ABB MicroSCADA Pro SYS 600C 2.93 Product Manual

Summary of MicroSCADA Pro SYS 600C 2.93

  • Page 1

    Microscada pro sys 600c 2.93 product guide.

  • Page 2

    Trace back information: workspace main version a11 checked in 2012-11-13.

  • Page 3: Contents

    Contents 5 1 copyrights ............................................................................................. 6 2 introduction ........................................................................................... 6 2.1 this manual ..........................................................

  • Page 4

    29 5 product structure .................................................................................. 29 5.1 ordering, delivery, and life cycle policy ......................................... 29 5.1.1 computer ........................................................................ 29 5.1.2 ope...

  • Page 5: Copyrights

    1 copyrights the information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may appear in this document. In no event shall abb oy be liable for direct, indirect, special, incidental or c...

  • Page 6: Introduction

    2 introduction 2.1 this manual this manual provides product information on the compact system sys 600c (later referred to as sys 600c). It gives an overview of the product functionality, key benefits, application areas, technical details, and capacity and performance. 2.2 use of symbols this publica...

  • Page 7

    Document id name of the document 1mrs756646 sys 600 9.3 system configuration 1mrs757728 sys 600c user's guide 2.4 document revisions history date product version revision document created 16.11.2012 2.93 a 7 sys 600c 2.93 microscada pro product guide 1mrs757729 16.11.2012 issued: a/16.11.2012 versio...

  • Page 8: Functional Overview

    3 functional overview sys 600c is a modular and scalable automation system that can be configured and tailored for various applications and needs. This chapter gives an overview of the main functionality. 3.1 process communication the process communication is used to connect various process devices,...

  • Page 9

    Type protocol master and slave iec 60870-5-104 client iec 61850-8 master ansi x3.28 - ab (abb) master and slave rp 570/571 master and slave dnp 3.0 (subset 3) master and slave modbus client opc da, a&e server opc da, a&e 3.2 sys 600c workplaces 3.2.1 workplaces sys 600c can be equipped with 1 to 5 w...

  • Page 10

    Figure 3.1: process display 3.2.2.1 system self supervision the system self supervision function shows the status of the various system components in a display for easy and fast system maintenance and fault localization. The display shows information about the base system, applications, redundancy, ...

  • Page 11

    Figure 3.2: an example of typical system supervision display 3.2.3 event display with the event display you can monitor the information about events occurring in the system. Thus, you can make the right decisions and verify that taken measures have been successfully performed. You can also receive i...

  • Page 12

    Figure 3.3: event display the event display presents the data in a structured way for the user’s convenience. Each event is one row in the display. With default settings event display rows consist of a time stamp, object identification, a signal text and a text indicating the status. 3.2.4 alarm dis...

  • Page 13

    Figure 3.4: alarm display template 1 figure 3.5: alarm display template 2 the alarm display contains the following features and options: • two types of alarm display templates • filters • alarm display setting tool for colors and text layout • updating/frozen modes • alarm acknowledgement • alarm re...

  • Page 14

    • column sort • find 3.2.5 blocking display the blocking display summarizes the present blocking situation of signals in the supervised process. Each signal is presented as a signal row, which describes the signal in the process. The signal text row normally consists of a signal text and a group of ...

  • Page 15

    3.2.6 trends display the trends display is used for trend analyses and for showing measured values in the form of a curve or a table. A trend is a time-related follow-up of process data. All types of process objects, for example in and out data, binary, analog and digital data can be illustrated as ...

  • Page 16

    • authorization support • copy to clipboard • export to csv file 3.2.7 measurement reports display the measurement reports display is an application that collects data and visualizes the data in a numerical or graphical form. The measurement reports display is used to log and report data during long...

  • Page 17

    3.3 historian historian is a subsystem dedicated for fast and efficient data logging, data refinement and information visualisation. The flexible historian can store all process data for long periods and refine the data into meaningful information. This gives a clear view of the situation in the pri...

  • Page 18

    Or data object. The following data types can be logged in the historian: process objects: binary input (bi), binary output (bo), double binary input (db), digital input (di), digital output (do), analog input (ai), analog output (ao), pulse counter (pc), data objects with numerical value. Historian ...

  • Page 19

    3.5 localization it is possible to translate the user interface to any language that fits into the boundaries of the graphical user interface, that is, size, position, and direction of texts and icons. The system also supports several languages simultaneously enabling operators to work with the syst...

  • Page 20

    The network chipset used in the sys 600c supports intel teaming with advanced networking services. Teaming can be used to provide additional fault tolerance in case of a port or a switch failure, as well as for load balancing and link aggregation. The restrictions and possibilities of interface team...

  • Page 21

    - configurable password policies - configurable logon/warning banners - configurable session time-out feature • user authorization: users can be granted access rights to functions as required • communication encryption: encryption of tcp/ip connections (ipsec/vpn) • virus protection • patch manageme...

  • Page 22

    - powerful data collection to be used in single line diagrams, process displays, trends, reports, control, alarms, and events - process displays with support for zoom/pan/de-clutter - trends with zoom/pan, multiple graph types, ruler, cut, and paste 22 1mrs757729 microscada pro sys 600c 2.93 product...

  • Page 23: Application Areas

    4 application areas 4.1 overview sys 600c provides innovative solutions for different tasks and operations in the power automation process, from communication gateway functionality to full-fledged redundant control system applications. Sys 600c is a solid-state computer utilizing information distrib...

  • Page 24

    4.2 sys 600c as communication gateway sys 600c is used for multiple purposes at a substation level. The communication gateway function is one of the tasks that can be utilized at the substation level to enable connections to remote control centers (scada). Sys 600c communication gateway can connect ...

  • Page 25

    For increased availability, sys 600c can easily be configured as a redundant communication gateway as shown in figure 4.3. Figure 4.3: sys 600c as redundant communication gateway sys 600c also supports redundant remote communication lines between sys 600c and remote control center as shown in figure...

  • Page 26

    Figure 4.5: sys 600c as control system hsi to reduce the number of devices at the substation level, sys 600c control system hsi and the communication gateway function can be combined in the same computer as shown in figure 4.6. Figure 4.6: sys 600c as combined control system hsi and communication ga...

  • Page 27

    Figure 4.8: sys 600c as control system hsi for rtu 4.4 sys 600c as communication server sys 600c can function as a powerful communication server in medium and large remote control center configurations as well as in large substation automation applications. Sys 600c with its large number of serial c...

  • Page 28

    Figure 4.10: sys 600c as communication servers in a large substation automation system by utilizing the sys 600c communication server solution the processing load in the main system servers sys 600 or sys 600c is reduced. The communication servers are connected to the process devices and provide the...

  • Page 29: Product Structure

    5 product structure 5.1 ordering, delivery, and life cycle policy sys 600c is a product that combines the robust solid-state computer with the operating system and the sys 600 software. 5.1.1 computer the computer exists in a number of fixed configurations that is selected during ordering. The fixed...

  • Page 30

    5.1.4 product identification the sys 600c product is identified by the computer version and the sys 600 software version. Example: sys 600c 2.93 hardware version 2, sys 600 software version: 9.3 5.2 software options 5.2.1 communication protocols the following tables list the communication protocols ...

  • Page 31

    Slave protocol f4f westinghouse, no gateway support modbus rtu (cpi) 5.2.2 hsi features the following table lists the sys 600c hsi features. Table 5.3: user interface options value description user interface option 0...10 this is the number of workplaces that are in use simultan- eously. The number ...

  • Page 32

    Value description user interface option yes/no select this option, if you want to integrate lib 520 ied tools in the workplace. Lib 520 ied tools if you use only the ied tools in the workplace, no other lib license in needed. Yes/no select this option, if you want to integrate lib 530 ied tools in t...

  • Page 33

    Value description system option and interface yes/no this option should be selected, if the database mirroring functions are used and this system acts as a host. The host is the system that provides process data to another system. Database mirror- ing host for example, if you use mirroring between a...

  • Page 34

    Value description system option and interface 0...4 the opc a&e client is used to connect foreign devices to sys 600 by means of the opc a&e interface. Opc a&e client you need one client for each server that is to be connec- ted. Yes/no the sql export option provides a tool and functions for browsin...

  • Page 35: Hardware Characteristics

    6 hardware characteristics 6.1 hardware the following tables lists the sys 600c hardware specifications. Table 6.1: hardware specifications intel® core 2 duo 2.2ghz (t7400) cpu intel® 82945gm and ich7r chipset 2gb ddr2 memory intel® 82945 chipset integrated graphic controller vga award bios bios 30g...

  • Page 36

    Operating: -30°c ~ +65°c (-22 °f ~ 149°f) temperature (maximum continuous cpu burden 50% of lowest/highest operating temperature) storage: -40°c ~ +75°c (-40 °f ~167°f) 25 years (+25°c / 77°f) mtbf 22 years (+40°c / 104°f) 5% ~ 95% (+40°c / 104°f) non-condensing relative humidity ip40 protection cla...

  • Page 37

    Table 6.3: ieee std 1613-2003 standard compliance severity level description type test level 4- ±4kv 5khz all ports eft ieee c37.90.1 level 4 -±8kv contact/±15kv air esd ieee c37.90.3 level 3-2.5kv common/differ- ential 1.25kv for substation oscillatory wave ieee c37.90.1 2000vrms dielectric strengt...

  • Page 38: Capacity And Performance

    7 capacity and performance 7.1 sys 600c capacity this chapter gives an overview of the capacity of sys 600c regarding the following functions or aspects: • number of ieds that can be connected • usage of the following functions: workplaces and process displays, gateway, mirroring, hsb • data logging...

  • Page 39

    • number of events: 3 000 000 • number of logged values: 90 000 000 the maximum number of logged values corresponds roughly to 400 measurements sampled every 15 minutes and stored for 1 + 5 years (current year + 5 years of history). 7.3 process communication capacity the capacity of one protocol mea...

  • Page 40

    Modbus tcp 200 nr of ieds limited mostly by maximum response time 15 nr of ieds / line dnp serial 200 nr of ieds limited mostly by maximum response time 15 nr of ieds / line dnp lan if i/o count is small, number of ieds can be bigger 200 nr of ieds 15 nr of ieds / line table 7.2: impact on process c...

  • Page 41

    • ncc connection with two iec 104 lan communications including 116 ieds resulting in 2 800 process updates per second sent to two nccs *) 90% 16-bit analog data without time, 5% binary data without time and 5% binary data with time the following list shows some examples when ieds are connected to sy...

  • Page 42: Abbreviations

    8 abbreviations description abbreviation basic input/output system bios distributed control system dcs electromagnetic interference emi electromagnetic shielding ems human system interface hsi intelligent electronic device ied internet protocol ip local area network lan light emitting diode led mean...

  • Page 44

    Contact us 1mrs757729 a/16.11.2012 © copyright 2012 abb. All rights reserved. Abb oy substation automation products p.O. Box 699 fi-65101 vaasa finland tel. +358 10 22 11 fax. +358 10 224 1094 www.Abb.Com/substationautomation.