ABB Relion 611 series REB611 Product Manual

Manual is about: Busbar and Multipurpose Differential Protection and Control

Summary of Relion 611 series REB611

  • Page 1

    Relion ® 611 series busbar and multipurpose differential protection and control reb611 product guide.

  • Page 2

    Contents 1. Description.....................................................................3 2. Standard configuration...................................................3 3. Protection functions........................................................5 4. Application....................................

  • Page 3

    1. Description reb611 is a dedicated busbar protection ied (intelligent electronic device) designed for phase- segregated short-circuit protection, control, and supervision of single busbars. Reb611 is intended for use in high-impedance-based applications within utility substations and industrial po...

  • Page 4

    Table 2. Supported functions functionality conf. A protection 1) high-impedance differential protection, instance 1 ● high-impedance differential protection, instance 2 ● high-impedance differential protection, instance 3 ● non-directional earth-fault protection, low stage, instance 1 ● 2) non-direc...

  • Page 5

    3. Protection functions the ied offers phase-segregated (three phases) high-impedance differential protection and non- directional earth-fault protection for busbars, motors and generators. Reb611 also offers high- impedance differential-based restricted earth-fault protection for motors, generators...

  • Page 6

    An additional stand-by (residual) earth-fault protection is provided by the two non-directional earth-fault stages. The stand-by earth-fault protection can be used together with the high- impedance protection functionality to protect motors, generators and transformers against residual earth-faults....

  • Page 7

    Hi> 87 3 3 io>bf lockout relay 86 reb611 (standard conf a) 1 1 mcs 1i mcs 1i 3i>bf 51bf hi> 87 hi> 87 mcs 1i mcs 1i mcs 1i mcs 1i io> 51n-1 io>>> 50n 51n bf guid-9f68c879-2144-468c-9441-0bd7cb201e98 v1 en figure 3. Restricted earth-fault protection of the high and low voltage side of a power transfo...

  • Page 8

    5. Supported abb solutions abb’s 611 series protection and control ieds together with the com600 station automation device constitute a genuine iec 61850 solution for reliable power distribution in utility and industrial power systems. To facilitate and streamline the system engineering, abb’s ieds ...

  • Page 9

    Binary horizontal goose communication iec 61850 ethernet switch rem611 reb611 ref611 ref611 ref611 overcurrent earth-fault phase unbalance thermal overload ar sequence in progress disturb.Rec.Trigged trip circuit failure breaker failure ref611 overcurrent earth-fault phase unbalance thermal overload...

  • Page 10

    8. Disturbance recorder the ied is provided with a disturbance recorder with preconfigured analog and binary channels. The analog channels can be set to record either the waveform or the trend of the currents and residual voltage measured. The analog channels can also be set to trigger the recording...

  • Page 11

    Levels. The access control applies both locally and remotely to the front panel user interface, the web browser-based user interface and pcm600. 14. Inputs and outputs the ied is equipped with three phase-segregated differential current inputs and one residual-current input. The differential current...

  • Page 12

    Optional communication modules. The ied can be connected to ethernet-based communication systems via the rj-45 connector (100base-tx) or the fibre-optic lc connector (100base-fx). If connection to a serial bus is required, the 10-pin rs-485 screw terminal can be used. Modbus implementation supports ...

  • Page 13

    16. Technical data table 6. Dimensions description value width frame 177 mm case 164 mm height frame 177 mm (4u) case 160 mm depth 201 mm (153 + 48 mm) weight complete ied 4.1 kg plug-in unit only 2.1 kg table 7. Power supply description type 1 type 2 u aux nominal 100, 110, 120, 220, 240 v ac 50 an...

  • Page 14

    Table 9. Binary inputs description value operating range ±20% of the rated voltage rated voltage 24...250 v dc current drain 1.6...1.9 ma power consumption 31.0...570.0 mw threshold voltage 18...176 v dc reaction time 3 ms table 10. Signal output x100: so1 description value rated voltage 250 v ac/dc...

  • Page 15

    Table 12. Double-pole power output relays with tcs function description value rated voltage 250 v ac/dc continuous contact carry 8 a make and carry for 3.0 s 15 a make and carry for 0.5 s 30 a breaking capacity when the control-circuit time constant l/r contacts connected in series) 5 a/3 a/1 a mini...

  • Page 16

    Table 16. Irig-b description value irig time code format b004, b005 1) isolation 500 v 1 min modulation unmodulated logic level ttl level current consumption 2...4 ma power consumption 10...20 mw 1) according to 200-04 irig -standard table 17. Degree of protection of flush-mounted ied description va...

  • Page 17

    Table 20. Electromagnetic compatibility tests description type test value reference 1 mhz/100 khz burst disturbance test: iec 61000-4-18 iec 60255-22-1, class iii ieee c37.90.1-2002 • common mode 2.5 kv • differential mode 2.5 kv 3/10/30 mhz burst disturbance test: iec 61000-4-18 • common mode 2 kv ...

  • Page 18

    Table 20. Electromagnetic compatibility tests, continued description type test value reference power frequency immunity test: • common mode • differential mode binary inputs only 300 v rms 150 v rms iec 61000-4-16 iec 60255-22-7, class a emission tests: en 55011, class a iec 60255-25 • conducted 0.1...

  • Page 19

    Table 22. Mechanical tests description reference requirement vibration tests (sinusoidal) iec 60068-2-6 (test fc) iec 60255-21-1 class 2 shock and bump test iec 60068-2-27 (test ea shock) iec 60068-2-29 (test eb bump) iec 60255-21-2 class 2 seismic test iec 60255-21-3 class 2 table 23. Product safet...

  • Page 20

    Protection functions table 26. High-impedance differential protection (hipdif) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz ±1.5% of the set value or ±0.002 x in start time 1)2) minimum typical maximum ifault = 2.0 x set start value 12 ms 16 m...

  • Page 21

    Table 28. Non-directional earth-fault protection (efxptoc) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz eflptoc ±1.5% of the set value or ±0.002 x i n efhptoc and efiptoc 1) ±1.5% of the set value or ±0.002 x i n (at currents in the range of 0...

  • Page 22

    Table 29. Non-directional earth-fault protection (efxptoc) main settings parameter function value (range) step start value eflptoc 0.010...5.000 x i n 0.005 efhptoc 0.10...40.00 x i n 0.01 efiptoc 1) 1.00...40.00 x i n 0.01 time multiplier eflptoc 0.05...15.00 0.05 efhptoc 0.05...15.00 0.05 operate ...

  • Page 23

    Table 32. Operation characteristics parameter values (range) operating curve type 1=ansi ext. Inv. 2=ansi very. Inv. 3=ansi norm. Inv. 4=ansi mod inv. 5=ansi def. Time 6=l.T.E. Inv. 7=l.T.V. Inv. 8=l.T. Inv. 9=iec norm. Inv. 10=iec very inv. 11=iec inv. 12=iec ext. Inv. 13=iec s.T. Inv. 14=iec l.T. ...

  • Page 24

    Measurement functions table 33. Three-phase current measurement (cmmxu) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz ±0.5% or ±0.002 x i n (at currents in the range of 0.01...4.00 x i n ) suppression of harmonics dft: -50 db at f = n x f n , w...

  • Page 25

    Supervision functions table 35. Ct supervision for high-impedance protection scheme (hzccrdif) characteristic value operation accuracy depending on the frequency of the current measured: fn ±2 hz ±1.5% of the set value or ±0.002 x in reset time reset ratio typical 0.96 retardation time operate time ...

  • Page 26

    17. Local hmi the ied is equipped with a four-line liquid crystal display (depending on the chosen font and language, more or fewer lines might be visible). The display is designed for entering parameter settings of the protection and control functions. It is also suited for remotely controlled subs...

  • Page 27

    48 153 16 0 17 7 177 164 guid-0ed32be0-c610-4171-81a9-321735932451 v1 en figure 8. Flush mounting 98 16 0 186 17 7 103 guid-2b67cc71-7a0e-4ec8-86aa-9e94ee3c0baf v1 en figure 9. Semi-flush mounting 23 0 133 107 25° 190 guid-78e3ecc3-f2c7-4efe-bc94-caf89b5ca6d0 v1 en figure 10. Semi-flush with a 25º t...

  • Page 28

    20. Selection and ordering data the ied type and serial number label identifies the protection ied. The label is placed above the lhmi on the upper part of the plug-in unit. An order number label is placed on the side of the plug-in unit as well as inside the case. The order number consists of a str...

  • Page 29

    R e b 6 1 1 h b a a a a 1 n n 1 x e # description 14 option 1 none n 15 option 2 none n 16 power supply 48-250vdc; 100-240vac 1 24-60vdc 2 17 for future use undefined x 18 version product version 1.0 e guid-295664ae-a576-42fc-b535-ccd4dbbc726f v2 en guid-2680dae0-3bf4-458d-97ef-9d141ceb7ec2 v2 en fi...

  • Page 30

    22. Tools the ied is delivered as a pre-configured unit. The default parameter setting values can be changed from the front-panel user interface, the web browser-based user interface (whmi) or pcm600 in combination with the ied-specific connectivity package. The protection and control ied manager pc...

  • Page 31

    Table 39. Supported functions function whmi pcm600 pcm600 engineering pcm600 engineering pro ied parameter setting ● ● ● ● saving of ied parameter settings in the ied ● ● ● ● signal monitoring ● ● ● ● disturbance recorder handling ● ● ● ● alarm led viewing ● ● ● ● access control management ● ● ● ● i...

  • Page 32

    23. Terminal diagram reb611 16 17 19 18 x100 6 7 8 9 10 11 12 13 15 14 2 1 3 4 5 22 21 23 24 so2 tcs2 po4 so1 tcs1 po3 po2 po1 irf + - u aux 20 1) the ied features an automatic short-circuit mechanism in the ct connector when plug-in unit is detached 1) x120 1 2 3 4 5 6 7 8 9 10 11 12 14 io il1 il2 ...

  • Page 33

    25. Functions, codes and symbols table 40. Reb611 functions, codes and symbols function iec 61850 iec 60617 iec-ansi protection high-impedance differential protection, instance 1 hipdif1 dhi>(1) 87(1) high-impedance differential protection, instance 2 hipdif2 dhi>(2) 87(2) high-impedance differentia...

  • Page 34

    26. Document revision history document revision/date product series version history a/2011-11-18 1.0 first release b/2012-05-04 1.0 content updated busbar and multipurpose differential protection and control 1mrs757467 b reb611 product version: 1.0 34 abb.

  • Page 35

    35.

  • Page 36