ABB PowerValue 11 RT 10 kVA User Manual

Summary of PowerValue 11 RT 10 kVA

  • Page 1

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 1/37 abb modifications reserved powervalue 11 rt 6-10 kva user manual 04-3788_abb_opm_pva11 6-10kva-rt_en_140423 © copyright 2014 abb, all rights reserved..

  • Page 2

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 2/37 abb modifications reserved.

  • Page 3: Foreword

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 3/37 abb modifications reserved foreword the ups system operates with mains, battery or bypass power. It contains components that carry high currents and voltages. The properly installed ups system is grounded to earth and ip 20 rated against electrica...

  • Page 4

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 4/37 abb modifications reserved contents foreword ........................................................................................................................ 3 symbols ..........................................................................

  • Page 5

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 5/37 abb modifications reserved 4 communication ..................................................................................................... 30 4.1 rs-232 port.......................................................................................

  • Page 6: 1  Safety Instructions

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 6/37 abb modifications reserved 1 safety instructions 1.1 operator precautions the user must follow the precautions and only perform the described operations. Also in these measures the operator of the ups system must adhere to the instructions in this...

  • Page 7

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 7/37 abb modifications reserved • en-iec 60950-1. It equipment. Safety. Part 1: general requirements. • en-iec 62040-2. Uninterruptible power supply (ups). Part 2: emc requirements. The supplier’s responsibility is excluded in the event of any modifica...

  • Page 8

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 8/37 abb modifications reserved 1.6 maintenance, servicing and faults repairs may be carried out only by qualified maintenance personnel as the ups operates with hazardous voltages. Warning! Even after the unit is disconnected from the mains power supp...

  • Page 9: 2 Installation

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 9/37 abb modifications reserved 2 installation 2.1 delivery, transportation, positioning and storage 2.1.1 receipt of the ups and visual inspection upon receiving the ups, carefully examine the packing container and the ups for any sign of physical dam...

  • Page 10

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 10/37 abb modifications reserved 2.2.2 positioning powervalue 11 rt can be mounted in a rack or in a standalone configuration. Follow the instructions in this section accordingly to the installation requirements. Note that water condensing may occur if...

  • Page 11

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 11/37 abb modifications reserved powervalue 11 rt 10kva warning! This type of connection must be carried out by qualified electrical personnel. Connect an appropriate breaker between ups and batteries. 1. Plug the battery module cable into the ups batt...

  • Page 12

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 12/37 abb modifications reserved powervalue 11 rt 10 kva 1. Carefully rotate the lcd control panel of 90º to the right in top and bottom front panels. Figure 7: display rotation 2. Rotate the units to the vertical position 3. Screw the supports to the ...

  • Page 13

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 13/37 abb modifications reserved figure 9: powervalue 11 rt 6 kva rear view figure 10: powervalue 11 rt 10 kva rear view 2.4 electrical installation 2.4.1 commissioning the ups must be commissioned by a fully trained and authorized field service engine...

  • Page 14

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 14/37 abb modifications reserved model 6 kva 10 kva protective earth (pe) conductor (minimum cross section) 6mm2 (8 awg) 10mm2 (6 awg) input l, n, g ( minimum cross section) 6mm2 (8 awg) 10mm2 (6 awg) input fuse 60a 80a output l,n, g (minimum cross sec...

  • Page 15

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 15/37 abb modifications reserved warning! The cabling connections must be carried out by qualified electrical personnel. Single input feed connections in the single input feed configuration, there is a single ac input to the ups (inverter and bypass). ...

  • Page 16

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 16/37 abb modifications reserved dual input feed connections in the dual input feed configuration, two separate ac inputs are connected to the ups (one for the inverter and one for the bypass). Figure 18: ups diagram with dual input feed when the earth...

  • Page 17

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 17/37 abb modifications reserved figure 23: dual input feed connections for 10kva units frequency converter connections powervalue 11 rt can work as a frequency converter. In such configuration, only the input and output should be connected as indicate...

  • Page 18

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 18/37 abb modifications reserved 2.5 initial startup warning! Switch off the connected loads before turning on the ups. Switch on the loads one by one after the ups is turned on. 1. Verify that the total equipment ratings does not exceed the ups capaci...

  • Page 19

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 19/37 abb modifications reserved 2.7.2 installing a new parallel system 1. Before installing a new parallel ups system, prepare the input and output wires, the input and output breakers and the parallel cable. Follow the instructions in section 2.4.2 2...

  • Page 20

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 20/37 abb modifications reserved 2.7.3 adding an ups to an existing parallel system 1. Install a main maintenance mechanical switch or static switch for the parallel system. 2. Regulate the output voltage of the new ups. Check if the output voltage dif...

  • Page 21: 3 Operation

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 21/37 abb modifications reserved 3 operation this chapter describes how to operate the ups through the lcd display. Warning! Only persons which have been trained by service technicians of the supplier or his authorized service partners are allowed to o...

  • Page 22

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 22/37 abb modifications reserved 3.1.2 lcd display the lcd display gives the user a complete overview on the status of the ups. It shows information on the input, output, battery, load parameters, working-mode and also the settings on voltage, frequenc...

  • Page 23

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 23/37 abb modifications reserved status symbol description online-mode ups is running through the inverter (online-mode) battery-mode ups running on battery. (the alarm buzzer sounds every 4 seconds.) bypass-mode the power used by the load is supplied ...

  • Page 24

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 24/37 abb modifications reserved note: the bypass-mode is enabled by default and this can be configured through the user’s settings (see table 1. Without mains supply (cold start) 1. Check that all cables are connected correctly and well-fixed mechanic...

  • Page 25

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 25/37 abb modifications reserved 3.4.2 navigation to navigate through the ups screens, the scroll buttons are used. From the main screen, press or for information on alarm, parallel system and battery. From the main screen, press for more than 1s to en...

  • Page 26

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 26/37 abb modifications reserved note 1: when the clear epo status is enabled, the ups will stop alarming and will recover in bypass-mode. In this case, the ups needs be turned on by manual operation. Example: clearing the epo status figure 34: clear e...

  • Page 27

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 27/37 abb modifications reserved 3.4.2.4 identification press on the identification menu to navigate through its data. The identification information includes ups serial number, firmware serial number and-model type. Press >1s to return to the last mai...

  • Page 28

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 28/37 abb modifications reserved submenu item description optional values default value eco mode (he) voltage low limit when the voltage in the bypass is below this limit, the ups changes running mode. 5%~10% 5% eco mode (he) voltage high limit when th...

  • Page 29

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 29/37 abb modifications reserved example: setting the rated output voltage value (figure 38). Note: the ups must be in bypass to change this parameter. Figure 38: setting rated output voltage value.

  • Page 30: 4 Communication

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 30/37 abb modifications reserved 4 communication a usb and an rs-232 port are available to enable the communication between the ups and a remote computer/station. Only one communication port can be active at a time and the priority is given to the usb ...

  • Page 31

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 31/37 abb modifications reserved 4.3 network management card (optional) powervalue 11 rt is equipped with an intelligent slot for other optional cards for remote management of the ups through internet / intranet. Please contact your local supplier for ...

  • Page 32: 5 Maintenance

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 32/37 abb modifications reserved 5 maintenance powervalue 11 (6-10 kva) rt ups only requires minimal maintenance. The only requirement is to charge the ups regularly in order to maximize the expected life of the battery. When being connected to the mai...

  • Page 33: 6 Troubleshooting

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 33/37 abb modifications reserved 6 troubleshooting 6.1 fault identification and rectification alarm and events identify warning situations and notify errors or potential failures of the system. The output of the ups is not necessarily affected in case ...

  • Page 34

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 34/37 abb modifications reserved alarm or event possible cause remedy utility abnormal alarm code: 02 the input mains is out of the ups tolerance range check input mains condition site wiring fault alarm code: 04 site fault detection is supported on al...

  • Page 35

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 35/37 abb modifications reserved alarm or event possible cause remedy on maintenance bypass alarm code: 72 ups was manually switched to bypass and will remain in bypass until manually transferred out of bypass check the maintain bypass switch status he...

  • Page 36

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 36/37 abb modifications reserved 7 technical specification general data 6000 va 10000 va output rated power [w] 5400 w 9000 w output power factor 0.9 topology true online double conversion parallel configuration up to 2 units inbuilt batteries yes inpu...

  • Page 37

    04-3788_abb_opm_pva11 6-10kva-rt_en_140423 page 37/37 abb modifications reserved 614-00798-00