Microscada pro sys 600c 1.92 product guide.
Contents: 1. Copyrights ............................................................................................... 5 2. Introduction ............................................................................................. 6 2.1. This manual ....................................................
7. Capacity and performance .................................................................. 36 7.1. Sys 600c capacity ...................................................................... 36 7.2. Data logging capacity ................................................................... 36 7.3. Pr...
Copyrights 1. The information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may appear in this document. In no event shall abb oy be liable for direct, indirect, special, incidental or ...
Introduction 2. This manual 2.1. This manual provides product information on the compact system sys 600c (later referred to as sys 600c). It gives an overview of the product functionality, key benefits, application areas, technical details, and capacity and performance. Use of symbols 2.2. This publ...
Description abbreviation personal computer pc adobe acrobat file format pdf simple network management protocol snmp simple network time protocol sntp product name sys 600 product name sys 600c universal serial bus usb related documents 2.4. Document id name of the document 1mrs756805 sys 600c user's...
Functional overview 3. Sys 600c is a modular and scalable automation system that can be configured and tailored for various applications and needs. This chapter gives an overview of the main functionality. Process communication 3.1. The process communication is used to connect various process device...
Type protocol master and slave iec 60870-5-104 client iec 61850-8 master ansi x3.28 - ab (abb) master and slave rp 570 master and slave dnp 3.0 (subset 3) master and slave modbus client opc da, a&e server opc da, a&e sys 600c workplaces 3.2. Workplaces 3.2.1. Sys 600c can be equipped with 1 to 5 wor...
Through the process display the user can continuously monitor the process, such as switches and measurements, as well as access the control dialogs to issue commands, set parameters, and so on. C_20090111.Png figure 3.2.2-1 process display system self supervision the system self supervision function...
As possible. It can also be freely configured to display the information, the layout, and coloring of the events. It is also possible to have predefined filters that can easily be accessed from toolbars and menus. C_20090112.Png figure 3.2.3-1 event display alarm display 3.2.4. The alarm display sho...
C_20090113.Png figure 3.2.4-1 alarm display blocking display 3.2.5. The blocking display lists all active blockings in the system. The display can also be used to activate new blockings. The following aspects of a signal can be blocked: updating, control, event logging, alarm generation, event print...
C_20090114.Png figure 3.2.5-1 blocking display trends display 3.2.6. The trends display is an application that collects data and visualizes the data in a numerical or graphical form. It is used for following up and analyzing data in time frames from minutes to one month. The data is logged cyclicall...
C_20090115.Png figure 3.2.6-1 trends display measurement reports display 3.2.7. The measurement reports display is an application that collects data and visualizes the data in a numerical or graphical form. The measurement reports display is used to log and report data during longer periods than the...
C_20090116.Png figure 3.2.7-1 measurement reports display user management 3.3. Users of the system are given access rights according to the needs. The user sessions can be limited in time. The users can be given the right to view, control, or configure the different parts of the system or process. L...
Time synchronization 3.5. Sys 600c can be synchronized by an external gps clock. This is typically done using sntp over the local area network or through a serial port using a protocol provided by the clock manufacturer. It is also possible to add a pci card into the computer to retrieve the clock s...
The advantage of using data mirroring instead of standard communication, such as iec 60870-5-104, is that the data mirroring communication is much more efficient and the required engineering work to build up the system is minimal. Several special functions, such as event buffering during communicati...
• integrated tools for system engineering, for example expansion of databases, communication system, hsi clients, and users • support for third-party software and hardware through the use of open interface and communication • easy to upgrade with latest software versions that enable use of new and i...
Application areas 4. Overview 4.1. Sys 600c provides innovative solutions for different tasks and operations in the power automation process, from communication gateway functionality to full-fledged redundant control system applications. Sys 600c is a solid-state computer utilizing information distr...
Sys 600c as communication gateway 4.2. Sys 600c is used for multiple purposes at a substation level. The communication gateway function is one of the tasks that can be utilized at the substation level to enable connections to remote control centers (scada). Sys 600c communication gateway can connect...
For increased availability, sys 600c can easily be configured as a redundant commu- nication gateway as shown in figure 4.2-3. C_20090103.Bmp figure 4.2-3 sys 600c as redundant communication gateway sys 600c also supports redundant remote communication lines between sys 600c and remote control cente...
C_20090105.Bmp figure 4.3-1 sys 600c as control system hsi to reduce the number of devices at the substation level, sys 600c control system hsi and the communication gateway function can be combined in the same computer as shown in figure 4.3-2. C_20090106.Bmp figure 4.3-2 sys 600c as combined contr...
C_20090108.Bmp figure 4.3-4 sys 600c as control system hsi for rtu sys 600c as communication server 4.4. Sys 600c can function as a powerful communication server in medium and large remote control center configurations as well as in large substation automation applications. Sys 600c with its large n...
C_20090110.Bmp figure 4.4-2 sys 600c as communication servers in a large substation automation system by utilizing the sys 600c communication server solution the processing load in the main system servers sys 600 or sys 600c is reduced. The communication servers are connected to the process devices ...
Product structure 5. Ordering, delivery, and life cycle policy 5.1. Sys 600c is a product that combines the robust solid-state computer with the operating system and the sys 600 software. Hardware the hardware configuration cannot be changed after order (concerning the parts supplied by the abb prod...
Sys 600 software the sys 600 software can be extended or upgraded to new versions. This is done with the normal ordering tool with the upgrade/extension options. Sys 600 hotfixes and service packs can also be freely taken into use. New sys 600 versions will be available for the sys 600c hardware for...
Master protocol iec 61107 (metering) alpha meter protocol rcom table 5.2.1-2 slave protocols slave protocol iec 60870-5-101, single or redundant iec 60870-5-104, single or redundant dnp 3.0 lan/wan dnp 3.0 serial rp 570/rp 571 f4f westinghouse, no gateway support modbus rtu (cpi) hsi features 5.2.2....
Value description user interface option yes/no select this option, if you want to use the trend displays in the workplaces. Trends yes/no select this option, if you want to use the event list displays in the workplaces. Event list yes/no select this option, if you want to use the alarm list displays...
Table 5.2.3-1 system size parameters value description system size parameters 1..20 000 gateway functionality (com 500i) supports maximum 14 000 indications and 14 000 commands configured within sys 600c. Number of process objects connected to the process process i/o table 5.2.3-2 system options and...
Value description system option and interface yes/no this option should be selected, if the database mirroring func- tions are used and this system acts as a host. The host is the system that provides process data to another system. For example, if you use mirror- ing between a communication server ...
Value description system option and interface 0...4 this is a da client that is loosely coupled to the sys 600 base system and can therefore be installed also in a separate computer. It is used to connect opc da servers to sys 600. You need one client for each server that is to be connected. Note: t...
Hardware power supply: 176 - 264 vac / 200 - 370 vdc (single or redundant) ethernet ports 6 x rj45 ethernet ports 2 x rj45 + 4 x lc table 5.3-2 operating systems operating system windows xp professional, english version windows xp professional, chinese version windows server 2003, english version wi...
Hardware characteristics 6. Hardware 6.1. The following tables lists the sys 600c hardware characteristics. Table 6.1-1 hardware specifications and dimensions intel® core 2 duo 2.2ghz (t7400) cpu intel® 82945gm and ich7r chipset 2gb ddr2 memory intel® 82945 chipset integrated graphic controller vga ...
Emi/ems and environmental standard compliance 6.2. The following tables list the emi/ems and environmental standard compliance. Table 6.2-1 iec 61850-3 standard compliance severity level description type test level 4 -±8kv contact/±15kv air electrostatic discharge iec 61000-4-2-2001 level 3-18v/m, 6...
Severity level description type test level vr3- ≤5% voltage ripple of dc iec 60870-2-1-1995 -40°c~+75°c nonoperational temperature range ieee c37.90 -30°c (start up)~+65°c operational temperature range ieee c37.90 table 6.2-3 environmental standard compliance severity level description type test -30...
Capacity and performance 7. Sys 600c capacity 7.1. This chapter gives an overview of the capacity of sys 600c regarding the following functions or aspects: • number of ieds that can be connected • usage of the following functions: workplaces and process displays, gateway, mir- roring, hsb • data log...
This corresponds to: • number of events: 3 000 000 • number of logged values: 90 000 000 the maximum number of logged values corresponds roughly to 400 measurements sampled every 15 minutes and stored for 1 + 5 years (current year + 5 years of history). Process communication capacity 7.3. The capaci...
Limited mostly by maximum response time 15 nr of ieds / line modbus rtu 200 nr of ieds limited mostly by maximum response time 15 nr of ieds / line modbus tcp 200 nr of ieds limited mostly by maximum response time 15 nr of ieds / line dnp serial 200 nr of ieds limited mostly by maximum response time...
Comments impact on process com- munication function per workplace with measurement reports with 15 min report total of 900 objects data logged by measurement reports - 1% reports workpace with data logging the following list shows some examples when ieds are connected to sys 600c with the following ...
40