ABB IEC 60870-5-103 Communication Protocol Manual

Manual is about: Relion 670 series

Summary of IEC 60870-5-103

  • Page 1

    Relion® 670 series — iec 60870-5-103, 670 series version 2.2 communication protocol manual.

  • Page 3

    Document id: 1mrk 511 394-uen issued: october 2017 revision: a product version: 2.2 .1 © copyright 2017 abb. All rights reserved.

  • Page 4

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and...

  • Page 5

    Disclaimer the data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intende...

  • Page 6

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents section 1 introduction.......................................................................5 this manual........................................................................................ 5 intended audience.......................................................................

  • Page 8

    Settings.................................................................................. 29 supported information types.................................................. 29 function status earth-fault for iec 60870-5-103 i103ef.............29 functionality.............................................

  • Page 9

    Signals....................................................................................42 settings.................................................................................. 42 supported information types.................................................. 43 function commands user defined ...

  • Page 10

    Common address of asdu......................................................... 56 selection of standard information numbers in monitor direction..56 system functions in monitor direction.....................................56 status indications in monitor direction.....................................

  • Page 11

    Section 1 introduction 1.1 this manual guid-ab423a30-13c2-46af-b7fe-a73bb425eb5f v18 the communication protocol manual describes the communication protocols supported by the ied. The manual concentrates on the vendor-specific implementations. 1.2 intended audience guid-c9b8127f-5748-4bea-9e4f-cc762f...

  • Page 12

    1.3 product documentation 1.3.1 product documentation set guid-3aa69ea6-f1d8-47c6-a8e6-562f29c67172 v15 iec07000220-4-en.Vsd p la nn in g & p ur ch as e e ng in ee rin g in st al lin g c om m is si on in g o pe ra tio n m ai nt en an ce d ec om m is si on in g d ei ns ta lli ng & d is po sa l applic...

  • Page 13

    Describes the process of testing an ied in a substation which is not in service. The chapters are organized in the chronological order in which the ied should be commissioned. The relevant procedures may be followed also during the service and maintenance activities. The operation manual contains in...

  • Page 14

    1.3.3 related documents guid-94e8a5ca-be1b-45af-81e7-5a41d34ee112 v5 documents related to reb670 document numbers application manual 1mrk 505 370-uen commissioning manual 1mrk 505 372-uen product guide 1mrk 505 373-ben technical manual 1mrk 505 371-uen type test certificate 1mrk 505 373-ten document...

  • Page 15

    Documents related to ret670 document numbers application manual 1mrk 504 163-uen commissioning manual 1mrk 504 165-uen product guide 1mrk 504 166-ben technical manual 1mrk 504 164-uen type test certificate 1mrk 504 166-ten documents related to res670 document numbers application manual 1mrk 511 407-...

  • Page 16

    1.4 document symbols and conventions 1.4.1 symbols guid-2945b229-dab0-4f15-8a0e-b9cf0c2c7b15 v12 the electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. The cauti...

  • Page 17

    For example, select main menu/settings . • lhmi messages are shown in courier font. For example, to save the changes in non-volatile memory, select yes and press . • parameter names are shown in italics. For example, the function can be enabled and disabled with the operation setting. • each functio...

  • Page 18

    12.

  • Page 19

    Section 2 iec 60870-5-103 overview 2.1 iec 60870-5-103 standard guid-69ba3944-3809-43d0-a558-55fa2b87319b v7 iec 60870-5-103 is defined as a companion standard for the informative element of protection equipment. While the official iec 60870-5-103 standard dates back to 1997, the protocol has its ro...

  • Page 20

    A very limited set of application data informative elements has been defined by the standard. It should also be noticed that these sets of data are mainly defined for a single function protection ied. The ieds in turn are multifunctional protection and control ieds whose internal data model is based...

  • Page 21

    When communicating locally in the station using a personal computer (pc) or a remote terminal unit (rtu) connected to the communication and processing module, the only hardware needed is optical fibres and an opto/electrical converter for the pc/rtu, or a rs-485 connection depending on the used ied ...

  • Page 22

    16.

  • Page 23

    Section 3 iec 60870-5-103 communication engineering 3.1 iec 60870-5-103 engineering in pcm600 3.1.1 engineering in pcm600 guid-284eb0ba-bc79-4b90-8b78-878ba225479e v7 the application configuration tool (act) and the parameter setting tool (pst) in pcm600 are used to configure the communication for i...

  • Page 24

    • timesyncmode • evaltimeaccuracy • eventrepmode • cmdmode • repintermediatepos is: • “optical103:1” for the optical serial channel on the slm • “rs485103:1” for the rs485 port 2. The protocol to activate on a physical port is selected under: main menu/configuration/communication/station communicati...

  • Page 25

    If eventrepmode = hiprispont , spontaneous events will be delivered prior to gi event. To prevent old gi data from being delivered after a new spontaneous event, the pending gi event is modified to contain the same value as the spontaneous event. As a result, the gi dataset is not time-correlated. 3...

  • Page 26

    Iedtimeskew . But in linmasttime it applies the time changes occurred between two synchronization messages. • iedtimeskew : the ied measures the offset in between its own time and the master time and applies the same offset for the messages sent. • evaltimeaccuracy evaluates time accuracy for invali...

  • Page 27

    Pid-6610-settings v5 table 3: optical103 non group settings (basic) name values (range) unit step default description slaveaddress 1 - 254 - 1 1 slave address baudrate 9600 bd 19200 bd - - 9600 bd baudrate on serial line revpolarity off on - - on invert polarity cycmeasreptime 1.0 - 1800.0 s 0.1 5.0...

  • Page 28

    22.

  • Page 29

    Section 4 iec 60870-5-103 vendor specific implementation m11874-23 v4 the signal and setting tables specify the information types supported by the ieds with the communication protocol iec 60870-5-103 implemented. The information types are supported when corresponding functions are included in the pr...

  • Page 30

    4.1.1.2 function block guid-ec5f1c83-0f47-4548-86e3-ffe056571241 v2 iec10000287-1-en.Vsd i103meas block il1 il2 il3 in ul1 ul2 ul3 ul1l2 un p q f iec10000287 v1 en-us figure 5: i103meas function block 4.1.1.3 signals pid-6625-inputsignals v4 table 4: i103meas input signals name type default descript...

  • Page 31

    Name values (range) unit step default description maxin 1 - 99999 a 1 3000 maximum residual current in maxul1 0.05 - 2000.00 kv 0.05 230.00 maximum voltage for phase l1 maxul2 0.05 - 2000.00 kv 0.05 230.00 maximum voltage for phase l2 maxul3 0.05 - 2000.00 kv 0.05 230.00 maximum voltage for phase l3...

  • Page 32

    Inf description 148 ul2 148 ul3 145, 146 ul1-ul2 147 un, neutral voltage 146, 148 p, active power 146, 148 q, reactive power 148 f, frequency 4.1.2 measurands user defined signals for iec 60870-5-103 i103measusr 4.1.2.1 functionality guid-fc9ed4bd-f11c-4bda-8cdb-3acf00931d3a v1 i103measusr is a func...

  • Page 33

    Name type default description input6 real 0.0 service value for measurement on input 6 input7 real 0.0 service value for measurement on input 7 input8 real 0.0 service value for measurement on input 8 input9 real 0.0 service value for measurement on input 9 4.1.2.4 settings pid-3791-settings v5 tabl...

  • Page 34

    Table 9: i103measusr supported indications inf fun gi typ cot description * 1) * 2) no, polled with cl2 * 3) 2,7 meas1 * * no, polled with cl2 * 2,7 meas2 * * no, polled with cl2 * 2,7 meas3 * * no, polled with cl2 * 2,7 meas4 * * no, polled with cl2 * 2,7 meas5 * * no, polled with cl2 * 2,7 meas6 *...

  • Page 35

    4.1.3.3 signals pid-3973-inputsignals v5 table 10: i103ar input signals name type default description block boolean 0 block of status reporting 16_aract boolean 0 information number 16, auto-recloser active 128_cbon boolean 0 information number 128, circuit breaker on by auto-recloser 130_blkd boole...

  • Page 36

    4.1.4.2 function block guid-25b47484-2976-4063-bd81-ae02d03b08b0 v1 iec10000290-1-en.Vsd i103ef block 51_effw 52_efrev iec10000290 v1 en-us figure 8: i103ef function block 4.1.4.3 signals pid-3974-inputsignals v5 table 13: i103ef input signals name type default description block boolean 0 block of s...

  • Page 37

    4.1.5 function status fault protection for iec 60870-5-103 i103fltprot 4.1.5.1 functionality guid-6d52f442-1592-4ba7-919c-0cd79046cae5 v1 i103fltprot is used for fault indications in monitor direction. Each input on the function block is specific for a certain fault type and therefore must be connec...

  • Page 38

    4.1.5.3 signals pid-6864-inputsignals v1 table 16: i103fltprot input signals name type default description block boolean 0 block of status reporting. 64_stl1 boolean 0 information number 64, start phase l1 65_stl2 boolean 0 information number 65, start phase l2 66_stl3 boolean 0 information number 6...

  • Page 39

    Name type default description 93_ief boolean 0 information number 93, earth-fault trip, stage high arinprog boolean 0 autorecloser in progress (smbrrec- inprogr) fltloc boolean 0 faultlocator faultlocation valid (lmbrflo- calcmade) 4.1.5.4 settings pid-6864-settings v1 table 17: i103fltprot non grou...

  • Page 40

    Inf description typ gi cot 82 zone 5 2 n 1,7 83 zone 6 2 n 1,7 84 start general 2 y 1,7,9 85 breaker failure 2 n 1,7 86 trip measuring system phase l1 2 n 1,7 87 trip measuring system phase l2 2 n 1,7 88 trip measuring system phase l3 2 n 1,7 89 trip measuring system neutral n 2 n 1,7 90 over curren...

  • Page 41

    Name type default description 23_grp1 boolean 0 information number 23, setting group 1 is active 24_grp2 boolean 0 information number 24, setting group 2 is active 25_grp3 boolean 0 information number 25, setting group 3 is active 26_grp4 boolean 0 information number 26, setting group 4 is active 4....

  • Page 42

    4.1.7.2 function block guid-69c2c974-2d64-4174-9f9a-15383c09050d v1 iec10000293-1-en.Vsd i103superv block 32_measi 33_measu 37_ibkup 38_vtff 46_grwa 47_gral iec10000293 v1 en-us figure 11: i103superv function block 4.1.7.3 signals pid-3976-inputsignals v5 table 22: i103superv input signals name type...

  • Page 43

    Table 24: i103superv supported functions inf description typ gi cot 32 measurand supervision i 1 y 1,7,9 33 measurand supervision u 1 y 1,7,9 37 i>>back-up operation 1 y 1,7,9 38 vt fuse failure 1 y 1,7,9 46 group warning 1 y 1,7,9 47 group alarm 1 y 1,7,9 4.1.8 status for user defined signals for i...

  • Page 44

    4.1.8.3 signals pid-6485-inputsignals v5 table 25: i103usrdef input signals name type default description block boolean 0 block of status reporting input1 boolean 0 binary signal input 1 input2 boolean 0 binary signal input 2 input3 boolean 0 binary signal input 3 input4 boolean 0 binary signal inpu...

  • Page 45

    Name values (range) unit step default description typno2 absolute relative - - absolute type identification (typ) typno3 absolute relative - - absolute type identification (typ) typno4 absolute relative - - absolute type identification (typ) typno5 absolute relative - - absolute type identification ...

  • Page 46

    4.1.8.5 supported information types function status indications in monitor direction, user-defined, i103usrdef m11874-137 v7 function indication block in monitor direction with user-defined input signals. Number of instances: 20 function type is selected with parameter functiontype . Information num...

  • Page 47

    4.2.1.3 signals pid-3969-inputsignals v5 table 28: i103cmd input signals name type default description block boolean 0 block of commands pid-3969-outputsignals v5 table 29: i103cmd output signals name type description 16-ar boolean information number 16, off/on of autorecloser 17-diff boolean inform...

  • Page 48

    4.2.2 ied commands for iec 60870-5-103 i103iedcmd 4.2.2.1 functionality guid-19ad44b2-21d6-4db0-ad74-1578da30c100 v5 i103iedcmd is a command block in control direction with defined ied functions. All outputs are pulsed and they are not stored. Pulse length is fixed to 400ms. 4.2.2.2 function block g...

  • Page 49

    4.2.2.5 supported information types commands in control direction, i103iedcmd m11874-29 v6 command block in control direction with defined output signals. Number of instances: 1 function type is selected with parameter functiontype . Information number is defined for each output signals. Table 35: i...

  • Page 50

    Pid-3790-outputsignals v5 table 37: i103usrcmd output signals name type description output1 boolean command output 1 output2 boolean command output 2 output3 boolean command output 3 output4 boolean command output 4 output5 boolean command output 5 output6 boolean command output 6 output7 boolean co...

  • Page 51

    Table 39: i103usrcmd supported indications inf 1) description 1 output signal 01 2 output signal 02 3 output signal 03 4 output signal 04 5 output signal 05 6 output signal 06 7 output signal 07 8 output signal 08 1) user defined information number 4.2.4 function commands generic for iec 60870-5-103...

  • Page 52

    Pid-3970-outputsignals v5 table 41: i103gencmd output signals name type description cmd_off boolean command output off cmd_on boolean command output on 4.2.4.4 settings pid-3970-settings v5 table 42: i103gencmd non group settings (basic) name values (range) unit step default description functiontype...

  • Page 53

    When input block is on, the function will ignore gi requests and cease all monitoring activity. Consequently, no transitions will be detected. The i103poscmd function is also equipped with two additional commands: operate and cancel. These are hidden in act and respond only to base inf +2 and +3 res...

  • Page 54

    Table 45: each i103poscmd has four inf forming four commands and two indications inf inst 1 inst 2 inst 3... Inst 10 type cot purpose comment base + 0 160 164 168 196 20 20 direct operate set position direct base + 1 161 165 169 197 20 20 select select before operate base + 2 162 166 170 198 20 20 o...

  • Page 55

    4.2.6.2 function block guid-031c0f49-bebd-40fe-a33f-18f1d94bb4b0 v1 i103poscmdv block position iec15000081-2-en.Vsdx iec15000081 v2 en-us figure 18: i103poscmdv function block 4.2.6.3 signals pid-6578-inputsignals v5 table 46: i103poscmdv input signals name type default description block boolean 0 b...

  • Page 56

    4.3 disturbance recorder file transfer 4.3.1 disturbance recordings m17109-111 v9 • the transfer functionality is based on the disturbance recorder function. The analog and binary signals recorded will be reported to the master by polling. The eight last disturbances that are recorded are available ...

  • Page 57

    Number can be set to any value between 0 and 255. To get inf and fun for the recorded binary signals, there are parameters on the disturbance recorder for each input. The user must set these parameters to whatever he connects to the corresponding input. Refer to description of main function type set...

  • Page 58

    Dra#-input acc iec 60870-5-103 meaning 30 85 private range 31 86 private range 32 87 private range 33 88 private range 34 89 private range 35 90 private range 36 91 private range 37 92 private range 38 93 private range 39 94 private range 40 95 private range m11874-629 v7 disturbance upload all anal...

  • Page 59

    The only information that is easily available is test-mode status. The other information is always set (hard coded) to: tp recorded fault with trip. [1] tm disturbance data waiting for transmission [0] otev disturbance data initiated by other events [1] another information element in asdu23 is the f...

  • Page 60

    54.

  • Page 61

    Section 5 interoperability 5.1 physical layer guid-c1f320e5-e383-40f0-96e5-a811acb5c785 v1 5.1.1 electrical interface guid-9568e530-6ccc-4058-9aca-fb89027d0302 v3 table 50: electrical interface supported eia rs-485 yes number of loads 32 5.1.2 optical interface guid-072191b0-f840-4f11-b3ba-27a8bd0dd...

  • Page 62

    5.3 application layer guid-3d10fba6-f562-4050-8a3e-3860ecca9c0b v1 5.3.1 transmission mode for application data guid-0020f6c3-3c0d-4a0f-8c00-4b3a71c36853 v1 mode 1 (least significant octet first), as defined in 4.10 of iec 60870-5-4, is used exclusively in this companion standard. 5.3.2 common addre...

  • Page 63

    Inf semantics supported 23 characteristic 1 yes 24 characteristic 2 yes 25 characteristic 3 yes 26 characteristic 4 yes 27 auxiliary input 1 no 28 auxiliary input 2 no 29 auxiliary input 3 no 30 auxiliary input 4 no 5.3.3.3 supervision indications in monitor direction guid-458558ff-192d-43e5-9367-ca...

  • Page 64

    5.3.3.5 fault indications in monitor direction guid-5ff248c0-1b2c-467b-93ea-b0e0cfff715b v4 table 58: fault indications in monitor direction inf semantics supported 64 start /pick-up l 1 yes 65 start /pick-up l 2 yes 66 start /pick-up l 3 yes 67 start /pick-up n yes 68 general trip yes 69 trip l 1 y...

  • Page 65

    5.3.3.6 auto-reclosure indications in monitor direction guid-88f9afd6-6464-4de1-aecb-595142bdcdb3 v2 table 59: auto-reclosure indications in monitor direction inf semantics supported 128 cb ‘on’ by ar yes 129 cb ‘on’ by long-time ar no 130 ar blocked yes 5.3.3.7 measurands in monitor direction guid-...

  • Page 66

    5.3.4.2 general commands in control direction guid-83f365bb-62f9-4e34-a291-73430639b898 v2 table 63: general commands in control direction inf semantics supported 16 auto-recloser on/off yes 17 teleprotection on/off yes 18 protection on/off yes 19 led reset yes 23 activate characteristic 1 yes 24 ac...

  • Page 67

    5.3.6 miscellaneous guid-ed83483d-eded-4558-af63-bc2137f7b36a v4 measurands are transmitted with asdu 3 as well as with asdu 9. As defined in 7.2.6.8, the maximum mval can either be 1,2 or 2,4 times the rated value. No different rating shall be used in asdu 3 and asdu 9, i.E. For each measurand ther...

  • Page 68

    62.

  • Page 69

    Section 6 glossary 6.1 glossary m14893-1 v16 ac alternating current acc actual channel act application configuration tool within pcm600 a/d converter analog-to-digital converter adbs amplitude deadband supervision adm analog digital conversion module, with time synchronization ai analog input ansi a...

  • Page 70

    Cb circuit breaker cbm combined backplane module ccitt consultative committee for international telegraph and telephony. A united nations-sponsored standards body within the international telecommunications union. Ccm can carrier module ccvt capacitive coupled voltage transformer class c protection ...

  • Page 71

    Dfc data flow control dft discrete fourier transform dhcp dynamic host configuration protocol dip-switch small switch mounted on a printed circuit board di digital input dllb dead line live bus dnp distributed network protocol as per ieee std 1815-2012 dr disturbance recorder dram dynamic random acc...

  • Page 72

    Gcm communication interface module with carrier of gps receiver module gde graphical display editor within pcm600 gi general interrogation command gis gas-insulated switchgear goose generic object-oriented substation event gps global positioning system gsal generic security application gse generic s...

  • Page 73

    Ied intelligent electronic device iet600 integrated engineering tool i-gis intelligent gas-insulated switchgear iom binary input/output module instance when several occurrences of the same function are available in the ied, they are referred to as instances of that function. One instance of a functi...

  • Page 74

    Mvb multifunction vehicle bus. Standardized serial bus originally developed for use in trains. Ncc national control centre nof number of grid faults num numerical module oco cycle open-close-open cycle ocp overcurrent protection oem optical ethernet module oltc on-load tap changer otev disturbance d...

  • Page 75

    Rs422 a balanced serial interface for the transmission of digital data in point-to-point connections rs485 serial link according to eia standard rs485 rtc real-time clock rtu remote terminal unit sa substation automation sbo select-before-operate sc switch or push button to close scl short circuit l...

  • Page 76

    Tcp transmission control protocol. The most common transport layer protocol used on ethernet and the internet. Tcp/ip transmission control protocol over internet protocol. The de facto standard ethernet protocols incorporated into 4.2bsd unix. Tcp/ip was developed by darpa for internet working and e...

  • Page 77

    Phonetic alphabet stands for "z", which stands for longitude zero. Uv undervoltage wei weak end infeed logic vt voltage transformer x.21 a digital signalling interface primarily used for telecom equipment 3i o three times zero-sequence current.Often referred to as the residual or the earth-fault cur...

  • Page 78

    72.

  • Page 79

    73.

  • Page 80

    — abb ab grid automation products 721 59 västerås, sweden phone: +46 (0) 21 32 50 00 abb.Com/protection-control © copyright 2017 abb. All rights reserved. Specifications subject to change without notice. 1mrk 511 394-uen.