ABB REB650 2.1 IEC Product Manual

Manual is about: Busbar protection, Relion 650 series

Summary of REB650 2.1 IEC

  • Page 1

    Relion ® 650 series busbar protection reb650 2.1 iec product guide.

  • Page 2

    Contents 1. Application..................................................................... 3 2. Available functions..........................................................5 3. Differential protection....................................................12 4. Current protection........................

  • Page 3

    1. Application guid-f13c1639-4853-4305-84ca-d9648b0648b0 v3 the numerical high impedance differential busbar protection reb650 ied provides its users with a wide variety of application opportunities. Designed primarily for the protection of single busbar with or without sectionalizers in high impeda...

  • Page 4

    Wa1 wa2 high impedance busbar protection for up to 3 zones 12ai (9i + 3u) s scbr s scbr s scbr s scbr s scbr s scbr drp rdre dfr/ser dr zone1 _ ct zone2 _ ct zone3 _ ct qa1 qa1 qa1 zone 1 zone 2 zone 3 (used in this example as check zone) qb2 qa1 qb1 qa1 qb1 qa1 qb1 qb1 qa1 qb1 qa1 qb1 qb1 qb1 cv mm...

  • Page 5

    2. Available functions main protection functions guid-66baad98-851d-4aac-b386-b38b57718bd2 v12 table 1. Example of quantities 2 = number of basic instances 0-3 = option quantities 3-a03 = optional function included in packages a03 (refer to ordering details) iec 61850 ansi function description busba...

  • Page 6

    Control and monitoring functions guid-e3777f16-0b76-4157-a3bf-0b6b978863de v13 iec 61850 ansi function description busbar reb650 (a03) control qcbay apparatus control 1 locrem handling of lrswitch positions 1 locremctrl lhmi control of psto 1 slgapc logic rotating switch for function selection and l...

  • Page 7

    Iec 61850 ansi function description busbar reb650 (a03) itbgapc integer to boolean 16 conversion with logic node representation 16 teigapc elapsed time integrator with limit transgression and overflow supervision 12 intcomp comparator for integer inputs 12 realcomp comparator for real inputs 12 moni...

  • Page 8

    Table 2. Total number of instances for basic configurable logic blocks basic configurable logic block total number of instances and 328 gate 40 inv 468 lld 40 or 472 pulsetimer 40 rsmemory 40 srmemory 40 timerset 60 xor 40 1mrk 505 362-ben b busbar protection reb650 2.1 iec product version: 2.1 8 ab...

  • Page 9

    Communication guid-5f144b53-b9a7-4173-80cf-cd4c84579cb5 v13 iec 61850 ansi function description busbar reb650 (a03) station communication lonspa, spa spa communication protocol 1 ade lon communciation protocol 1 horzcomm network variables via lon 1 protocol operation selection between spa and iec 60...

  • Page 10

    Iec 61850 ansi function description busbar reb650 (a03) fstaccs, fstaccsna field service tool access via spa protocol over ethernet communication 1 activlog activity logging parameters 1 altrk service tracking 1 singlelcch single ethernet port link status 1 prpstatus dual ethernet port link status 1...

  • Page 11

    Basic ied functions guid-c8f0e5d2-e305-4184-9627-f6b5864216ca v10 table 3. Basic ied functions iec 61850 or function name description interrsig self supervision with internal event list selfsupevlst self supervision with internal event list timesynchgen time synchronization module bininput, synchcan...

  • Page 12

    Table 4. Local hmi functions iec 61850 or function name ansi description lhmictrl local hmi signals language local human machine language screen local hmi local human machine screen behavior fnkeyty1–fnkeyty5 fnkeymd1– fnkeymd5 parameter setting function for hmi in pcm600 ledgen general led indicati...

  • Page 13

    Ef4ptoc can be set directional or non-directional independently for each of the steps. Idir, upol and ipol can be independently selected to be either zero sequence or negative sequence. Second harmonic blocking can be set individually for each step. Ef4ptoc can be used as main protection for phase-t...

  • Page 14

    Two step overvoltage protection ov2ptov m13798-3 v14 overvoltages may occur in the power system during abnormal conditions such as sudden power loss, tap changer regulating failures, and open line ends on long lines. Two step overvoltage protection (ov2ptov) function can be used to detect open line ...

  • Page 15

    Generic communication function for double point indication dpgapc semod55850-5 v6 generic communication function for double point indication dpgapc function block is used to send double indications to other systems, equipment or functions in the substation through iec 61850-8-1 or other communicatio...

  • Page 16

    • timerset function has pick-up and drop-out delayed outputs related to the input signal. The timer has a settable time delay. • xor function block. Each block has two outputs where one is inverted. Fixed signal function block m15322-3 v11 the fixed signals function fxdsign generates nine pre-set (f...

  • Page 17

    • event list • indications • event recorder • trip value recorder • disturbance recorder the disturbance report function is characterized by great flexibility regarding configuration, starting conditions, recording times, and large storage capacity. A disturbance is defined as an activation of an in...

  • Page 18

    Analog and double indication values are also transferred through the event function. Generic communication function for single point indication spgapc semod55713-5 v7 generic communication function for single point indication spgapc is used to send one single logical signal to other systems or equip...

  • Page 19

    Values will happen in both forward and reverse directions. These energy values are available as output signals and also as pulse outputs. Integration of energy values can be controlled by inputs (startacc and stopacc) and enaacc setting and it can be reset to initial values with rstacc input. The ma...

  • Page 20

    Iec 60870-5-103 communication protocol semod120137-5 v3 a single glass or plastic port is provided for the iec 60870-5-103 standard. This allows design of simple substation automation systems including equipment from different vendors. Disturbance files uploading is provided. Dnp3.0 communication pr...

  • Page 21

    Layout and dimensions ip14539-1 v1 dimensions ip14826-1 v1 m2152-3 v5 iec04000448 v2 en-us figure 3. Case without rear cover iec04000464 v2 en-us figure 4. Case without rear cover with 19” rack mounting kit m15243-12 v8 case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8....

  • Page 22

    15. Connection diagrams connection diagrams guid-cf4effa5-3081-4fc7-9a14-ed127c3c0fde v4 the connection diagrams are delivered on the ied connectivity package dvd as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/substationautom...

  • Page 23

    16. Technical data general ip11376-1 v2 m10993-1 v3 definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the ...

  • Page 24

    Auxiliary dc voltage ip15843-1 v3 m12286-1 v5 table 7. Psm - power supply module quantity rated value nominal range auxiliary dc voltage, el (input) el = (24-60) v el = (90-250) v el ± 20% el ± 20% power consumption 32 w typically - auxiliary dc power in-rush - binary inputs and outputs ip15844-1 v1...

  • Page 25

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M50609-2 v6 table 9. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220...

  • Page 26

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M12318-1 v7 table 11. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) ...

  • Page 27

    Bom/iom should be activated continuously due to power dissipation. M12584-1 v6 table 12. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max syste...

  • Page 28

    Bom/iom should be activated continuously due to power dissipation. M12441-1 v8 table 13. Bom - binary output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays binary outputs 24 max system voltage 250 v ac, dc test voltage across open contact, 1 min 100...

  • Page 29

    Table 16. Frequency influence (reference standard: iec 60255–1) dependence on within nominal range influence frequency dependence, operate value f r ±2.5 hz for 50 hz f r ±3.0 hz for 60 hz ±1.0%/hz harmonic frequency dependence (20% content) 2 nd , 3 rd and 5 th harmonic of f r ±1.0% harmonic freque...

  • Page 30

    Table 18. Insulation test type test values reference standard dielectric test 2.0 kv ac, 1 min. Iec 60255-27 ansi c37.90 impulse voltage test 5 kv, 1.2/50 m s, 0.5 j insulation resistance > 100 m w at 500 vdc table 19. Environmental tests test type test value reference standard cold operation test t...

  • Page 31

    Differential protection m13081-1 v11 table 22. 1ph high impedance differential protection hzpdif function range or value accuracy operate voltage (10-900) v i=u/r ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio >95% at (30-900) v - maximum continuous power u>trip 2 /seriesresistor ≤200 w -...

  • Page 32

    Current protection m12342-1 v18 table 23. Four-step phase overcurrent protection oc4ptoc function setting range accuracy operate current, step 1-4 (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - minimum operate current, step 1-4 (1-10000)...

  • Page 33

    M15223-1 v16 table 24. Four step residual overcurrent protection ef4ptoc technical data function range or value accuracy operate current, step 1-4 (1-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - relay characteristic angle (rca) (-180 to 180...

  • Page 34

    Guid-e83ad807-8fe0-4244-a50e-86b9af92469e v5 table 25. Four step negative sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - independent time ...

  • Page 35

    M13266-2 v8 table 26. Thermal overload protection, two time constants trpttr function range or value accuracy base current 1 and 2 (30–250)% of ibase ±1.0% of i r operate time: 2 2 2 2 p ref i i t ln i i t æ ö - ç ÷ = × ç ÷ - è ø equation1356 v2 en-us (equation 1) i = actual measured current ip = lo...

  • Page 36

    M13279-1 v9 table 28. Pole discordance protection ccpdsc function range or value accuracy operate current (0–100)% of ibase ±1.0% of i r independent time delay between trip condition and trip signal (0.000-60.000) s ±0.2% or ± 25 ms whichever is greater 1mrk 505 362-ben b busbar protection reb650 2....

  • Page 37

    Voltage protection m13290-1 v14 table 29. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ...

  • Page 38

    M13304-1 v13 table 30. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time charac...

  • Page 39

    Secondary system supervision m16069-1 v11 table 32. Fuse failure supervision fufspvc function range or value accuracy operate voltage, zero sequence (1-100)% of ubase ±0.5% of u r operate current, zero sequence (1–100)% of ibase ±0.5% of i r operate voltage, negative sequence (1-100)% of ubase ±0.5%...

  • Page 40

    Logic m12380-1 v10 table 33. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolv...

  • Page 41

    Guid-45df373f-dc39-4e1b-b45b-6b454e8e0e50 v1 table 40. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 34 10 20 guid-0ec4192a-ef03-47c0-aec1-09b68b411a98 v1 table 41. Number of inv instances logic block quantity with cycle time 3 ms 8 ms 100 ms inv 114 114 240 gui...

  • Page 42

    Guid-0b07f78c-10bd-4070-aff0-6ee36454aa03 v1 table 48. Number of xor instances logic block quantity with cycle time 3 ms 8 ms 100 ms xor 10 10 20 guid-23d4121a-4c9a-4072-bbe3-6db076edab79 v1 guid-27df23c0-a0b2-4bb0-80b5-fc7b7f7fe448 v1 guid-c1e61ae5-22cf-4198-97cf-8c8043ee96d2 v1 guid-77febe9b-0882-...

  • Page 43

    Guid-f5e124e3-0b85-41ac-9830-a2362fd289f2 v1 table 55. Running hour-meter teilgapc function range or value accuracy time limit for alarm supervision, talarm (0 - 99999.9) hours ±0.1% of set value time limit for warning supervision, twarning (0 - 99999.9) hours ±0.1% of set value time limit for overf...

  • Page 44

    Monitoring m12386-1 v14 table 56. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i 0.2 x i r ± 0.5% of i at 0.2 x i r i 0.5 x i r ± 0.2% ...

  • Page 45

    Guid-ed634b6d-9918-464f-b6a4-51b78129b819 v5 table 59. Phase-neutral voltage measurement vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v guid-9b8a7fa5-9c98-4cbd-a162-...

  • Page 46

    M12760-1 v9.1.1 table 63. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 91 maximum number of analog in...

  • Page 47

    Guid-83b0f607-d898-403a-94fd-7fe8d45c73ff v6 table 65. Insulation liquid monitoring function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value temperature l...

  • Page 48

    M12702-1 v4 table 69. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing m13747-1 v5 table 70. Trip value recorder function value buffer capacity maximum n...

  • Page 49

    Metering m13404-2 v5 table 73. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - semod153707-2 v4 table 74. Energy metering etpmmtr function range or value accuracy energy metering kwh export...

  • Page 50

    Station communication m15031-1 v7 table 75. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp/...

  • Page 51

    Semod117441-2 v5 table 80. Slm – spa/iec 60870-5-103/dnp3 port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000ft m typically *) plastic fiber: 7 db (25m/80ft m typically *) fiber diameter glass fiber...

  • Page 52

    Hardware ied semod53385-1 v1 m11778-1 v4 table 83. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) m12327-1 v3 table 84. Water and dust protection level according to iec 60529 front ip40 (ip54 with ...

  • Page 53

    Basic ied functions m11963-1 v5 table 90. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out m12331-1 v7 table 91. Time synchronization, time tagging function value time tagging resolution, events and sampled mea...

  • Page 54

    Inverse characteristic m12388-1 v19 table 93. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en-us i = i m...

  • Page 55

    Table 94. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 3.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal in...

  • Page 56

    Semod116978-2 v9 table 96. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2....

  • Page 57

    Table 97. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en-us u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + × ...

  • Page 58

    Table 98. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 32...

  • Page 59

    17. Ordering for pre-configured ied guid-7d93fa75-e25c-4dff-a1a4-5bac831b61db v2.1.1 guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and...

  • Page 60

    Connection type #7 notes and rules connection type for power supply module compression terminals m ringlug terminals n connection type for input/output modules compression terminals p selection for position #7. P auxiliary power supply #8 notes and rules 24-60 vdc a 90-250 vdc b selection for positi...

  • Page 61

    Remote end communication, dnp serial comm. And time synchronization modules #12 notes and rules slot position (rear view) x312 x313 x302 x303 available slots █ █ █ █ no remote communication board included x x x x irig-b time synchronization module f f f f galvanic rs485 communication module g g g g ...

  • Page 62

    18. Ordering for accessories accessories ip15151-1 v1 test switch semod111888-5 v11 the test system combitest intended for use with the ieds is described in 1mrk 512 001-ben and 1mrk 001024-ca. Please refer to the website: www.Abb.Com/substationautomation for detailed information. Due to the high fl...

  • Page 63

    Rule: specify additional quantity of ied connect cd requested . Quantity: 1mrk 002 290-ad user documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 505 359-uen technical manual iec quantity: 1mrk 505 360-uen commissioning manual iec quantity: 1mrk...

  • Page 64

    Reference information m2175-3 v4 for our reference and statistics we would be pleased to be provided with the following application data: country: end user: station name: voltage level: kv related documents guid-94e8a5ca-be1b-45af-81e7-5a41d34ee112 v3 documents related to reb650 document numbers app...

  • Page 65

    65.

  • Page 66

    Contact us for more information please contact: abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 www.Abb.Com/protection-control note: we reserve the right to make technical changes or modify the contents of this document without prior notice. Abb ab does not...