daten/durchfluss/fcm2000/ex-zulassungen fm @ 8\mod_1176716681812_3101.Doc @ 82738 @ 33 4.6.3 ex-app...

  • Page 47

    Installation d184b111u02 coriolismaster fcm2000 47 pos: 33 /Überschriften/1.1/1-spaltig/d - f/digitale kommunikation @ 6\mod_1170934175875_3101.Doc @ 66313 @ 22 4.7 digital communication pos: 34 /==== wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.Doc @ 3828 @ change from one to two co...

  • Page 48

    Installation 48 coriolismaster fcm2000 d184b111u02 4.7.3 foundation fieldbus (ff) ff interface compliant with ff standard 890/ 891 and ff-902 interoperability test campaign no. It 027200 manufacturer id 0x000320 device id 0x0018 configuration • directly on the unit • via services integrated in the s...

  • Page 49

    Commissioning d184b111u02 coriolismaster fcm2000 49 pos: 38.1 /Überschriften/1/g - i/inbetriebnahme @ 0\mod_1131980668835_3101.Doc @ 3150 @ 11 5 commissioning pos: 38.2 /Überschriften/1.1/1-spaltig/a - c/allgemeine informationen @ 7\mod_1166522996531_3101.Doc @ 53066 @ 22 5.1 general information pos...

  • Page 50

    Commissioning 50 coriolismaster fcm2000 d184b111u02 pos: 38.6 /inbetriebnahme/durchfluss/fcm2000/kontrollen vor inbetriebnahme/gerät einstellen @ 9\mod_1178697886078_3101.Doc @ 90204 @ 5.1.2 device configuration the device can be factory calibrated to customer specifications upon request. If no cust...

  • Page 51

    Commissioning d184b111u02 coriolismaster fcm2000 51 pos: 38.8 /Überschriften/1.1/1-spaltig/j - l/kontrolle vor der inbetriebnahme @ 0\mod_1131981195011_3101.Doc @ 3486 @ 22 5.2 preliminary checks prior to start-up pos: 38.9 /inbetriebnahme/durchfluss/fcm2000/kontrollen vor inbetriebnahme/profibus pa...

  • Page 52

    Commissioning 52 coriolismaster fcm2000 d184b111u02 the address switch setting is only adopted when the device is restarted, not during running operation! A restart can be triggered by switching on the power supply or by software reset (factory_reset in physical block). The factory setting of the sw...

  • Page 53

    Commissioning d184b111u02 coriolismaster fcm2000 53 pos: 38.13 /Überschriften/1.1.1/1-spaltig/bedienschutzschalter @ 7\mod_1171892824968_3101.Doc @ 68982 @ 33 5.2.3 operating protection switch pos: 38.14 /inbetriebnahme/durchfluss/fcm2000/kontrollen vor inbetriebnahme/bedienschutzschalter @ 11\mod_1...

  • Page 54

    Commissioning 54 coriolismaster fcm2000 d184b111u02 pos: 38.16 /Überschriften/1.1/1-spaltig/g - i/hinweise für einen sicheren betrieb – atex (2007-11-21 13:30:44) @ 11\mod_1174377909473_3101.Doc @ 73263 @ 22 5.3 information for safe operation – atex pos: 38.17 /Überschriften/1.1.1/1-spaltig/Überprüf...

  • Page 55

    Commissioning d184b111u02 coriolismaster fcm2000 55 pos: 38.22 /Überschriften/1.1.1/1-spaltig/namur-kontakt @ 7\mod_1174378509430_3101.Doc @ 73347 @ 33 5.3.3 namur contact pos: 38.23 /inbetriebnahme/durchfluss/fcm2000/hinweise für sicheren betrieb - atex/namur-kontakt @ 7\mod_1174381080275_3101.Doc ...

  • Page 56

    Commissioning 56 coriolismaster fcm2000 d184b111u02 pos: 38.25 /ex-technische daten/durchfluss/fcm2000/anschlussräume (zeichnung) @ 6\mod_1169211654440_3101.Doc @ 61903 @ flowmeter sensor connecting box remote connecting box connecting box mc26 ii 2g eex em [ib] iic t6 ii 1/2g eex em [ib] iic t6 ii ...

  • Page 57

    Commissioning d184b111u02 coriolismaster fcm2000 57 pos: 38.28 /inbetriebnahme/durchfluss/fcm2000/hinweise fĂźr sicheren betrieb - atex/hinweise fĂźr sicheren betrieb - atex @ 7\mod_1174468731953_3101.Doc @ 73943 @ the safety specifications for the intrinsically safe circuits may be found in the ec-ty...

  • Page 58

    Commissioning 58 coriolismaster fcm2000 d184b111u02 pos: 38.31 /Überschriften/1.1/1-spaltig/g - i/hinweise für einen sicheren betrieb – fm @ 11\mod_1174377998583_3101.Doc @ 73284 @ 22 5.4 information for safe operation – fm pos: 38.32 /Überschriften/1.1.1/1-spaltig/Überprüfung @ 11\mod_1174378401273...

  • Page 59

    Commissioning d184b111u02 coriolismaster fcm2000 59 pos: 38.35 /Überschriften/1.1.1/1-spaltig/klassen nach fm @ 7\mod_1174472807453_3101.Doc @ 74006 @ 33 5.4.2 classes per fm pos: 38.36 /inbetriebnahme/durchfluss/fcm2000/hinweise für sicheren betrieb - fm/klassen nach fm @ 7\mod_1174472656500_3101.D...

  • Page 60

    Parameterization 60 coriolismaster fcm2000 d184b111u02 pos: 40 /Überschriften/1/p - r/parametrierung @ 0\mod_1132314985710_3101.Doc @ 3160 @ 11 6 parameterization pos: 41.1 /konfiguration, parametrierung/durchfluss/fcm2000/dateneingabe @ 7\mod_1175003771750_3101.Doc @ 74484 @ 2 after the power to th...

  • Page 61

    Parameterization d184b111u02 coriolismaster fcm2000 61 enter function for magnet stick operation the enter function is initiated when the data / enter sensor is activated for more than 3 seconds. The display flashes to indicate that the function is active. There are two different methods of entering...

  • Page 62

    Parameterization 62 coriolismaster fcm2000 d184b111u02 pos: 41.3 /konfiguration, parametrierung/durchfluss/fcm2000/dateneingabe in kurzform @ 11\mod_1183538279921_3101.Doc @ 109583 @ 2 6.2 entering data in “short form” action input display information → v 98.14 % starting point for “process informat...

  • Page 63

    Parameterization d184b111u02 coriolismaster fcm2000 63 pos: 41.5 /Überschriften/1.1/1-spaltig/p - r/parameterübersicht @ 11\mod_1173965749953_3101.Doc @ 72483 @ 22 6.3 parameter overview pos: 41.6 /konfiguration, parametrierung/durchfluss/fcm2000/parameterübersicht @ 7\mod_1171893992125_3101.Doc @ 6...

  • Page 64

    Parameterization 64 coriolismaster fcm2000 d184b111u02 parameter value range / input type note densimass code 4289794 if ordered with densimass option, this menu shows the order specific densimass code. If the densimass shall be activated after shipping the meter, please contact your abb service or ...

  • Page 65

    Parameterization d184b111u02 coriolismaster fcm2000 65 parameter value range / input type note unit name enter enter any unit name. Baume min. Concentr. Enter enter of min. Valid concentration value. 0.00 baume max. Concentr. Enter enter of max. Valid concentration value. 100.00 baume submenu matrix...

  • Page 66

    Parameterization 66 coriolismaster fcm2000 d184b111u02 parameter value range / input type note submenu unit in this submenu the units can be defined for the measured variables (mass flowrate, density and temperature) and for the calculated variables (volume flowrate and mass or volume flow totals). ...

  • Page 67

    Parameterization d184b111u02 coriolismaster fcm2000 67 parameter value range / input type note units factor technician* float 50.0000 kg in this menu the number of kilograms equivalent to one programmable mass flow unit are entered. Minimum value: 0.00001 kg maximum value: 5000000 kg submenu technic...

  • Page 68

    Parameterization 68 coriolismaster fcm2000 d184b111u02 parameter value range / input type note qmmax qmaxdn float 100.00 kg/min the flow range can be set between the limits from 0.01 ... 1.0 qmmax meter pipe and applies to both flow directions. Qmmax is the value used as the basis for the qm- curren...

  • Page 69

    Parameterization d184b111u02 coriolismaster fcm2000 69 parameter value range / input type note system zero adj. -0.0111 % after pressing „enter“ the selection of whether a manual or automatic zero adjustment is to conducted can be made using „data“ or „step“. System zero adj. Function automatic? The...

  • Page 70

    Parameterization 70 coriolismaster fcm2000 d184b111u02 parameter value range / input type note max alarm qm 0 ... 105 % float 100.00 % technician* set the upper mass flowrate limit. It must be greater than the lower mass flowrate limit. Minimum: 0 % maximum: 105 % min alarm 0.5 ... 3.5 kg/l 0.5 kg/l...

  • Page 71

    Parameterization d184b111u02 coriolismaster fcm2000 71 parameter value range / input type note submenu display the process display can be user formatted for numerous display combinations. 1st line q [bar graph] table selection of line 1 q [%] qm qv q [%] (see additional parameter descriptions page 8...

  • Page 72

    Parameterization 72 coriolismaster fcm2000 d184b111u02 parameter value range / input type note 1st line multiplex q [bar graph] table qv qm qv q [%] temperature density concentr. Unit concentr. Percent qm concentration tag number totalizer mass totalizer mass → f totalizer mass ← r totalizer volumes...

  • Page 73

    Parameterization d184b111u02 coriolismaster fcm2000 73 parameter value range / input type note submenu totalizer submenu totalizer mass this menu contains additional submenus for the totalizers for the mass and volume flow integration and one menu to simultaneously reset all the totalizers. All four...

  • Page 74

    Parameterization 74 coriolismaster fcm2000 d184b111u02 parameter value range / input type note submenu volume totalizer totalizer volumes totalizer → f display display of totalizer status; forward totalizer 123456.78 l input overflow → f display 0 number of totalizer overflows; 1 overflow = 10000000...

  • Page 75

    Parameterization d184b111u02 coriolismaster fcm2000 75 parameter value range / input type note submenu example for an external counter: 1 kg = 1 pulse pulse output output of mass / volume float mass 0.0001 ... 1000 pulse/unit in this menu the selection can be made if the pulse output should be based...

  • Page 76

    Parameterization 76 coriolismaster fcm2000 d184b111u02 parameter value range / input type note qv → l = 100 % 0.1 ... 10000000 float 120.00 l/min in this menu the volume flowrate value is entered for which the current output is to indicate its 100 % value (20 ma). The menu is only displayed when the...

  • Page 77

    Parameterization d184b111u02 coriolismaster fcm2000 77 parameter value range / input type note current output 0 ... 20 ma table 4 ... 20 ma 4 ... 20 ma technician* used to define the current output range. The current output can be switched between 0 ... 20 ma and 4 ... 20 ma. Hart communication util...

  • Page 78

    Parameterization 78 coriolismaster fcm2000 d184b111u02 parameter value range / input type note submenu current output 2 in contrast to current output 1, current output 2 is not hart-enabled and has a fixed current output range (4 ... 20 ma). In submenu current output 2, dependent on the measurement ...

  • Page 79

    Parameterization d184b111u02 coriolismaster fcm2000 79 parameter value range / input type note temp → l = 100 % -50 ... 180 float 180.0 °c in this menu the temperature value is entered for which the current output is to indicate its 100 % value (20 ma). The menu is only displayed when the current ou...

  • Page 80

    Parameterization 80 coriolismaster fcm2000 d184b111u02 parameter value range / input type note contact output no function no function f/r-signal _ f/r-signal / contact output general alarm _ max alarm_ _ general alarm / max/min alarm _ max/min alarm / min alarm _ min alarm / max alarm _ max alarm / ...

  • Page 81

    Parameterization d184b111u02 coriolismaster fcm2000 81 parameter value range / input type note submenu included only with hart software. Interface communication hart hart off technician* the communication type can be selected. Available selections are: • hart • off unit address 0 ... 15 integer 0 te...

  • Page 82

    Parameterization 82 coriolismaster fcm2000 d184b111u02 parameter value range / input type note ai2 channel tb mass flow only contained in the profibus pa software. Tb density tb temperature tb totmass > v tb totmass tb totvol > v tb totvol tb volume flow ai3 channel tb mass flow only contained in th...

  • Page 83

    Parameterization d184b111u02 coriolismaster fcm2000 83 parameter value range / input type note tot2 channel tb mass flow only contained in the profibus pa software. Tb volume flow tb diagextmask bit-wise selection 0x080001fe0fff of alarms this can be used to select the bits of the error register to ...

  • Page 84

    Parameterization 84 coriolismaster fcm2000 d184b111u02 parameter value range / input type note function test on float iout 2 off technician* iout 2 this function can be used to set a value for the current output independent of the variable assigned to the current output, for test purposes. A current...

  • Page 85

    Parameterization d184b111u02 coriolismaster fcm2000 85 parameter value range / input type note qm measure table enter enter enter this menu can be used to measure the actual mass flowrate while in the simulation mode. Qm -115 ... +115 % float 15.00 % technician* the mass flowrate value for the simul...

  • Page 86

    Parameterization 86 coriolismaster fcm2000 d184b111u02 parameter value range / input type note submenu status the following queries can be performed: • error log • warning register • power outage error log number: 3 displays the sum of all detected and active errors. Use „enter“ to display the first...

  • Page 87

    Parameterization d184b111u02 coriolismaster fcm2000 87 parameter value range / input type note fcm2000 10.2008 d699g001u01 b.30 in the first line the instrument designation is displayed (fcm2000) and the revision date of the software (e.G., 10.2008). In the second line, the software designation (d69...

  • Page 88

    Parameterization 88 coriolismaster fcm2000 d184b111u02 pos: 41.8 /Überschriften/1.1/1-spaltig/v - z/zusätzliche parameterbeschreibungen @ 11\mod_1175243628218_3101.Doc @ 75304 @ 22 6.4 additional parameter descriptions pos: 41.9 /konfiguration, parametrierung/durchfluss/fcm2000/zusätzliche parameter...

  • Page 89

    Parameterization d184b111u02 coriolismaster fcm2000 89 only contained within profibus pa software pa addr+state display of pa address and state tb massflow val display of the respective value of the transducer block tb massflow stat display of the respective state of the transducer block tb volflow ...

  • Page 90

    Parameterization 90 coriolismaster fcm2000 d184b111u02 6.4.2 submenu pulse output example 1 a new pulse width is entered settings input qmmax = 24 kg/min = 0.4 kg/s totalizer unit kg pulse factor = 100 pulses /kg pulse width 10 ms → 0.4 kg/s ⋅ 100 pulse/kg = 40 pulse/s → frequency = 40 hz → period =...

  • Page 91

    Parameterization d184b111u02 coriolismaster fcm2000 91 pos: 41.11 /Überschriften/1.1.1/1-spaltig/konzentrationsmessung densimass @ 23\mod_1226413442156_3101.Doc @ 224287 @ 33 6.4.3 concentration measurement densimass pos: 41.12 /konfiguration, parametrierung/durchfluss/fcm2000/konzentrationsmessung ...

  • Page 92

    Parameterization 92 coriolismaster fcm2000 d184b111u02 calculation of accuracy the accuracy of the concentration computation depends foremost on the quality of the matrix data. As density and temperature measurement is the input for the calculation both accuracies define the accuracy of the concentr...

  • Page 93

    Parameterization d184b111u02 coriolismaster fcm2000 93 pos: 41.14 /konfiguration, parametrierung/durchfluss/fcm2000/software-historie @ 7\mod_1171894144875_3101.Doc @ 69131 @ 6.5 software history according to namur recommendation ne53, abb offers a transparent and traceable software history. 6.5.1 s...

  • Page 94

    Parameterization 94 coriolismaster fcm2000 d184b111u02 6.5.2 fieldbus version profibus pa software d699g001u02 software version revision date type of changes documentation a.1x 01.05.2006 new release foundation fieldbus software d699g001u03 software version revision date type of changes documentatio...

  • Page 95

    Error messages d184b111u02 coriolismaster fcm2000 95 pos: 43 /Überschriften/1/d - f/fehlermeldungen @ 0\mod_1132064208078_3101.Doc @ 3146 @ 11 7 error messages pos: 44.1 /fehlermeldungen/durchfluss/fcm2000/alarmübersicht @ 11\mod_1175062836031_3101.Doc @ 74543 @ 2 7.1 alarm overview the tables on th...

  • Page 96

    Error messages 96 coriolismaster fcm2000 d184b111u02 pos: 44.3 /fehlermeldungen/durchfluss/fcm2000/alarmĂźbersicht tabelle @ 23\mod_1226667608261_3101.Doc @ 225023 @ measurement variable totalizer current output priority error no. Error descript io n qm [% ] qv [ % ] density [g/cm 3 ] tem p erat ure ...

  • Page 97

    Error messages d184b111u02 coriolismaster fcm2000 97 pos: 44.5 /Überschriften/1.1/1-spaltig/a - c/beschreibung der warnungen @ 11\mod_1175074174328_3101.Doc @ 74685 @ 22 7.2 description of the warnings pos: 44.6 /fehlermeldungen/durchfluss/fcm2000/warnungen tabelle @ 11\mod_1175074674625_3101.Doc @ ...

  • Page 98

    Error messages 98 coriolismaster fcm2000 d184b111u02 pos: 44.8 /Überschriften/1.1/1-spaltig/a - c/beschreibung der fehlermeldungen @ 11\mod_1175074248734_3101.Doc @ 74726 @ 7.3 description of error messages pos: 44.9 /fehlermeldungen/durchfluss/fcm2000/fehlermeldungen tabelle @ 7\mod_1171894439781_3...

  • Page 99

    Error messages d184b111u02 coriolismaster fcm2000 99 error code and clear text priority description possible causes corrective measures incorrect wiring (only for remote design) check wiring between flowmeter primary and converter error: 7b t instrument housing measurement 12 erroneous temperature -...

  • Page 100

    Maintenance / repair 100 coriolismaster fcm2000 d184b111u02 pos: 46.1 /Überschriften/1/v - z/wartung / reparatur @ 0\mod_1132065140479_3101.Doc @ 3171 @ 11 8 maintenance / repair pos: 46.2 /wartung / reparatur/durchfluss/fxe4000/allgemeine hinweise (standard) @ 2\mod_1150794975328_3101.Doc @ 31016 @...

  • Page 101

    Maintenance / repair d184b111u02 coriolismaster fcm2000 101 pos: 46.6 /wartung / reparatur/allgemein/1.1 reinigung @ 0\mod_1132066200463_3101.Doc @ 3550 @ 2 8.2 cleaning when cleaning the exterior of meters, make sure that the cleaning agent used does not corrode the housing surface and the seals. P...

  • Page 102

    Spare parts list 102 coriolismaster fcm2000 d184b111u02 pos: 48 /Überschriften/1/d - f/ersatzteilliste @ 0\mod_1132129676467_3101.Doc @ 3144 @ 11 9 spare parts list pos: 49 /ersatzteiliste/durchfluss/fcm2000/messumformer me2 @ 7\mod_1172133118984_3101.Doc @ 69505 @ cover large (rear view) view witho...

  • Page 103

    Spare parts list d184b111u02 coriolismaster fcm2000 103 g00385 1 fig. 61: fuse in field-mount housing 1 fuse field-mount housing g00386 1 fig. 62: fuse in transmitter module 1 fuse in module pos: 50 /======= seitenumbruch ======== @ 0\mod_1126532365768_3101.Doc @ 3830 @.

  • Page 104

    Technical data 104 coriolismaster fcm2000 d184b111u02 pos: 51 /Überschriften/1/s - u/technische daten @ 0\mod_1132904574837_3101.Doc @ 3169 @ 11 10 technical data pos: 52 /==== wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.Doc @ 3828 @ change from one to two columns pos: 53.1 /Übersch...

  • Page 105

    Technical data d184b111u02 coriolismaster fcm2000 105 10.1.2 materials and additional technical data materials of flowmeter sensor fluid-wetted parts stainless steel 1.4571 / 1.4308 (316ti / cf8) stainless steel 1.4435 / 316l hastelloy c4/2.4610 with flowmeter material 1.4435 certified acc. To ehedg...

  • Page 106

    Technical data 106 coriolismaster fcm2000 d184b111u02 pos: 53.4 /Überschriften/1.1/1-spaltig/m - o/modell fcm2000-ms2 @ 11\mod_1172135843687_3101.Doc @ 69589 @ 22 10.2 model fcm2000-ms2 pos: 53.5 /technische daten / datenblatt/durchfluss/fcm2000/technische daten/messaufnehmer/modell fcm2000-ms2 @ 11...

  • Page 107

    Technical data d184b111u02 coriolismaster fcm2000 107 pressure loss curves viscosity [cst] ∆ p [bar ] g00317 0,1 0,1 1,0 10 100 0,01 1 10 70 [kg/h] 10 00 50 0 20 0 10 0 50 20 10 5 1 fig. 68: pressure losses ms21, dn 1.5 (1/16”) viscosity [cst] ∆ p [bar ] g00318 3 0,1 1,0 10 10 100 300 [kg/h] 1 00 0 ...

  • Page 108

    Technical data 108 coriolismaster fcm2000 d184b111u02 pos: 53.7 /==== wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.Doc @ 3829 @ change from one to two columns pos: 53.8 /Überschriften/1.1/1-spaltig/m - o/messumformer @ 7\mod_1172139386968_3101.Doc @ 69610 @ 10.3 transmitter pos: 53.9...

  • Page 109

    Appendix d184b111u02 coriolismaster fcm2000 109 pos: 56.1 /Überschriften/1/a - c/anhang @ 0\mod_1132904773022_3101.Doc @ 3134 @ 11 11 appendix pos: 56.2 /Überschriften/1.1/1-spaltig/v - z/weitere dokumente @ 0\mod_1134369962894_3101.Doc @ 3218 @ 22 11.1 additional documents pos: 56.3 /anhang/durchfl...

  • Page 110

    Appendix 110 coriolismaster fcm2000 d184b111u02 pos: 56.8 /zertifikate/durchfluss/fcm2000/eg-konformitätserklärung @ 24\mod_1227010300386_0.Doc @ 227237 @.

  • Page 111

    Appendix d184b111u02 coriolismaster fcm2000 111 pos: 56.9 /zertifikate/durchfluss/fcm2000/eg-baumusterprĂźfbescheinigung_atex_1443_x @ 24\mod_1227011659745_3101.Doc @ 227261 @.

  • Page 112

    Appendix 112 coriolismaster fcm2000 d184b111u02.

  • Page 113

    Appendix d184b111u02 coriolismaster fcm2000 113.

  • Page 114

    Appendix 114 coriolismaster fcm2000 d184b111u02.

  • Page 115

    Appendix d184b111u02 coriolismaster fcm2000 115.

  • Page 116

    Appendix 116 coriolismaster fcm2000 d184b111u02.

  • Page 117

    Appendix d184b111u02 coriolismaster fcm2000 117.

  • Page 118

    Appendix 118 coriolismaster fcm2000 d184b111u02.

  • Page 119

    Appendix d184b111u02 coriolismaster fcm2000 119.

  • Page 120

    Appendix 120 coriolismaster fcm2000 d184b111u02.

  • Page 121

    Appendix d184b111u02 coriolismaster fcm2000 121 pos: 56.10 /zertifikate/durchfluss/fcm2000/eg-konformitätserklärung_dgrl @ 24\mod_1227012045777_0.Doc @ 227285 @.

  • Page 122

    Appendix 122 coriolismaster fcm2000 d184b111u02 pos: 56.11 /zertifikate/durchfluss/fcm2000/ehedg-zertifikat @ 24\mod_1227012151464_0.Doc @ 227309 @.

  • Page 123

    Appendix d184b111u02 coriolismaster fcm2000 123 pos: 56.12 /======= seitenumbruch ======== @ 0\mod_1126532365768_3101.Doc @ 3830 @.

  • Page 124

    Appendix 124 coriolismaster fcm2000 d184b111u02 pos: 56.13 /anhang/durchfluss/fcm2000/Übersicht geräteparameter und technische ausführung @ 7\mod_1172133965125_3101.Doc @ 69526 @ 2 11.3 overview of setting parameters and technical design measuring point: tag no.: flowmeter model: converter type: ord...

  • Page 125

    Appendix d184b111u02 coriolismaster fcm2000 125 pos: 56.15 /anhang/allgemein/rĂźcksendeformular @ 0\mod_1132757486454_3101.Doc @ 3820 @ statement on the contamination of devices and components repair and/or maintenance work will only be performed on devices and components if a statement form has been...

  • Page 126

    Index 126 coriolismaster fcm2000 d184b111u02 pos: 58 /Überschriften/1/g - i/index @ 0\mod_1138787046328_3101.Doc @ 3151 @ 11 12 index pos: 59 /==== wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.Doc @ 3828 @ change from one to two columns pos: 60 /inhaltsverzeichnis/index @ 0\mod_11387...

  • Page 127

    Index d184b111u02 coriolismaster fcm2000 127 s safety.........................................................................6 safety information for electrical installation .............14 safety instructions for transport...............................14 sicherheitstechnische daten der ein- und a...

  • Page 128

    Abb has sales & customer support expertise in over 100 countries worldwide. Www.Abb.Com/flow the company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. Printed in the fed. Rep. Of germany (12.2008) © abb 2008 d18...