ABB REL650 series Product Manual

Manual is about: Line distance protection

Summary of REL650 series

  • Page 1

    Relion® 650 series — line distance protection rel650 version 2.2 product guide.

  • Page 2

    Contents 1. Application..................................................................... 3 2. Available functions..........................................................7 3. Impedance protection...................................................15 4. Current protection............................

  • Page 3

    1. Application guid-6efe28bf-7974-4a94-a7c2-ab43d48e1151 v3 rel650 is used for the protection, control and monitoring of overhead lines and cables in solidly or impedance earthed networks. It is suitable for the protection of heavily loaded lines and multi-terminal lines where the requirement for fa...

  • Page 4

    Qb1 qb2 qa1 qb9 qc9 wa1 wa2 cc rbrf 50bf 3i>bf oc4 ptoc 51_67 4(3i>) ef4 ptoc 51n_67n 4(in>) ef pioc 50n in>> ph pioc 50 3i>> s cilo 3 control s cswi 3 control vn mmxu met un vn mmxu met un s simg 63 zclc psch s siml 71 q cbay 3 control s xcbr 3 control wa2_vt wa1_vt line_ct line_vt smp ptrc 94 1->0...

  • Page 5

    Description of a12 guid-fcf2c16d-d4cd-4812-b795-6052ae6c0c50 v1 qb1 qb2 qa1 qb9 qc9 wa1 wa2 rel650 a12 – single breaker with single phase tripping for high ohmic and resonance earthed systems 12ai (7i+5u) cc rbrf 50bf 3i>bf oc4 ptoc 51_67 4(3i>) ef4 ptoc 51n_67n 4(in>) ef pioc 50n in>> ph pioc 50 3i...

  • Page 6

    1mrk 506 384-ben a line distance protection rel650 2.2 product version: 2.2.1 6 abb.

  • Page 7

    2. Available functions guid-f5776dd1-bd04-4872-bb89-a0412b4b5cc3 v1 the following tables list all the functions available in the ied. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. Main protection functions guid-66baad98-851d-4aac-b...

  • Page 8

    Back-up protection functions guid-a8d0852f-807f-4442-8730-e44808e194f0 v13 iec 61850 or function name ansi function description line distance rel650 (a11) rel650 (a12) current protection phpioc 50 instantaneous phase overcurrent protection 1 1 oc4ptoc 51_67 1) directional phase overcurrent protectio...

  • Page 9

    Control and monitoring functions guid-e3777f16-0b76-4157-a3bf-0b6b978863de v15 iec 61850 or function name ansi function description line distance rel650 (a11) rel650 (a12) control sesrsyn 25 synchrocheck, energizing check and synchronizing 1 1 smbrrec 79 autorecloser 1 1 qcbay bay control 1 1 locrem...

  • Page 10

    Iec 61850 or function name ansi function description line distance rel650 (a11) rel650 (a12) and, gate, inv, lld, or, pulsetimer, rsmemory, srmemory, timerset, xor basic configurable logic blocks (see table 2 ) 40–420 40–420 fxdsign fixed signal function block 1 1 b16i boolean to integer conversion,...

  • Page 11

    Iec 61850 or function name ansi function description line distance rel650 (a11) rel650 (a12) monitoring cvmmxn power system measurement 6 6 cmmxu current measurement 10 10 vmmxu voltage measurement phase-phase 6 6 cmsqi current sequence measurement 6 6 vmsqi voltage sequence measurement 6 6 vnmmxu v...

  • Page 12

    Communication guid-5f144b53-b9a7-4173-80cf-cd4c84579cb5 v15 iec 61850 or function name ansi function description line distance rel650 (a11) rel650 (a12) station communication lonspa, spa spa communication protocol 1 1 ade lon communciation protocol 1 1 horzcomm network variables via lon 1 1 protocol...

  • Page 13

    Iec 61850 or function name ansi function description line distance rel650 (a11) rel650 (a12) pcmaccs ied configuration protocol 1 1 secalarm component for mapping security events on protocols such as dnp3 and iec103 1 1 fstaccs field service tool access 1 1 iec 61850-9-2 process bus communication, 4...

  • Page 14

    Basic ied functions guid-c8f0e5d2-e305-4184-9627-f6b5864216ca v12 table 3. Basic ied functions iec 61850 or function name description interrsig self supervision with internal event list timesynchgen time synchronization module bininput, synchcan, synchgps, synchcmpps, synchlon, synchpph, synchpps, s...

  • Page 15

    Table 4. Local hmi functions iec 61850 or function name ansi description lhmictrl local hmi signals language local human machine language screen local hmi local human machine screen behavior fnkeyty1–fnkeyty5 fnkeymd1– fnkeymd5 parameter setting function for hmi in pcm600 ledgen general led indicati...

  • Page 16

    The main purpose of the oosppam function is to detect, evaluate, and take the required action during pole slipping occurrences in the power system. The oosppam function detects pole slip conditions and trips the generator as fast as possible, after the first pole-slip if the center of oscillation is...

  • Page 17

    Ef4ptoc can be set to be directional or non-directional independently for each step. Idir, upol and ipol can be independently selected to be either zero sequence or negative sequence. A second harmonic blocking can be set individually for each step. Directional operation can be combined together wit...

  • Page 18

    Normally the own breaker is tripped to correct such a situation. If the situation persists the surrounding breakers should be tripped to clear the unsymmetrical load situation. The pole discordance protection function (ccpdsc) operates based on information from auxiliary contacts of the circuit brea...

  • Page 19

    Sapfrc is provided with an undervoltage blocking. The operation is based on positive sequence voltage measurement and requires two phase-phase or three phase- neutral voltages to be connected. 7. Secondary system supervision current circuit supervision ccsspvc m12444-3 v10 open or short circuited cu...

  • Page 20

    Bay control qcbay m13447-3 v8 the bay control (qcbay) function is used together with local remote and local remote control functions to handle the selection of the operator place per bay. Qcbay also provides blocking functions that can be distributed to different apparatuses within the bay. Proxy fo...

  • Page 21

    Signal to the remote end, and to block the permissive tripping at the local end. This blocking condition is maintained long enough to ensure that no unwanted operation will occur as a result of the current reversal. On verification of a weak end infeed condition, the weak end infeed logic provides a...

  • Page 22

    According to the specific application needs for settable pulse or steady output. Group alarm logic function almcalh guid-16e60e27-f7a8-416d-8648-8174aac49bb5 v4 the group alarm logic function (almcalh) is used to route several alarm signals to a common indication, led and/or contact, in the ied. Gro...

  • Page 23

    Integer to boolean 16 conversion with logic node representation itbgapc semod158421-5 v9 integer to boolean conversion with logic node representation function (itbgapc) is used to transform an integer which is transmitted over iec 61850 and received by the function to 16 boolean (logic) output signa...

  • Page 24

    The event recorder logs all selected binary input signals connected to the disturbance recorder function. Each recording can contain up to 150 time-tagged events. The event recorder information is available for the disturbances locally in the ied. The event recording information is an integrated par...

  • Page 25

    Fault locator lmbrflo m13970-3 v13 the accurate fault locator is an essential component to minimize the outages after a persistent fault and/or to pin- point a weak spot on the line. The fault locator is an impedance measuring function giving the distance to the fault in km, miles or % of line lengt...

  • Page 26

    13. Human machine interface local hmi amu0600442 v14 iec13000239-3-en.Vsd iec13000239 v3 en-us figure 3. Local human-machine interface the lhmi of the ied contains the following elements: • graphical display capable of showing a user defined single line diagram and provide an interface for controlli...

  • Page 27

    Redundant station bus communication according to iec 62439-3 uses two optical ethernet ports. The hsr ring supports the connection of up to 30 relays. If more than 30 relays are to be connected, it is recommended to split the network into several rings to guarantee the performance for real-time appl...

  • Page 28

    Function status earth-fault for iec 60870-5-103 i103ef i103ef is a function block with defined functions for earth fault indications in monitor direction. This block includes the functiontype parameter; the information number parameter is defined for each output signal. Function status fault protect...

  • Page 29

    Alternative connectors of ring lug or compression type can be ordered. Binary input module bim m1769-3 v4 the binary input module has 16 optically isolated inputs and is available in two versions, one standard and one with enhanced pulse counting capabilities on the inputs to be used with the pulse ...

  • Page 30

    G f k h j iec04000464-3-en.Vsdx iec04000464 v3 en-us figure 7. Case without rear cover with 19” rack mounting kit m15243-12 v9 case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242.1/ 9.53 255.8/ 10.07 205.7/ 8.10 190.5/ 7.50 203.7/ 8.02 - 228.6/ 9.00 - the h and k d...

  • Page 31

    18. Connection diagrams guid-cf4effa5-3081-4fc7-9a14-ed127c3c0fde v6 the connection diagrams are delivered in the ied connectivity package as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/protection-control . Connection diagram...

  • Page 32

    19. Technical data general ip11376-1 v2 m10993-1 v3 definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the ...

  • Page 33

    Energizing quantities, rated values and limits analog inputs ip15842-1 v1 m16988-1 v11 table 5. Trm - energizing quantities, rated values and limits for protection transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1 or 5 a...

  • Page 34

    Table 7. Bim - binary input module quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/250 v, 50 ma 220/250 v, 110 ma max. 0.05 w/input max. 0...

  • Page 35

    M12573-1 v9 table 9. Iom - binary input/output module quantity rated value nominal range binary inputs 8 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/250 v, 50 ma 220/250 v, 110 ma max. 0...

  • Page 36

    M12584-1 v7 table 11. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1...

  • Page 37

    Table 13. Temperature and humidity influence parameter reference value nominal range influence ambient temperature, operate value +20°c -20°c to +55°c 0.02%/°c relative humidity operative range 10-90% 0-95% 10-90% - storage temperature - -40°c to +70°c - table 14. Auxiliary dc supply voltage influen...

  • Page 38

    Table 16. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-26 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12, class iv surge withstand capabilit...

  • Page 39

    Table 18. Environmental tests test type test value reference standard cold operation test test ad for 16 h at -25°c iec 60068-2-1 cold storage test test ab for 16 h at -40°c iec 60068-2-1 dry heat operation test test bd for 16 h at +70°c iec 60068-2-2 dry heat storage test test bb for 16 h at +85°c ...

  • Page 40

    Impedance protection guid-6c2ef52a-8166-4a23-9861-38931682aa7d v7 table 21. Distance protection zmfpdis function range or value accuracy number of zones 3 selectable directions, 3 fixed directions - minimum operate current, ph-ph and ph-e (5-6000)% of ibase ±1.0% of i r positive sequence reactance r...

  • Page 41

    M16036-1 v10 table 22. Power swing detection zmrpsb function range or value accuracy reactive reach (0.10-3000.00) w /phase ±2.0% static accuracy conditions: voltage range: (0.1-1.1) x u r current range: (0.5-30) x i r angle: at 0 degrees and 85 degrees resistive reach (0.10–1000.00) w /loop power s...

  • Page 42

    Guid-42119bff-1756-431c-a5a1-0ab637213e96 v1 table 25. Phase preference logic ppl2phiz function range or value accuracy operate value, phase-to-phase and phase-to-neutral undervoltage (1 - 100)% of ubase ±0.5% of u r reset ratio, undervoltage - operate value, residual voltage (5 - 300)% of ubase ±0....

  • Page 43

    Current protection m12336-1 v13 table 27. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of ibase - operate time at 0 to 2 x i set min. = 15 ms max. ...

  • Page 44

    M12342-1 v20 table 28. Directional phase overcurrent protection, four steps oc4ptoc function setting range accuracy operate current, step 1-4 (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - minimum operate current, step 1-4 (1-10000)% of ...

  • Page 45

    M15223-1 v17 table 30. Directional residual overcurrent protection, four steps ef4ptoc function range or value accuracy operate current, step 1-4 (1-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - relay characteristic angle (rca) (-180 to 180)...

  • Page 46

    Guid-e83ad807-8fe0-4244-a50e-86b9af92469e v6 table 31. Four step directional negative phase sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase -...

  • Page 47

    Semod173350-2 v16 table 32. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of ibase ±1.0% of i r at i £ i r ±1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cos ...

  • Page 48

    M12352-1 v14 table 33. Thermal overload protection, one time constant lcpttr/lfpttr function range or value accuracy reference current (2-400)% of ibase ±1.0% of i r reference temperature (0-300)°c, (0 - 600)°f ± 1.0°c, ±2.0°f operate time: 2 2 2 2 2 ln p trip amb p ref ref i i t t t i i i t t - = -...

  • Page 49

    M13279-1 v10 table 35. Pole discordance protection ccpdsc function range or value accuracy operate current (0–100)% of ibase ±1.0% of i r independent time delay between trip condition and trip signal (0.000-60.000) s ±0.2% or ± 30 ms whichever is greater guid-7ea9731a-8d56-4689-9072-d72d9cdfd795 v8 ...

  • Page 50

    Voltage protection m13290-1 v15 table 37. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ...

  • Page 51

    M13304-1 v14 table 38. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time charac...

  • Page 52

    M13317-2 v14 table 39. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 - step 2 (1.0-200.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r in...

  • Page 53

    Frequency protection m13360-1 v15 table 40. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ±2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms f...

  • Page 54

    M14976-1 v9 table 42. Rate-of-change of frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever...

  • Page 55

    Secondary system supervision m12358-1 v10 table 43. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0%...

  • Page 56

    Control m12359-1 v15 table 45. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r rese...

  • Page 57

    M12379-1 v13 table 46. Autorecloser smbrrec function range or value accuracy dead time: shot 1 “t1 1ph” shot 1 “t1 2ph” shot 1 “t1 3ph “ shot 1 “t1 3phhs” (0.000-120.000) s ±0.2% or ±35 ms whichever is greater dead time: shot 2 “t2 3ph” shot 3 “t3 3ph” shot 4 “t4 3ph” shot 5 “t5 3ph” (0.00-6000.00) ...

  • Page 58

    Scheme communication m16038-1 v14 table 47. Scheme communication logic with delta based blocking scheme signal transmit zcpsch function range or value accuracy scheme type off intertrip permissive ur permissive or blocking deltablocking - operate voltage, delta u (0–100)% of ubase ±5.0% of Δu operat...

  • Page 59

    Guid-cc9a02c2-aae8-4b8c-a091-d4ed584a2ea7 v1 table 50. Local acceleration logic zclcpsch function range or value accuracy operate current, loadcurr (1–100)% of ibase ±1.0% of i r operate current, mincurr (1–100)% of ibase ±1.0% of i r delay time on pick-up for current release (0.000–60.000) s ±0.2% ...

  • Page 60

    Logic m12380-1 v12 table 52. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolv...

  • Page 61

    Guid-d1179280-1d99-4a66-91ac-b7343dba9f23 v2 table 59. Number of and instances logic block quantity with cycle time 3 ms 8 ms 100 ms and 60 60 160 guid-45df373f-dc39-4e1b-b45b-6b454e8e0e50 v2 table 60. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 10 10 20 guid-...

  • Page 62

    Guid-c6c98fe0-f559-45ee-b853-464516775417 v2 table 67. Number of timerset instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms timerset 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms guid-0b07f78c-10bd-4070-aff0-6ee36454aa03 v1 table 68. Number of xor instances logic bl...

  • Page 63

    Table 74. Number of teigapc instances function quantity with cycle time 3 ms 8 ms 100 ms teigapc 4 4 4 guid-cea332ff-838d-42b7-aefc-c1e87809825e v2 table 75. Number of intcomp instances function quantity with cycle time 3 ms 8 ms 100 ms intcomp 10 10 10 guid-3fdd7677-1d86-42ad-a545-b66081c49b47 v3 t...

  • Page 64

    Monitoring m12386-1 v15 table 77. Power system measurement cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i 0.2 x i r ± 0.5% of i at 0.2 x i r i 0.5 x...

  • Page 65

    Guid-ed634b6d-9918-464f-b6a4-51b78129b819 v6 table 80. Voltage measurement phase-earth vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v guid-9b8a7fa5-9c98-4cbd-a162-71...

  • Page 66

    M12760-1 v10 table 84. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 116 maximum number of analog inpu...

  • Page 67

    Guid-83b0f607-d898-403a-94fd-7fe8d45c73ff v7 table 86. Insulation supervision for liquid medium function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value t...

  • Page 68

    M13765-1 v5 table 90. Indications function value buffer capacity maximum number of indications presented for single disturbance 352 maximum number of recorded disturbances 100 m12702-1 v4 table 91. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maxim...

  • Page 69

    Metering m13404-2 v5 table 96. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - semod153707-2 v5 table 97. Function for energy calculation and demand handling etpmmtr function range or value...

  • Page 70

    Station communication m15031-1 v8 table 98. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–115200 bd protocol tcp...

  • Page 71

    M12589-1 v4 table 103. Slm – lon port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000 ft typically *) plastic fiber: 7 db (10m/35ft typically *) fiber diameter glass fiber: 62.5/125 m m plastic fiber...

  • Page 72

    Hardware ied semod53385-1 v1 m11778-1 v6 table 107. Case material steel sheet front plate stainless steel with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) m12327-1 v4 table 108. Water and dust protection level according to iec 60529 front ip40 (ip54 with se...

  • Page 73

    Guid-96676d5d-0835-44da-bc22-058fd18bdf34 v2 table 114. Num: communication ports num 4 ethernet ports 1 basic, 3 optional ethernet connection type sfp optical lc or galvanic rj45 1mrk 506 384-ben a line distance protection rel650 2.2 product version: 2.2.1 abb 73.

  • Page 74

    Basic ied functions m11963-1 v5 table 115. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out m12331-1 v8 table 116. Time synchronization, time tagging function value time tagging resolution, events and sampled m...

  • Page 75

    Inverse characteristic m12388-1 v21 table 119. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en-us i = i ...

  • Page 76

    Table 120. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 3.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal i...

  • Page 77

    Guid-19f8e187-4ed0-48c3-92f6-0d9eaa2b39bb v3 table 122. Ansi inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us re...

  • Page 78

    Table 123. Iec inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en-us i = i measured /i set 0.10 ≤ k ≤ 2.00 1.5 x i set ≤ i ≤ 20 x i ...

  • Page 79

    Guid-2ae8c92e-5da8-487f-927d-8e553ee29240 v1 table 125. Ansi inverse time characteristics for voltage restrained time overcurrent protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en-us reset characteristi...

  • Page 80

    Semod116978-2 v10 table 127. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: ...

  • Page 81

    Table 128. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en-us u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + ×...

  • Page 82

    Table 129. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en-us u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 3...

  • Page 83

    20. Ordering for pre-configured ied guid-970741c9-5c16-4350-8fd6-106ee3bcecc5 v3 guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or ...

  • Page 84

    Mounting details with ip40 of protection from the front ordering no #6 notes and rules no mounting kit included x 19" rack mounting kit for 1/2 x 19" case or 2xrhgs6 or rhgs12 1mrk002420-bb a 19" rack mounting kit for 3/4 x 19" case or 3xrhgs6 1mrk002420-ba b 19" rack mounting kit for 1/1 x 19" case...

  • Page 85

    Binary input/output modules ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1 bim required in position p3 and 1 bom always included in position p4. Slot position (front view/rear view) p3/x31 p4/x41 p...

  • Page 86

    21. Ordering for accessories accessories ip15151-1 v1 interface converter (for remote end data communication) m16668-3 v9 external interface converter from c37.94 to g703 quantity: 1mrk 002 245-aa external interface converter from c37.94 to g703.E1 quantity: 1mrk 002 245-ba test switch semod111888-5...

  • Page 87

    Rule: specify additional quantity of ied connect usb flash drive requested . Quantity: 1mrk 003 500-ab user documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 506 381-uen technical manual iec quantity: 1mrk 506 382-uen commissioning manual iec q...

  • Page 88

    Reference information m2175-3 v4 for our reference and statistics we would be pleased to be provided with the following application data: country: end user: station name: voltage level: kv related documents guid-94e8a5ca-be1b-45af-81e7-5a41d34ee112 v5 documents related to rel650 document numbers app...