ABB REC670 2.1 IEC Product Manual

Manual is about: Relion 670 series Bay control

Summary of REC670 2.1 IEC

  • Page 1

    Relion ® 670 series bay control rec670 2.1 iec product guide.

  • Page 2

    Contents 1. Application..................................................................... 3 2. Available functions..........................................................8 3. Control......................................................................... 18 4. Differential protection.............

  • Page 3

    1. Application m13637-3 v12 the ied is used for the control, protection and monitoring of different types of bays in power networks. The ied is especially suitable for applications in control systems where the iec 61850–8–1 ed 1 or ed 2 station bus features of the ied can be fully utilized. It is us...

  • Page 4

    Description of configuration a30 m15200-3 v7 rec670 a30 – double busbar in single breaker arrangement 12ai (6i + 6u) qb1 qa1 qb2 qb9 s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 contr...

  • Page 5

    Description of configuration a31 guid-3e17dbd1-28eb-43df-b6f3-bafecb338a10 v2 rec670 a31 – bus coupler bay arrangement 12ai (6i + 6u) qb1 qa1 qb20 s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control drp rdre dfr/ser dr q crsv 3 control brc ptoc 46 iu...

  • Page 6

    Description of configuration b30 m15200-12 v5 rec670 b30 - double breaker arrangement 12ai (6i + 6u) qb1 qa1 qb61 qb2 qa2 qb62 qb9 s cilo 3 control s cswi 3 control s xcbr 3 control etp mmtr met w/varh brc ptoc 46 iub> cc psdc 52pd pd other functions available from the function library tcm yltc 84 l...

  • Page 7

    Description of configuration c30 m15200-24 v5 s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control s cilo 3 control s cswi 3 control s xswi 3 control...

  • Page 8

    2. Available functions main protection functions guid-66baad98-851d-4aac-b386-b38b57718bd2 v12 table 1. Example of quantities 2 = number of basic instances 0-3 = option quantities 3-a03 = optional function included in packages a03 (refer to ordering details) iec 61850 ansi function description bay c...

  • Page 9

    Back-up protection functions guid-a8d0852f-807f-4442-8730-e44808e194f0 v10 iec 61850 ansi function description bay control rec670 (customized) rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) current protection phpioc 50 instantaneous phase overcurrent protection 0-6 1-c51 1-c51 2-c52 2-c53 oc4pt...

  • Page 10

    Iec 61850 ansi function description bay control rec670 (customized) rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) sapfrc 81 rate-of-change frequency protection 0-6 6-e01 6-e01 6-e01 6-e01 ftaqfvr 81a frequency time accumulation protection 0-12 multipurpose protection cvgapc general current and...

  • Page 11

    Control and monitoring functions guid-e3777f16-0b76-4157-a3bf-0b6b978863de v12.1.1 iec 61850 ansi function description bay control rec670 rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) control sesrsyn 25 synchrocheck, energizing check and synchronizing 0-6, 0-2 1 1 2 3 smbrrec 79 autorecloser 0...

  • Page 12

    Iec 61850 ansi function description bay control rec670 rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) fufspvc fuse failure supervision 0-4 3 3 3 3 vdspvc 60 fuse failure supervision based on voltage difference 0-2 1-g03 1-g03 1-g03 1-g03 logic smpptrc 94 tripping logic 6 6 6 6 6 tmagapc trip ma...

  • Page 13

    Iec 61850 ansi function description bay control rec670 rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) cvmmxn, vmmxu, cmsqi, vmsqi, vnmmxu measurements 6 6 6 6 6 cmmxu measurements 10 10 10 10 10 aisvbas function block for service value presentation of secondary analog inputs 1 1 1 1 1 event eve...

  • Page 14

    Table 2. Total number of instances for basic configurable logic blocks basic configurable logic block total number of instances and 280 gate 40 inv 420 lld 40 or 280 pulsetimer 40 rsmemory 40 srmemory 40 timerset 60 xor 40 table 3. Total number of instances for configurable logic blocks q/t configur...

  • Page 15

    Communication guid-5f144b53-b9a7-4173-80cf-cd4c84579cb5 v12 iec 61850 ansi function description bay control rec670 (customized) rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) station communication lonspa, spa spa communication protocol 1 1 1 1 1 ade lon communication protocol 1 1 1 1 1 horzcomm...

  • Page 16

    Iec 61850 ansi function description bay control rec670 (customized) rec670 (a30) rec670 (a31) rec670 (b30) rec670 (c30) front, lanabi, lanab, lancdi, lancd ethernet configuration of links 1 1 1 1 1 gateway ethernet configuration of link one 1 1 1 1 1 optical103 iec 60870-5-103 optical serial communi...

  • Page 17

    Basic ied functions guid-c8f0e5d2-e305-4184-9627-f6b5864216ca v9 table 5. Basic ied functions iec 61850 or function name description interrsig selfsupevlst self supervision with internal event list timesynchgen time synchronization module bininput, synchcan, synchgps, synchcmpps, synchlon, synchpph,...

  • Page 18

    Table 5. Basic ied functions, continued iec 61850 or function name description runtime ied runtime comp camconfig central account management configuration camstatus central account management status toolinf tools information component safefilecopy safe file copy function table 6. Local hmi functions...

  • Page 19

    Each autoreclosing function is configured to co-operate with the synchrocheck function. The autoreclosing function provides high-speed and/or delayed three pole autoreclosing. Apparatus control apc m13444-3 v13 the apparatus control functions are used for control and supervision of circuit breakers,...

  • Page 20

    Circuit breaker sxcbr m13489-3 v6 the purpose of circuit breaker (sxcbr) is to provide the actual status of positions and to perform the control operations, that is, pass all the commands to primary apparatuses in the form of circuit breakers via binary output boards and to supervise the switching o...

  • Page 21

    Automationbits, command function for dnp3.0 autobits semod158591-5 v7 automationbits function for dnp3 (autobits) is used within pcm600 to get into the configuration of the commands coming through the dnp3 protocol. The autobits function plays the same role as functions goosebinrcv (for iec 61850) a...

  • Page 22

    Ns4ptoc can be used as main protection for unsymmetrical fault; phase-phase short circuits, phase-phase-earth short circuits and single phase earth faults. Ns4ptoc can also be used to provide a system backup for example, in the case of the primary protection being out of service due to communication...

  • Page 23

    Normally the own breaker is tripped to correct such a situation. If the situation persists the surrounding breakers should be tripped to clear the unsymmetrical load situation. The pole discordance protection function ccpdsc operates based on information from auxiliary contacts of the circuit breake...

  • Page 24

    7. Frequency protection underfrequency protection saptuf m13349-3 v12 underfrequency occurs as a result of a lack of generation in the network. Underfrequency protection saptuf measures frequency with high accuracy, and is used for load shedding systems, remedial action schemes, gas turbine startup ...

  • Page 25

    9. Secondary system supervision current circuit supervision ccsspvc m12444-3 v10 open or short circuited current transformer cores can cause unwanted operation of many protection functions such as differential, earth-fault current and negative-sequence current functions. Current circuit supervision ...

  • Page 26

    And re-closing during certain conditions, but naturally, it can not fully replace a communication channel. The logic can be controlled either by the autorecloser (zone extension) or by the loss-of-load current (loss-of-load acceleration). Scheme communication logic for residual overcurrent protectio...

  • Page 27

    • inverter function block that inverts one input signal to the output. • lld function block. Loop delay used to delay the output signal one execution cycle. • or function block. Each block has up to six inputs and two outputs where one is inverted. • pulsetimer function block can be used, for exampl...

  • Page 28

    Output at the last received value and blocks new integer values to be received and converted to binary coded outputs. Comparator for integer inputs intcomp guid-a93564fa-0017-4939-a9c1-095da0fd9832 v1 the function gives the possibility to monitor the level of integer values in the system relative to...

  • Page 29

    Term (for example corrective actions) and in the long term (for example functional analysis). The event recorder logs all selected binary input signals connected to the disturbance recorder function. Each recording can contain up to 150 time-tagged events. The event recorder information is available...

  • Page 30

    Time, number of operation cycles and estimate the accumulated energy during arcing periods. Fault locator lmbrflo m13970-3 v12 the accurate fault locator is an essential component to minimize the outages after a persistent fault and/or to pin- point a weak spot on the line. The fault locator is an i...

  • Page 31

    14. Human machine interface local hmi amu0600442 v14 iec13000239-2-en.Vsd iec13000239 v2 en-us figure 5. Local human-machine interface the lhmi of the ied contains the following elements: • graphical display capable of showing a user defined single line diagram and provide an interface for controlli...

  • Page 32

    Communication with unsolicited events, time synchronizing and disturbance reporting is provided for communication to rtus, gateways or hmi systems. Multiple command and transmit m14791-3 v3 when ieds are used in substation automation systems with lon, spa or iec 60870-5-103 communication protocols, ...

  • Page 33

    Communication (spa, iec 60870-5-103 and dnp3 port) and one port is dedicated for lon communication. Line data communication module ldcm m16075-3 v4 each module has one optical port, one for each remote end to which the ied communicates. Alternative cards for long range (1550 nm single mode), medium ...

  • Page 34

    Xx08000165.Vsd j g f k h iec08000165 v1 en-us figure 7. Case with rear cover and 19” rack mounting kit iec06000182-2-en.Vsd iec06000182 v2 en-us figure 8. A 1/2 x 19” size ied side-by-side with rhgs6. M15243-12 v7 case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242...

  • Page 35

    19. Connection diagrams connection diagrams guid-cf4effa5-3081-4fc7-9a14-ed127c3c0fde v3 the connection diagrams are delivered on the ied connectivity package dvd as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/substationautom...

  • Page 36

    20. Technical data general ip11376-1 v2 m10993-1 v3 definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the ...

  • Page 37

    Table 8. Trm - energizing quantities, rated values and limits for measuring transformer modules quantity rated value nominal range current i r = 1 or 5 a (0-1.8) × i r at i r = 1 a (0-1.6) × i r at i r = 5 a permissive overload 1.1 × i r cont. 1.8 × i r for 30 min at i r = 1 a 1.6 × i r for 30 min a...

  • Page 38

    Binary inputs and outputs ip15844-1 v1 m12576-1 v7 table 12. Bim - binary input module quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ±20% rl ±20% rl ±20% rl ±20% power consumption 24/30 v, 50ma 48/60 v, 50ma 110/125 v, 50ma 220/250 v, 50m...

  • Page 39

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M12573-1 v8 table 14. Iom - binary input/output module quantity rated value nominal range binary inputs 8 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ±20% rl ±20% rl ±20% rl ±...

  • Page 40

    Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. M12318-1 v6 table 15. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) ...

  • Page 41

    Table 15. Iom - binary input/output module contact data (reference standard: iec 61810-2), continued function or quantity trip and signal relays fast signal relays (parallel reed relay) breaking capacity for ac, cos φ > 0.4 250 v/8.0 a 250 v/8.0 a breaking capacity for dc with l/r 48 v/1 a 110 v/0.4...

  • Page 42

    Semod175395-2 v6 table 17. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48 - 60 vdc 110 - 250 vdc number of outputs 6 6 impedance open state ~300 kΩ ~810 kΩ test voltage across open contact, 1 min no ...

  • Page 43

    M12441-1 v7 table 19. Bom - binary output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays binary outputs 24 max system voltage 250 v ac, dc test voltage across open contact, 1 min 1000 v rms current carrying capacity per relay, continuous per relay, ...

  • Page 44

    Table 22. Frequency influence (reference standard: iec 60255–1) dependence on within nominal range influence frequency dependence, operate value f r ±2.5 hz for 50 hz f r ±3.0 hz for 60 hz ±1.0% / hz harmonic frequency dependence (20% content) 2 nd , 3 rd and 5 th harmonic of f r ±2.0% harmonic freq...

  • Page 45

    Table 24. Insulation test type test values reference standard dielectric test 2.0 kv ac, 1 min. Iec 60255-27 ansi c37.90 impulse voltage test 5 kv, 1.2/50 ms, 0.5 j insulation resistance >100 mw at 500 vdc table 25. Environmental tests test type test value reference standard cold operation test test...

  • Page 46

    Differential protection m13081-1 v11 table 28. 1ph high impedance differential protection hzpdif function range or value accuracy operate voltage (10-900) v i=u/r ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio >95% at (30-900) v - maximum continuous power u>trip 2 /seriesresistor ≤200 w -...

  • Page 47

    Current protection m12336-1 v11 table 29. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of ibase - operate time at 0 to 2 x i set min. = 15 ms max. ...

  • Page 48

    M12342-1 v16 table 30. Four-step phase overcurrent protection oc4ptoc function setting range accuracy operate current, step 1 - 4 (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - minimum operate current, step 1 - 4 (1-10000)% of lbase ± 1....

  • Page 49

    M15223-1 v14 table 32. Four step residual overcurrent protection ef4ptoc technical data function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of lbase - relay characteristic angle (rca) (-180 to 1...

  • Page 50

    Guid-e83ad807-8fe0-4244-a50e-86b9af92469e v5 table 33. Four step negative sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - independent time ...

  • Page 51

    Semod173350-2 v13 table 34. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cosj directional residual overcurrent (0.25-200.00)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cosj ...

  • Page 52

    M12352-1 v13 table 35. Thermal overload protection, one time constant lcpttr/lfpttr function range or value accuracy reference current (2-400)% of ibase ±1.0% of i r reference temperature (0-300)°c, (0 - 600)°f ± 1.0°c, ±2.0°f operate time: 2 2 2 2 2 ln p trip amb p ref ref i i t t t i i i t t - = -...

  • Page 53

    M12353-1 v11 table 37. Breaker failure protection ccrbrf function range or value accuracy operate phase current (5-200)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r ...

  • Page 54

    Semod175152-2 v10 table 40. Directional underpower protection guppdup function range or value accuracy power level for step 1 and step 2 (0.0–500.0)% of sbase ±1.0% of s r at s ≤ s r ±1.0% of s at s > s r where 1.732 r r r s u i = × × characteristic angle for step 1 and step 2 (-180.0–180.0) degrees...

  • Page 55

    Guid-6a7da510-e145-4c5b-a7dc-97bc4258e621 v8 table 43. Capacitor bank protection cbpgapc function range or value accuracy operate value, overcurrent (10-900)% of lbase ±2.0% of i r at i ≤ i r ±2.0% of i at i > i r reset ratio, overcurrent >95% at (100-900)% of ibase - start time, overcurrent, at 0.5...

  • Page 56

    Voltage protection m13290-1 v14 table 44. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ...

  • Page 57

    M13304-1 v12 table 45. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time charac...

  • Page 58

    M13317-2 v12 table 46. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 and step 2 (1.0-200.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r ...

  • Page 59

    Semod175210-2 v6 table 48. Loss of voltage check lovptuv function range or value accuracy operate voltage (1–100)% of ubase ±0.5% of u r pulse timer when disconnecting all three phases (0.050–60.000) s ±0.2% or ±15 ms whichever is greater time delay for enabling the functions after restoration (0.00...

  • Page 60

    Frequency protection m13360-1 v13 table 49. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ±2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms f...

  • Page 61

    M14976-1 v8 table 51. Rate-of-change frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is...

  • Page 62

    Multipurpose protection m13095-2 v7 1mrk 511 361-ben b bay control rec670 2.1 iec product version: 2.1 62 abb.

  • Page 63

    Table 53. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, - negseq, -3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2- phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph-ph - measuring voltage input...

  • Page 64

    Table 53. General current and voltage protection cvgapc , continued function range or value accuracy independent time delay, undervoltage at 1.2 to 0.8 x u set , step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater overvoltage: start time at 0.8 to 1.2 x u set min. = 15 ms max. = 30 ms...

  • Page 65

    Semod175176-2 v5 table 54. Rotor earth fault protection based on general current and voltage protection (cvgapc) and rxtte4 function range or value for machines with: • rated field voltage up to 350 v dc • static exciter with rated supply voltage up to 700 v 50/60 hz supply voltage 120 or 230 v 50/6...

  • Page 66

    Guid-7ea9731a-8d56-4689-9072-d72d9cdfd795 v7 table 55. Voltage-restrained time overcurrent protection vrpvoc function range or value accuracy start overcurrent (2.0 - 5000.0)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent > 95% - operate time, start overcurrent at 0...

  • Page 67

    Secondary system supervision m12358-1 v8 table 56. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0% ...

  • Page 68

    Guid-e2ea8017-bb4b-48b0-beda-e71fee353774 v4 table 58. Fuse failure supervision vdspvc function range or value accuracy operate value, block of main fuse failure (10.0-80.0)% of ubase ±0.5% of ur reset ratio operate time, block of main fuse failure at 1 to 0 x u r min. = 5 ms – max. = 15 ms reset ti...

  • Page 69

    Control m12359-1 v12 table 59. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r rese...

  • Page 70

    M12379-1 v11 table 60. Autorecloser smbrrec function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 1ph shot 1 - t1 2ph shot 1 - t1 3phhs shot 1 - t1 3ph (0.000-120.000) s ±0.2% or ±35 ms whichever is greater shot 2 - t2 3ph shot 3 - t3 3ph shot 4 ...

  • Page 71

    Semod175215-2 v12 table 61. Voltage control tr1atcc and tr8atcc function range or value accuracy transformer reactance (0.1–200.0)Ω, primary - time delay for lower command when fast step down mode is activated (1.0–100.0) s - voltage control set voltage (85.0–120.0)% of ubase ±0.25 % of u r outer vo...

  • Page 72

    Table 61. Voltage control tr1atcc and tr8atcc, continued function range or value accuracy time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms whichever is greater tap changer constant time-out (1–120) s ±0.2% or ±200 ms whichever is greater raise/lower command output pu...

  • Page 73

    Scheme communication m16038-1 v11 table 62. Scheme communication logic for distance or overcurrent protection zcpsch function range or value accuracy scheme type off intertrip permissive ur permissive or blocking deltablocking - operate voltage, delta u (0–100)% of ubase ±5.0% of Δu operate current,...

  • Page 74

    Logic m12380-1 v9 table 65. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolvi...

  • Page 75

    Guid-45df373f-dc39-4e1b-b45b-6b454e8e0e50 v1 table 72. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 10 10 20 guid-0ec4192a-ef03-47c0-aec1-09b68b411a98 v1 table 73. Number of inv instances logic block quantity with cycle time 3 ms 8 ms 100 ms inv 90 90 240 guid-...

  • Page 76

    Guid-0b07f78c-10bd-4070-aff0-6ee36454aa03 v1 table 80. Number of xor instances logic block quantity with cycle time 3 ms 8 ms 100 ms xor 10 10 20 guid-23d4121a-4c9a-4072-bbe3-6db076edab79 v1 table 81. Number of andqt instances logic block quantity with cycle time 3 ms 8 ms 100 ms andqt - 20 100 guid...

  • Page 77

    Guid-94c803b4-6c5a-4072-ab5c-20dde98c9a70 v1 table 88. Number of rsmemoryqt instances logic block quantity with cycle time 3 ms 8 ms 100 ms rsmemoryqt - 10 30 guid-341562fb-6149-495b-8a63-200df16a5590 v1 table 89. Number of srmemoryqt instances logic block quantity with cycle time 3 ms 8 ms 100 ms s...

  • Page 78

    Guid-3820f464-d296-4cad-8491-f3f997359d79 v1 table 94. Number of btigapc instances function quantity with cycle time 3 ms 8 ms 100 ms btigapc 4 4 8 guid-b45901f4-b163-4696-8220-7f8cac84d793 v1 table 95. Number of ib16 instances function quantity with cycle time 3 ms 8 ms 100 ms ib16 6 4 8 guid-a339b...

  • Page 79

    Monitoring m12386-1 v13 table 100. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u≤ 50 v ± 0.2% of u at u> 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i r ± 0.5% of i at 0.2 x i r i r ± 0.2% of i at 0.5 x i r...

  • Page 80

    Guid-ed634b6d-9918-464f-b6a4-51b78129b819 v5 table 103. Phase-neutral voltage measurement vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v guid-9b8a7fa5-9c98-4cbd-a162...

  • Page 81

    Guid-c43b8654-60fe-4e20-8328-754c238f4ad0 v2 table 107. Limit counter l4ufcnt function range or value accuracy counter value 0-65535 - max. Count up speed 30 pulses/s (50% duty cycle) - m12760-1 v9.1.1 table 108. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) ...

  • Page 82

    Guid-83b0f607-d898-403a-94fd-7fe8d45c73ff v6 table 110. Insulation liquid monitoring function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value temperature ...

  • Page 83

    M13765-1 v4 table 114. Indications function value buffer capacity maximum number of indications presented for single disturbance 96 maximum number of recorded disturbances 100 m12702-1 v4 table 115. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maxi...

  • Page 84

    Metering m13404-2 v5 table 119. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - semod153707-2 v4 table 120. Energy metering etpmmtr function range or value accuracy energy metering kwh expo...

  • Page 85

    Station communication m15031-1 v7 table 121. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp...

  • Page 86

    M12589-1 v4 table 126. Slm – lon port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000 ft typically *) plastic fiber: 7 db (10m/35ft typically *) fiber diameter glass fiber: 62.5/125 mm plastic fiber:...

  • Page 87

    Remote communication m12756-1 v8 table 131. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm singlemode 9/125 µm singlemode 9/125 µm peak emission wave length nominal maximum ...

  • Page 88

    Hardware ied semod53385-1 v1 m11778-1 v4 table 132. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) m12327-1 v3 table 133. Water and dust protection level according to iec 60529 front ip40 (ip54 wit...

  • Page 89

    Basic ied functions m11963-1 v5 table 138. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out m12331-1 v7 table 139. Time synchronization, time tagging function value time tagging resolution, events and sampled m...

  • Page 90

    Semod141136-2 v8 table 142. Irig-b quantity rated value number of channels irig-b 1 number of optical channels 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00...

  • Page 91

    Inverse characteristic m12388-1 v17 table 143. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en-us i = i ...

  • Page 92

    Table 144. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 3.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal i...

  • Page 93

    Semod116978-2 v8 table 146. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2...

  • Page 94

    Table 147. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en-us u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + ×...

  • Page 95

    Table 148. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 3...

  • Page 96

    21. Ordering for customized ied guid-43bac6e7-5454-464e-a4b0-97d2a602785d v4.2.1 table 149. General guidelines guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can b...

  • Page 97

    Table 153. Differential protection position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 a 0 0 0 0 0 0 0 0 0 0 0 0 0 table 154. Differential functions function function identification ordering no positi on available qty selected qty notes and rules 1ph high impedance differential protection hzpdif 1mrk005904-ha...

  • Page 98

    Table 160. Frequency protection position 1 2 3 4 e table 161. Frequency functions function function identification ordering no positi on available qty selected qty notes and rules underfrequency protection saptuf 1mrk005914-aa 1 0-6 overfrequency protection saptof 1mrk005914-ba 2 0-6 rate-of-change ...

  • Page 99

    Table 169. Control functions function function identification ordering no positi on available qty selected qty notes and rules synchrocheck, energizing check and synchronizing sesrsyn 1mrk005917-aa 1 0-2 rule: can only be ordered with apparatus control apc10/ apc15 synchrocheck, energizing check and...

  • Page 100

    Table 171. Scheme communication functions function function identification ordering no positi on available qty selected qty notes and rules scheme communication logic for distance or overcurrent protection zcpsch 1mrk005920-aa 1 0-1 current reversal and weak-end infeed logic for distance protection ...

  • Page 101

    Table 179. Casing selection casing selection notes and rules 1/2 x 19" case a 3/4 x 19” case 1 trm slot b 3/4 x 19" case 2 trm slots c 1/1 x 19” case 1 trm slot d 1/1 x 19" case 2 trm slots e selected table 180. Mounting selection mounting details with ip40 of protection from the front selection not...

  • Page 102

    Table 184. Analog system selection analog system selection notes and rules no first trm included x 0 note: only the same type of trm (compression or ringlug) in the same terminal. Compression terminals a ringlug terminals b first trm 12i 1a, 50/60hz 1 first trm 12i 5a, 50/60hz 2 first trm 9i+3u 1a, ...

  • Page 103

    Table 185. Maximum quantity of i/o modules note: when ordering i/o modules, observe the maximum quantities according to the table below case sizes bim iom bom/ som mim maximum in case 1/1 x 19”, one (1) trm 14 6 4 4 14 cards, including a combination of four cards of type bom, som and mim 1/1 x 19”, ...

  • Page 104

    Table 186. Binary input/output module selection binary input/output modules selection notes and rules slot position (rear view) x31 x41 x51 x61 x71 x81 x91 x101 x111 x121 x131 x141 x151 x161 note! Max 3 positions in 1/2 rack, 8 in 3/4 rack with 1 trm, 5 in 3/4 rack with 2 trm ,11 in 1/1 rack with 2 ...

  • Page 105

    Som static output module, 12 outputs, 48-60 vdc t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 t1 note: som must not be placed in the following positions: 1/2 case slot x51, 3/4 case 1 trm slot x101, 3/4 case 2 trm slot x71, 1/1 case 1 trm slot x161, 1/1 case 2 trm slot x131 x51 not in b30/c30. Som static o...

  • Page 106

    22. Ordering for pre-configured ied guid-25af8847-411f-4f1d-91ed-0ed71c5aa8a1 v8.1.1 guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and...

  • Page 107

    Software options #3 notes and rules no option x 00 all fields in the ordering form do not need to be filled in high impedance differential protections - 3 blocks a 02 note: a02 only in a30/a31/b30, a07 only in c30 high impedance differential protections - 6 blocks a 07 sensitive directional residual...

  • Page 108

    Casing #5 notes and rules 1/2 x 19" case a 3/4 x 19" case 1 trm slot b 3/4 x 19" case 2 trm slots c 1/1 x 19" case 1trm slots d 1/1 x 19" case 2 trm slots e selection for position #5. Mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x 19" rack mount...

  • Page 109

    Binary input/output module, ma and time synchronizating boards. #11 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1bim and 1 bom included in a30 and a31. 2 bim and 1 bom included in b30 and c30. Slot position (rear...

  • Page 110

    Remote end communication, dnp serial comm. And time synchronization modules #12 notes and rules slot position (rear view) x312 x313 x302 x303 x322 x323 note: the maximum number and type of ldcm modules supported depend on the total amount of modules (bim, bom, ldcm, oem, gtm, slm, rs485, irig- b) in...

  • Page 111

    23. Ordering for accessories accessories ip15151-1 v1 gps antenna and mounting details m12374-3 v5 gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, 20 m (appx. 65 ft) quantity: 1mrk 001 665-aa cable for antenna, 40 m (appx. 131 ft) quantity: 1mrk 001 665-ba interface...

  • Page 112

    External resistor unit semod120228-4 v7 high impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100v operating voltage quantity: 1 2 3 rk 795 101-ma high impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100v operating voltage quantity: rk...

  • Page 113

    User documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 511 358-uen ansi quantity: 1mrk 511 310-uus technical manual iec quantity: 1mrk 511 359-uen ansi quantity: 1mrk 511 311-uus commissioning manual iec quantity: 1mrk 511 360-uen ansi quantity...

  • Page 114

    Engineering manual, 670 series iec quantity: 1mrk 511 355-uen ansi quantity: 1mrk 511 355-uus cyber security guideline iec quantity: 1mrk 511 356-uen reference information m2175-3 v4 for our reference and statistics we would be pleased to be provided with the following application data: country: end...

  • Page 115

    115.

  • Page 116

    Contact us for more information please contact: abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 www.Abb.Com/substationautomation note: we reserve the right to make technical changes or modify the contents of this document without prior notice. Abb ab does n...