ABB Relion 650 series ANSI Manual

Other manuals for Relion 650 series ANSI: Engineering Manual
Manual is about: IEC 61850 Communication protocol

Summary of Relion 650 series ANSI

  • Page 1

    Relion ® protection and control 650 series ansi iec 61850 communication protocol manual.

  • Page 3

    Document id: 1mrk 511 281-uus issued: october 2016 revision: a product version: 1.3 © copyright 2013 abb. All rights reserved.

  • Page 4

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and...

  • Page 5

    Disclaimer the data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intende...

  • Page 6

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents section 1 introduction............................................................................9 this manual.............................................................................................. 9 intended audience............................................................

  • Page 8

    Tap changer control and supervision, 6 binary inputs tcmyltc (84)............................................................................. 59 logical nodes for control.........................................................................61 bay control cbay........................................

  • Page 9

    Instantaneous phase overcurrent protection 3-phase output phpioc (50)................................................................................ 94 instantaneous residual overcurrent protection efpioc (50n).....94 local acceleration logic plal.......................................................

  • Page 10

    Thermal overload protection, one time constant, celsius lcpttr(26)............................................................................... 129 thermal overload protection, one time constant, fahrenheit lfpttr(26)................................................................................1...

  • Page 11

    Pole discordance protection rpld .................................................155 pole discrepancy protection ccrpld (52pd)........................... 155 power swing detection rpsb..........................................................156 power swing detection zmrpsb (68).......................

  • Page 12

    Logical nodes for sensors and monitoring............................................203 circuit breaker monitoring scbr.................................................... 203 breaker close/trip circuit monitoring tcsscbr......................... 203 circuit breaker condition monitoring sscbr..........

  • Page 13

    Section 9 glossary............................................................................ 227 table of contents 650 series ansi 7 communication protocol manual.

  • Page 14

    8.

  • Page 15

    Section 1 introduction 1.1 this manual the communication protocol manual describes the communication protocols supported by the ied. The manual concentrates on the vendor-specific implementations. 1.2 intended audience this manual addresses the communication system engineer or system integrator resp...

  • Page 16

    1.3 product documentation 1.3.1 product documentation set iec07000220-3-en.Vsd p la nn in g & p u rc h a se e n g in e e ri ng in st al lin g c om m is si o n in g o p e ra tio n m a in te na n ce d ec om m is si o n in g d ei n st a lli n g & d is po sa l application manual operation manual install...

  • Page 17

    During the testing phase. The manual provides procedures for the checking of external circuitry and energizing the ied, parameter setting and configuration as well as verifying settings by secondary injection. The manual describes the process of testing an ied in a substation which is not in service...

  • Page 18

    Documents related to rel650 identity number application manual 1mrk 506 334-uus technical manual 1mrk 506 335-uus commissioning manual 1mrk 506 336-uus product guide 1mrk 506 337-bus type test certificate 1mrk 506 337-tus application notes for circuit breaker control 1mrg006806 documents related to ...

  • Page 19

    650 series manuals identity number communication protocol manual, dnp 3.0 1mrk 511 280-uus communication protocol manual, iec 61850–8–1 1mrk 511 281-uus communication protocol manual, iec 60870-5-103 1mrk 511 282-uus cyber security deployment guidelines 1mrk 511 285-uus point list manual, dnp 3.0 1m...

  • Page 20

    • abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. • push button navigation in the lhmi menu structure is presented by using the push button icons. For example, to navigate between the options, use and . • hmi menu ...

  • Page 21

    Iec 61850 or function name ansi function description zgcpdis 21g underimpedance protection for generators and transformers lexpdis 40 loss of excitation oosppam 78 out-of-step protection lepdis load enchroachment table 2: backup protection functions iec 61850 or function name ansi function descripti...

  • Page 22

    Iec 61850 or function name ansi function description oexpvph 24 overexcitation protection lovptuv 27 loss-of-voltage check stefphiz 59thd 100% stator ground fault protection, 3rd harmonic based frequency protection saptuf 81 underfrequency function saptof 81 overfrequency function sapfrc 81 rate-of-...

  • Page 23

    Iec 61850 or function name ansi function description ecrwpsch 85 current reversal and weak end infeed logic for residual overcurrent protection logic smpptrc 94 tripping logic, common 3-phase output sptptrc 94 tripping logic, phase segregated output tmaggio trip matrix logic or configurable logic bl...

  • Page 24

    Iec 61850 or function name ansi function description cmsqi current sequence component measurement vmsqi voltage sequence measurement vnmmxu phase-neutral voltage measurement cntggio event counter l4ufcnt event counter with limit supervision drprdre disturbance report axradr analog input signals bxrb...

  • Page 25

    Table 5: basic ied functions iec 61850 or function name function description basic functions included in all products interrsig self-supervision with internal event list actvgrp parameter setting groups testmode test mode functionality chnglck change lock function athstat authority status smai_20_1 ...

  • Page 26

    20

  • Page 27

    Section 2 introduction to iec 61850 the general scope of the iec 61850 protocol standard is designed to support the communication of all functions being performed in the substation. Its’ main goal is interoperability; this is the ability for ieds from one or different manufacturers to exchange infor...

  • Page 28

    Detailed information regarding the iec61850 implementation of the ied 650 is described inside the conformance documents. • mics, modeling information conformance statement, contains the declaration of the used logical node types. • pics, protocol information conformance statement, contains the detai...

  • Page 29

    Document id title iec 61850-5 first edition 2003-07 ref. Number: iec 61850-5:2003(e) communication networks and systems in substations - part 5: communication requirements for functions and devices models iec 61850-6 first edition 2004-03 ref. Number: iec 61850-6: 2004(e) communication networks and ...

  • Page 30

    Iec 61850 pics 1mrg006609 650 series 1.2 - iec 61850 pics: protocol implementation conformance statement iec 61850 pixit 1mrg006608 650 series 1.2 - iec 61850 pixit: protocol implementation extra information iec 61850 tics 1mrg006607 650 series 1.2 – iec 61850 tics: tissue implementation conformance...

  • Page 31

    Section 3 substation configuration description language (scl) three different types of scl files - scd, cid and icd, can be exported from pcm 600. The scl language is based on xml. However, detailed knowledge of the xml contents is not needed. The scl xml file (icd/scd/cid) contains five sections, w...

  • Page 32

    Iec08000178.Vsd ied name accesspoint address gse ied name accesspoint address gse services authentication ldevice dai dotype datype enumtype substation voltagelevel bay lnode ied ld ln ied ld ln communucation subnetwork connected ap ied accesspoint server goose control ln0 ln dataset doi datatypetem...

  • Page 33

    3.2 the communication section the organization of the physical ieds to the communication network is independent of the substation structure. The iec 61850 standard defines the communication network with no relation to an existing media or protocol. The mapping to an existing media and protocol is sp...

  • Page 34

    3.3 the ied section the ied section describes the complete ied as it is needed for iec 61850 communication and signal engineering. The data type template part of an ied may be seen as part of the ied, even when separated in its own section. The ied's icd files include the description of the logical ...

  • Page 35

    En06000104.Vsd ap subnetwork control ied cvmmxu1 sb1.Ld0 server lphd sxcbr1 scswi1 sxswi1 scswi2 sxswi2 scswi3 sxswi3 scswi4 sxswi4 scswi5 lln0 mod cbopcap origin data data attribute beh health nameplt ctlval pos loc opcnt blkopn blkcls stval q t logical node ctlmodel iec06000104 v2 en figure 4: org...

  • Page 36

    Select the requested signals (dos) and link them to the client ieds as receiver. When using a dataset for mms, the requested signals are dos but when creating a dataset for goose messaging, das are used. The control services are not directly engineered. They are included in the data objects, which h...

  • Page 37

    • included in pcm600 is the new iec61850 configuration tool which allows the user to define data sets and control blocks for both client server and goose communication. • the iec61850 configuration tool gives the user the possibility to make the iec61850 engineering without export / import step. It ...

  • Page 38

    3.5 engineering concept in iec 61850-6 • top-down approach means that the system engineering tool has icd files available for each ied to be included in the system configuration. The icd files may be of the template type and represent a pre-configured ied. • bottom-up approach means that the configu...

  • Page 39

    Section 4 communication profile the iec 61850 standard is conceptually written to be independent of an existing communication media and message transmission concept. Out of this, a specific communication profile is decided and has been commonly used. The profile contains: • ethernet as the media • t...

  • Page 40

    Sv goose timesync (sntp) mms protocol suite gsse tcp/ip t-profile iso co t-profile iso/iec 8802-2 llc gsse t-profile udp/ip iso/iec 8802-3 ethertype sampled values (multicast) generic object oriented substation event time sync core acsi services generic substation status event iso/iec 8802-3 iec0900...

  • Page 41

    Section 5 supported services iec 61850-7-2 describes the services in the standard. Iec 61850-8-1 describes how the services are applied in the communication. The conformance documents contain the description of the supported services in the ied. Services that are not mentioned in this chapter or in ...

  • Page 42

    Unbuffered reporting as well as buffered reporting is supported. Note that the parameters buftm and intprd shall have the relation buftm denominator, for example: n*buftm = intprd, n is an arbitrary number. Generic object oriented substation event (goose) the structured goose is supported. This mean...

  • Page 43

    • spggio - iec61850 generic communication i/ o functions • dpggio - iec61850 generic communication i/ o functions • mvggio - iec61850 generic communication i/ o functions control of the different control sequences, the ‘direct-with-normal-security’ and ‘sbo-with- enhanced’ security are supported (de...

  • Page 44

    38.

  • Page 45

    Section 6 data sets and control blocks 6.1 data sets iec 61850 has defined data sets and report control blocks to transmit signals for monitoring purposes. Data sets are also used for goose messages in horizontal communication among ieds. The project defines the data objects or single data attribute...

  • Page 46

    • all data objects or their data attributes can be selected for a data set. • only those data attributes of a data object can/will be selected which have the same function constraint (fc). • data objects with different fc can be selected for a data set. For example, dos with fc = st and dos with fc=...

  • Page 47

    • when integrity is selected in the trigger option attribute, it is needed to define an integrity period to force the transmission of all data listed in the dataset. This is done by the attribute integrity period. This feature can be used as a background cycle to ensure that the process image in all...

  • Page 48

    • this trigger forces the transmission of all process values defined in the data set when a timer value (the integrity period) expires. • general interrogation • this trigger is forced by the clients (= station level ied; ncc gateway, station hmi, ...). Normally a gi is asked for, when the client an...

  • Page 49

    En06000107.Vsd ld0/sxcbr1.Pos fc=st ld0/sxswi1.Pos fc=st ld0/sxswi2.Pos fc=st ld0/sxswi3.Pos fc=st ld0/sxswi4.Pos fc=st ld0/lln0.Apppos data-set ied hsi client 1 ied ncc gw 1 client 2 ied ncc gw m client m ied 1 server 1 subnetwork itci2 itci1 ihsi1 lln0 iec06000107 v2 en figure 9: link brcb to a cl...

  • Page 50

    6.3 goose control blocks (gocb) en06000109.Vsd s e nd data-set r e ce iv e r e ce iv e ln ln ln ln ln s e nd data-set r e ce iv e r e ce iv e ln ln ln ln s e nd data-set r e ce iv e r e ce iv e ln ln ln ln ln ln subnetwork ln0 gocb dataset input gocb gocb dataset dataset input input comm. Gse ld0 se...

  • Page 51

    The goose service model of iec 61850-7-2 provides the possibility for fast and reliable system-wide distribution of input and output data values. This implementation uses a specific scheme of re-transmission to achieve the appropriate level of reliability. When a goose server generates a sendgooseme...

  • Page 52

    Figure 10 shows the goose concept for three ieds which interchange goose messages between each other. To send goose messages a gocb must be defined and a data set is needed that contains the data objects of single data attributes to be sent. A goose message is forced to be transmitted when a trigger...

  • Page 53

    Section 7 logical node data model the data model used by iec 61850 is based on logical nodes containing a set of data objects. The data model is defined in the standards. • iec 61850-7-4 compatible logical node classes and data classes • iec 61850-7-3 common data classes the standard describes only ...

  • Page 54

    To be included in each ln. This clause describes the general handling of the data objects within the 650 series products. The mandatory data objects as defined in iec 61850-7-4 as part of the common logical node are mode, behavior, health and nameplate. Mode the operation modes on (enabled) and bloc...

  • Page 55

    Table 6: tr8atcc (90) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - - cmd mode parame...

  • Page 56

    Do name do type da name fc t signal mon/c md description lotappos b_dins q st - - mon tap position for minimum voltage t st - - mon tap position for minimum voltage circa b_dmv mag.F mx - icircul mon circulating current q mx - icircul mon circulating current t mx - icircul mon circulating current lo...

  • Page 57

    Do name do type da name fc t signal mon/c md description parop c_dspc t st - parallel mon transformer operates in parallel mode ltcid v1_dins stval st - - mon identity of the transformer q st - - mon identity of the transformer t st - - mon identity of the transformer parset v1_dins stval st - - mon...

  • Page 58

    Do name do type da name fc t signal mon/c md description lva2on v1_dspc oper.Test co - - cmd command parameter for iec61850 oper.Check co - - cmd command parameter for iec61850 stval st - - mon setting lvaconst2 is used (service value) q st - - mon setting lvaconst2 is used (service value) t st - - ...

  • Page 59

    Do name do type da name fc t signal mon/c md description lvareset v1_dspc oper.Test co - - cmd command parameter for iec61850 oper.Check co - - cmd command parameter for iec61850 forcemast v1_dspc oper.Ctlval co - - cmd command parameter for iec61850 oper.Origin.Orcat co - - cmd command parameter fo...

  • Page 60

    Do name do type da name fc t signal mon/c md description t3pargr v1_dsps q st - t3pg mon transformer 3 included in parallel group t st - t3pg mon transformer 3 included in parallel group t4pargr v1_dsps stval st - t4pg mon transformer 4 included in parallel group q st - t4pg mon transformer 4 includ...

  • Page 61

    Do name do type da name fc t signal mon/c md description hivarfwd v1_dsps stval st - qgtfwd mon reactive power above the set limit powerreactiveforw q st - qgtfwd mon reactive power above the set limit powerreactiveforw t st - qgtfwd mon reactive power above the set limit powerreactiveforw hivarrv v...

  • Page 62

    Do name do type da name fc t signal mon/c md description hrhuntalm v1_dsps q st - hourhunt mon number of commands within the latest hour exceeded maximum level t st - hourhunt mon number of commands within the latest hour exceeded maximum level huntalm v1_dsps stval st - hunting mon number of comman...

  • Page 63

    Do name do type da name fc t signal mon/c md description lodare v11_dmv t mx - atccout mon group connection to yltcin busv v12_dmv mag.F mx - atccout mon group connection to yltcin q mx - atccout mon group connection to yltcin t mx - atccout mon group connection to yltcin setv v13_dmv mag.F mx - atc...

  • Page 64

    Do name do type da name fc t signal mon/c md description bndctrsng v2_dmv t mx - - mon voltage setpoint single bndctrpar v2_dmv mag.F mx - vsetpar mon average voltage setpoint used in parallel mode q mx - vsetpar mon average voltage setpoint used in parallel mode t mx - vsetpar mon average voltage s...

  • Page 65

    7.2.1.2 tap changer control and supervision, 6 binary inputs tcmyltc (84) ln type ln prefix ln class function block name tcmyltc (revision 1) tcm yltc tcmyltc (84) table 7: tcmyltc (84) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode ...

  • Page 66

    Do name do type da name fc t signal mon/c md description hitappos v1_dins q st - - mon tap position for the highest voltage t st - - mon tap position for the highest voltage lotappos v1_dins stval st - - mon tap position for the lowest voltage q st - - mon tap position for the lowest voltage t st - ...

  • Page 67

    Do name do type da name fc t signal mon/c md description tapchgflt v1_dsps t st - tcerral mon alarm for none or illegal tap position change tapposflt v1_dsps stval st - poserral mon alarm that indicates a problem with the position indication q st - poserral mon alarm that indicates a problem with th...

  • Page 68

    Do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 locswpos v1_dins stval st - - mon position of the local/remote switch q st - - mon position o...

  • Page 69

    Do name do type da name fc t signal mon/c md description rem v1_dsps stval st - rem mon remote operation allowed q st - rem mon remote operation allowed t st - rem mon remote operation allowed 7.3.2 logical node for interlocking scilo (3) ln type ln prefix ln class function block name scilo (revisio...

  • Page 70

    7.3.3 switch controller cswi 7.3.3.1 switch controller scswi ln type ln prefix ln class function block name scswi (revision 1) s cswi scswi table 10: scswi logical node data do name do type da name fc t signal mon/c md description pos a_ddpc cancel.Ctlval co - - cmd command parameter for iec61850 ca...

  • Page 71

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - - cmd mode parameter for 61850 oper.T co - - cmd mode par...

  • Page 72

    7.4 logical nodes for conversion functions 7.4.1 integer to boolean converter fcvb 7.4.1.1 integer to boolean 16 conversion with logic node representation ib16fcvb ln type ln prefix ln class function block name ib16fcvb (revision 0) ib16 fcvb ib16fcvb table 11: ib16fcvb logical node data do name do ...

  • Page 73

    Do name do type da name fc t signal mon/c md description iscso b_dinc q st - - mon integer to be converted to bit pattern out1 to out16 t st - - mon integer to be converted to bit pattern out1 to out16 ctlmodel cf - - - used by ch 7.4.2 boolean to integer converter fcvi 7.4.2.1 boolean 16 to integer...

  • Page 74

    7.5 logical nodes for protection functions 7.5.1 differential protection pdif 7.5.1.1 transformer differential protection, two winding t2wpdif (87t) ln type ln prefix ln class function block name t2wpdif (revision 2) t2w pdif t2wpdif (87t) table 13: t2wpdif (87t) logical node data do name do type da...

  • Page 75

    Do name do type da name fc t signal mon/c md description oprst v1_dsps q st - tripres mon trip signal from restrained differential protection t st - tripres mon trip signal from restrained differential protection opnssen v1_dsps stval st - trnssens mon trip signal from sensitive negative sequence di...

  • Page 76

    Do name do type da name fc t signal mon/c md description itrflt v1_dsps q st - - mon indication that internal fault has been detected t st - - mon indication that internal fault has been detected difalm v1_dsps stval st - idalarm mon general alarm for sustained differential currents q st - idalarm m...

  • Page 77

    Do name do type da name fc t signal mon/c md description beh a_dins t st - beh mon behaviour parameter for 61850 op b_dact general st t trip mon common trip signal q st t trip mon common trip signal t st t trip mon common trip signal oprst v1_dsps stval st - tripres mon trip signal from restrained d...

  • Page 78

    Do name do type da name fc t signal mon/c md description exflt v1_dsps q st - - mon indication that external fault/ disturbance has been detected t st - - mon indication that external fault/ disturbance has been detected itrflt v1_dsps stval st - - mon indication that internal fault has been detecte...

  • Page 79

    Do name do type da name fc t signal mon/c md description beh a_dins t st - beh mon behaviour parameter for 61850 str b_dacd general st - pickup mon general pickup signal q st - pickup mon general pickup signal t st - pickup mon general pickup signal op b_dact general st t trip mon common trip signal...

  • Page 80

    Do name do type da name fc t signal mon/c md description mod ainc oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st...

  • Page 81

    Do name do type da name fc t signal mon/c md description opunrst v1sps t st - tripunre mon trip signal from unrestrained differential protection opnsunrst v1sps stval st - trnsunr mon trip signal from unrestrained negative sequence differential protection q st - trnsunr mon trip signal from unrestra...

  • Page 82

    Do name do type da name fc t signal mon/c md description opnctalm v1sps stval st - openctal mon open ct alarm output signal. Issued after a delay ... Q st - openctal mon open ct alarm output signal. Issued after a delay ... T st - openctal mon open ct alarm output signal. Issued after a delay ... Di...

  • Page 83

    Do name do type da name fc t signal mon/c md description beh a_dins q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 op b_dact general st t trip mon trip signal q st t trip mon trip signal t st t trip mon trip signal impalm v1_dsps stval st - alarm mon alarm ...

  • Page 84

    Do name do type da name fc t signal mon/c md description mod a_dinc t st - - mon mode status value parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 table 19: zqmpdis (21) logical ...

  • Page 85

    Table 21: zqmpdis (21) logical node data (instance 3) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - z3_pu mon start...

  • Page 86

    Do name do type da name fc t signal mon/c md description str b_dacd general st - z5_pu mon start signal zone5 q st - z5_pu mon start signal zone5 t st - z5_pu mon start signal zone5 op b_dact general st t trz5 mon trip signal zone5 q st t trz5 mon trip signal zone5 t st t trz5 mon trip signal zone5 ...

  • Page 87

    7.5.2.2 phase selection with load encroachment, quadrilateral characteristic fdpspdis (21) ln type ln prefix ln class function block name fdpspdis (revision 1) fdps pdis fdpspdis table 25: fdpspdis logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co -...

  • Page 88

    Do name do type da name fc t signal mon/c md description strcnda v1_dins t st - dlecnd mon pickup for load encroachment and 3i0 strfwdpha v1_dsps stval st - fwd_a mon fault detected in phasea - forward direction q st - fwd_a mon fault detected in phasea - forward direction t st - fwd_a mon fault det...

  • Page 89

    Do name do type da name fc t signal mon/c md description strrvgnd v1_dsps stval st - rev_g mon ground fault detected in reverse direction q st - rev_g mon ground fault detected in reverse direction t st - rev_g mon ground fault detected in reverse direction strndpha v1_dsps stval st - ndir_a mon non...

  • Page 90

    Do name do type da name fc t signal mon/c md description str3ph v1_dsps t st - fwd_3ph mon pick up in forward direction for three- phase fault relgnd v1_dsps stval st - phg_flt mon current conditions release of phase- ground measuring elements q st - phg_flt mon current conditions release of phase- ...

  • Page 91

    Do name do type da name fc t signal mon/c md description mod a_dinc q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter fo...

  • Page 92

    Do name do type da name fc t signal mon/c md description mod a_dinc t st - - mon mode status value parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 table 28: zgcpdis (21g) logical...

  • Page 93

    Table 30: zgcpdis (21g) logical node data (instance 3) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - z3_pu mon star...

  • Page 94

    Table 32: lexpdis (40) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode pa...

  • Page 95

    Do name do type da name fc t signal mon/c md description prireact v2_dmv mag.F mx - xohm mon reactance in primary ohms q mx - xohm mon reactance in primary ohms t mx - xohm mon reactance in primary ohms 7.5.2.6 load enchroachment lepdis ln type ln prefix ln class function block name lepdis (revision...

  • Page 96

    Do name do type da name fc t signal mon/c md description str e_dacd neut st - - mon ground fault detected q st - - mon general pickup signal t st - - mon general pickup signal 7.5.3 directional overpower pdop 7.5.3.1 directional over-power protection goppdop (32) ln type ln prefix ln class function ...

  • Page 97

    Do name do type da name fc t signal mon/c md description opz1 v1_dsps t st - trip1 mon trip signal from stage 1 opz2 v1_dsps stval st - trip2 mon trip signal from stage 2 q st - trip2 mon trip signal from stage 2 t st - trip2 mon trip signal from stage 2 strz1 v1_dsps stval st - pickup1 mon pickup s...

  • Page 98

    Do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - bfi_3p mon general pickup signal q st - bfi_3p mon general pickup sig...

  • Page 99

    Table 36: sapfrc (81) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode par...

  • Page 100

    7.5.6 instantaneous overcurrent pioc 7.5.6.1 instantaneous phase overcurrent protection 3-phase output phpioc (50) ln type ln prefix ln class function block name phpioc (revision 1) ph pioc phpioc (50) table 37: phpioc (50) logical node data do name do type da name fc t signal mon/c md description m...

  • Page 101

    Table 38: efpioc (50n) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode pa...

  • Page 102

    Do name do type da name fc t signal mon/c md description mod a_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour paramete...

  • Page 103

    Do name do type da name fc t signal mon/c md description beh a_dins q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 losofgrd a_dsps stval st - lcg mon loss of channel guard signal output from communication scheme logic q st - lcg mon loss of channel guard si...

  • Page 104

    7.5.8.2 current reversal and wei logic for distance protection 3-phase zcrwpsch (85) ln type ln prefix ln class function block name zcrwpsch (revision 2) zcrw psch zcrwpsch (85) table 41: zcrwpsch (85) logical node data do name do type da name fc t signal mon/c md description op a_dact general st t ...

  • Page 105

    Do name do type da name fc t signal mon/c md description protx a_dsps t st t echo mon a signal that indicates channel start (cs) by wei logic str b_dacd general st - echo mon a signal that indicates channel start (cs) by wei logic q st - echo mon a signal that indicates channel start (cs) by wei log...

  • Page 106

    Do name do type da name fc t signal mon/c md description mod a_dinc q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter fo...

  • Page 107

    7.5.8.4 current reversal and weak-end infeed logic for residual overcurrent protection ecrwpsch (85) ln type ln prefix ln class function block name ecrwpsch (revision 2) ecrw psch ecrwpsch (85) table 43: ecrwpsch (85) logical node data do name do type da name fc t signal mon/c md description mod a_d...

  • Page 108

    Do name do type da name fc t signal mon/c md description op b_dact q st t trwei mon trip of wei logic t st t trwei mon trip of wei logic rvablk b_dact general st - irvl mon operation of current reversal logic q st - irvl mon operation of current reversal logic t st - irvl mon operation of current re...

  • Page 109

    Do name do type da name fc t signal mon/c md description mod a_dinc t st - - mon mode status parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - start mon gen...

  • Page 110

    Do name do type da name fc t signal mon/c md description opdirresa v1_dsps stval st - trdirin mon trip of the directional residual overcurrent q st - trdirin mon trip of the directional residual overcurrent t st - trdirin mon trip of the directional residual overcurrent angav v2_dmv mag.F mx - ang f...

  • Page 111

    Table 45: zcvpsof logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode paramet...

  • Page 112

    Table 46: ef4ptoc (51n_67n) logical node data (instance 1) do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co ...

  • Page 113

    Table 48: ef4ptoc (51n_67n) logical node data (instance 1) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 dir b_dacd general st - stdir mon ...

  • Page 114

    Do name do type da name fc t signal mon/c md description op b_dact t st t trst1 mon trip signal from step 1 mod c_dinc stval st - - mon mode status value parameter for 61850 q st - - mon mode status value parameter for 61850 t st - - mon mode status value parameter for 61850 table 51: ef4ptoc (51n_6...

  • Page 115

    Table 53: ef4ptoc (51n_67n) logical node data (instance 4) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - pu_st4 mon...

  • Page 116

    Do name do type da name fc t signal mon/c md description mod c_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 table 55: oc4ptoc (51_67) logical node data (instance 1) do name do type da name fc t signal ...

  • Page 117

    Table 57: oc4ptoc (51_67) logical node data (instance 2) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - st2 mon star...

  • Page 118

    Table 59: oc4ptoc (51_67) logical node data (instance 4) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - st4 mon star...

  • Page 119

    7.5.11.3 four step phase overcurrent protection, phase segregated output oc4sptoc ln type ln prefix ln class function block name gen4phar instance 1 (revision 2) gen4 phar oc4sptoc (51_67) oc4slln0 instance 1 (revision 0) - lln0 oc4sptoc (51_67) ph3ptoc instance 1 (revision 1) ph3 ptoc oc4sptoc (51_...

  • Page 120

    Do name do type da name fc t signal mon/c md description mod a_dinc q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter fo...

  • Page 121

    Do name do type da name fc t signal mon/c md description mod c_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 table 65: oc4sptoc (51_67) logical node data (instance 3) do name do type da name fc t signal...

  • Page 122

    Table 67: oc4sptoc (51_67) logical node data (instance 1) do name do type da name fc t signal mon/c md description str a_dacd general st - start mon general start signal phsa st - stl1 mon start signal from phase l1 dirphsa st - dirl1 mon direction for phase l1 phsb st - stl2 mon start signal from p...

  • Page 123

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.T co - - cmd mode parameter oper.Test co - - cmd mode parameter oper.Check co - - cmd mode parameter stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status paramet...

  • Page 124

    Do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - pickup mon pickup signal of the protection logic q st - pickup mon pi...

  • Page 125

    Do name do type da name fc t signal mon/c md description mod a_dinc t st - - mon mode status value parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 table 71: dnsptoc (46) logical ...

  • Page 126

    Do name do type da name fc t signal mon/c md description op b_dact t st t troc2 mon trip signal from step 2 (oc2) mod c_dinc stval st - - mon mode status value parameter for 61850 q st - - mon mode status value parameter for 61850 t st - - mon mode status value parameter for 61850 table 73: dnsptoc ...

  • Page 127

    Table 74: ns2ptoc (46i2) logical node data (instance 1) do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - -...

  • Page 128

    Table 76: ns2ptoc (46i2) logical node data (instance 2) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - pu_st2 mon pi...

  • Page 129

    Ln type ln prefix ln class function block name saptof (revision 1) sa ptof saptof (81) table 78: saptof (81) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co ...

  • Page 130

    Ov2ptov instance 1 (revision 1) ov2 ptov ov2ptov (59) ov2ptov instance 2 (revision 1) ov2 ptov ov2ptov (59) ph3ptrc instance 1 (revision 1) ph3 ptrc ov2ptov (59) table 79: ov2ptov (59) logical node data (instance 1) do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co -...

  • Page 131

    Do name do type da name fc t signal mon/c md description mod c_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 table 81: ov2ptov (59) logical node data (instance 2) do name do type da name fc t signal mon...

  • Page 132

    Do name do type da name fc t signal mon/c md description mod c_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 7.5.13.2 two step residual overvoltage protection rov2ptov (59n) ln type ln prefix ln class f...

  • Page 133

    Do name do type da name fc t signal mon/c md description str b_dacd general st - pickup mon general pickup signal q st - pickup mon general pickup signal t st - pickup mon general pickup signal op b_dact general st t trip mon common trip signal q st t trip mon common trip signal t st t trip mon comm...

  • Page 134

    Do name do type da name fc t signal mon/c md description op b_dact general st t trst2 mon trip signal from step 2 q st t trst2 mon trip signal from step 2 t st t trst2 mon trip signal from step 2 mod c_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850...

  • Page 135

    Do name do type da name fc t signal mon/c md description lors v1_dspc oper.Origin.Orcat co - - cmd command parameter for iec61850 oper.Origin.Orident co - - cmd command parameter for iec61850 oper.Ctlnum co - - cmd command parameter for iec61850 oper.T co - - cmd command parameter for iec61850 oper....

  • Page 136

    Do name do type da name fc t signal mon/c md description almthm a_dsps stval st - alarm mon alarm signal q st - alarm mon alarm signal t st - alarm mon alarm signal str b_dacd general st - pickup mon general pickup signal q st - pickup mon general pickup signal t st - pickup mon general pickup signa...

  • Page 137

    Do name do type da name fc t signal mon/c md description tmpamb v2_dmv mag.F mx - tempamb mon ambient temperature used in the calculations q mx - tempamb mon ambient temperature used in the calculations t mx - tempamb mon ambient temperature used in the calculations 7.5.15.2 thermal overload protect...

  • Page 138

    Do name do type da name fc t signal mon/c md description op b_dact t st t trip mon common trip signal tmp b_dmv mag.F mx - temp mon calculated temperature of the device q mx - temp mon calculated temperature of the device t mx - temp mon calculated temperature of the device tmprl b_dmv mag.F mx - te...

  • Page 139

    Table 90: trpttr (49) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode par...

  • Page 140

    Do name do type da name fc t signal mon/c md description tmmrslo v2_dmv mag.F mx - treslo mon estimated time to reset of the function (in min) q mx - treslo mon estimated time to reset of the function (in min) t mx - treslo mon estimated time to reset of the function (in min) aclcpct v2_dmv mag.F mx...

  • Page 141

    Do name do type da name fc t signal mon/c md description str a_dacd t st - ri mon general pickup signal beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 op b_dact general st t trip mon common trip si...

  • Page 142

    Table 93: uc2ptuc (37) logical node data (instance 2) do name do type da name fc t signal mon/c md description str a_dacd general st - pu_st2 mon start of step 2 phsa st - - mon start signal for step 2 in l1 phsb st - - mon start signal for step 2 in l2 phsc st - - mon start signal for step 2 in l3 ...

  • Page 143

    7.5.17 undervoltage ptuv 7.5.17.1 two step undervoltage protection uv2ptuv (27) ln type ln prefix ln class function block name gen2lln0 instance 1 (revision 1) - lln0 uv2ptuv (27) ph3ptrc instance 1 (revision 1) ph3 ptrc uv2ptuv (27) uv2ptuv instance 1 (revision 1) uv2 ptuv uv2ptuv (27) uv2ptuv inst...

  • Page 144

    Do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 op b_dact general st t trip mon common trip signal q st t trip mon common trip signal t st t ...

  • Page 145

    Do name do type da name fc t signal mon/c md description str a_dacd phsc st - - mon pickup signal from step2 phase c q st - pu_st2 mon start signal from step 2 t st - pu_st2 mon start signal from step 2 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter fo...

  • Page 146

    Do name do type da name fc t signal mon/c md description str b_dacd q st - pickup mon pickup signal t st - pickup mon pickup signal op b_dact general st t trip mon trip signal q st t trip mon trip signal t st t trip mon trip signal 7.5.18 underfrequency ptuf 7.5.18.1 underfrequency protection saptuf...

  • Page 147

    Do name do type da name fc t signal mon/c md description op b_dact t st t trip mon common trip signal blklomg v1_dsps stval st - blkdmagn mon measurement blocked due to low voltage amplitude q st - blkdmagn mon measurement blocked due to low voltage amplitude t st - blkdmagn mon measurement blocked ...

  • Page 148

    Do name do type da name fc t signal mon/c md description str b_dacd general st - bfi mon general pickup signal q st - bfi mon general pickup signal t st - bfi mon general pickup signal op b_dact general st t trip mon common trip signal q st t trip mon common trip signal t st t trip mon common trip s...

  • Page 149

    Do name do type da name fc t signal mon/c md description beh a_dins q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - start mon start signal from accidental energizing protection q st - start mon start signal from accidental energizing ...

  • Page 150

    Do name do type da name fc t signal mon/c md description mod a_dinc stval st - - mon mode status value parameter for 61850 q st - - mon mode status value parameter for 61850 t st - - mon mode status value parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon ...

  • Page 151

    7.5.22 ground fault protection phiz 7.5.22.1 100% stator ground fault protection, 3rd harmonic based stefphiz (59thd) ln type ln prefix ln class function block name stefphiz (revision 2) stef phiz stefphiz (59thd) table 104: stefphiz (59thd) logical node data do name do type da name fc t signal mon/...

  • Page 152

    Do name do type da name fc t signal mon/c md description opun v1_dsps q st - trip_vn mon trip by fund. Freq. Neutral over-voltage protection t st - trip_vn mon trip by fund. Freq. Neutral over-voltage protection str3rdh v1_dsps stval st - pu_3h mon start by one of two 3rd harmonic voltage-based prot...

  • Page 153

    Do name do type da name fc t signal mon/c md description un v2_dmv mag.F mx - v_n mon fund. Frequency voltage at generator neutral q mx - v_n mon fund. Frequency voltage at generator neutral t mx - v_n mon fund. Frequency voltage at generator neutral volangclc v2_dmv mag.F mx - angle mon angle betwe...

  • Page 154

    Table 106: vrpvoc (51v) logical node data (instance 1) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - stuv mon start...

  • Page 155

    Table 108: vrpvoc (51v) logical node data (instance 1) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 str b_dacd general st - stoc mon start...

  • Page 156

    7.7 logical nodes for protection related functions 7.7.1 breaker failure rbrf 7.7.1.1 breaker failure protection 3-phase activation and output ccrbrf (50bf) ln type ln prefix ln class function block name ccrbrf (revision 1) cc rbrf ccrbrf (50bf) table 110: ccrbrf (50bf) logical node data do name do ...

  • Page 157

    7.7.1.2 breaker failure protection phase segregated activation and output csprbrf (50bf) ln type ln prefix ln class function block name csprbrf (revision 0) csp rbrf csprbrf (50bf) table 111: csprbrf (50bf) logical node data do name do type da name fc t signal mon/c md description opin a_dact genera...

  • Page 158

    Ln type ln prefix ln class function block name ccsrdif (revision 1) ccs rdif ccsrdif (87) table 112: ccsrdif (87) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Oriden...

  • Page 159

    Table 113: drprdre logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - - cmd mode parameter...

  • Page 160

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status value parameter for 61850 q st - - mon mode status value parameter ...

  • Page 161

    Table 115: sddrfuf logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode parame...

  • Page 162

    Table 116: ccrpld (52pd) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode ...

  • Page 163

    Table 117: zmrpsb (68) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode pa...

  • Page 164

    Ln type ln prefix ln class function block name smbrrec (revision 2) smb rrec smbrrec (79) table 118: smbrrec (79) logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Oriden...

  • Page 165

    Do name do type da name fc t signal mon/c md description rec32cnt v1_dins stval st - count3p2 mon counting the number of three-phase reclosing shot 2 q st - count3p2 mon counting the number of three-phase reclosing shot 2 t st - count3p2 mon counting the number of three-phase reclosing shot 2 rec33c...

  • Page 166

    Do name do type da name fc t signal mon/c md description rdyrec v1_dsps q st - ready mon indicates that ar is ready for a new sequence t st - ready mon indicates that ar is ready for a new sequence actrec v1_dsps stval st - active mon reclosing sequence in progress q st - active mon reclosing sequen...

  • Page 167

    Do name do type da name fc t signal mon/c md description prgrec34 v1_dsps stval st - 3pt4 mon three-phase reclosing in progress, shot 4 q st - 3pt4 mon three-phase reclosing in progress, shot 4 t st - 3pt4 mon three-phase reclosing in progress, shot 4 prgrec35 v1_dsps stval st - 3pt5 mon three-phase...

  • Page 168

    Do name do type da name fc t signal mon/c md description beh a_dins q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 op b_dact general st t closecmd mon closing command for cb q st t closecmd mon closing command for cb t st t closecmd mon closing command for ...

  • Page 169

    Do name do type da name fc t signal mon/c md description rec35cnt v1_dins q st - count3p5 mon counting the number of three-phase reclosing shot 5 t st - count3p5 mon counting the number of three-phase reclosing shot 5 totreccnt v1_dins stval st - countar mon counting total number of reclosing shots ...

  • Page 170

    Do name do type da name fc t signal mon/c md description unsrec v1_dsps stval st - unsuccl mon reclosing unsuccessful, signal resets after the reclaim time q st - unsuccl mon reclosing unsuccessful, signal resets after the reclaim time t st - unsuccl mon reclosing unsuccessful, signal resets after t...

  • Page 171

    Do name do type da name fc t signal mon/c md description wtmst v1_dsps q st - wfmaster mon signal to slave issued by master for sequential reclosing t st - wfmaster mon signal to slave issued by master for sequential reclosing prgrec11 v1_dsps stval st - 1pt1 mon single-phase reclosing in progress, ...

  • Page 172

    Do name do type da name fc t signal mon/c md description hzind a_dsps q st - frdiffa mon frequency difference out of limit for auto operation t st - frdiffa mon frequency difference out of limit for auto operation angind a_dsps stval st - phdiffa mon phase angle difference out of limit for auto oper...

  • Page 173

    Do name do type da name fc t signal mon/c md description vlin v2_dmv mag.F mx - vline mon line voltage q mx - vline mon line voltage t mx - vline mon line voltage table 121: sesrsyn (25) logical node data (instance 2) do name do type da name fc t signal mon/c md description beh a_dins stval st - beh...

  • Page 174

    Table 122: sesrsyn (25) logical node data (instance 1) do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - - ...

  • Page 175

    Do name do type da name fc t signal mon/c md description vhialm v1_dsps t st - voksc mon voltage magnitudes above set limits inadcbcls v1_dsps stval st - inadvcls mon inadvertent circuit breaker closing q st - inadvcls mon inadvertent circuit breaker closing t st - inadvcls mon inadvertent circuit b...

  • Page 176

    7.8 logical nodes for generic references 7.8.1 generic process i/o ggio 7.8.1.1 select release selggio . Ln type ln prefix ln class function block name selggio (revision 1) sel ggio selggio table 124: selggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper....

  • Page 177

    Table 125: slggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode paramet...

  • Page 178

    Do name do type da name fc t signal mon/c md description spcco v2_dspc oper.Test co - - cmd command parameter for iec61850 oper.Check co - - cmd command parameter for iec61850 ctlmodel cf - - - used by ch sbotimeout cf - - - used by ch sboclass cf - - - used by ch 7.8.1.3 selector mini switch vsggio...

  • Page 179

    Do name do type da name fc t signal mon/c md description dpcso d_ddpc oper.Origin.Orident co - - cmd command parameter for iec61850 cancel.Origin.Orident co - - cmd command parameter for iec61850 cancel.Ctlnum co - - cmd command parameter for iec61850 oper.Ctlnum co - - cmd command parameter for iec...

  • Page 180

    Do name do type da name fc t signal mon/c md description mod a_dinc stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour paramete...

  • Page 181

    Do name do type da name fc t signal mon/c md description spcso1 v2_dspc oper.Ctlnum co - - cmd command parameter for iec61850 oper.T co - - cmd command parameter for iec61850 oper.Test co - - cmd command parameter for iec61850 oper.Check co - - cmd command parameter for iec61850 stval st - out1 mon ...

  • Page 182

    Do name do type da name fc t signal mon/c md description spcso4 v2_dspc t st - out4 mon output4 spcso5 v2_dspc oper.Ctlval co - - cmd command parameter for iec61850 oper.Origin.Orcat co - - cmd command parameter for iec61850 oper.Origin.Orident co - - cmd command parameter for iec61850 oper.Ctlnum c...

  • Page 183

    Do name do type da name fc t signal mon/c md description spcso8 v2_dspc oper.Test co - - cmd command parameter for iec61850 oper.Check co - - cmd command parameter for iec61850 stval st - out8 mon output8 q st - out8 mon output8 t st - out8 mon output8 7.8.1.6 event counter cntggio ln type ln prefix...

  • Page 184

    Do name do type da name fc t signal mon/c md description cnt3 v1_dbcr q st - value3 mon output of counter 3 t st - value3 mon output of counter 3 cnt4 v1_dbcr actval st - value4 mon output of counter 4 q st - value4 mon output of counter 4 t st - value4 mon output of counter 4 cnt5 v1_dbcr actval st...

  • Page 185

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.T co - - cmd mode status value parameter for 61850 oper.Test co - - cmd mode status value parameter for 61850 oper.Check co - - cmd mode status value parameter for 61850 stval st - - mon mode parameter for 61850 q st - - mon mo...

  • Page 186

    7.8.1.8 iec61850 generic communication i/o functions spggio ln type ln prefix ln class function block name spggio (revision 1) sp ggio spggio table 131: spggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orca...

  • Page 187

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode parameter oper.Test co - - cmd mode parameter oper.Check co - - cmd mode parameter stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for ...

  • Page 188

    Do name do type da name fc t signal mon/c md description ind9 c_dsps t st - out9 mon output 9 status ind10 c_dsps stval st - out10 mon output 10 status q st - out10 mon output 10 status t st - out10 mon output 10 status ind11 c_dsps stval st - out11 mon output 11 status q st - out11 mon output 11 st...

  • Page 189

    Table 133: mvggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode paramet...

  • Page 190

    Table 134: pcggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode paramet...

  • Page 191

    Table 135: tmaggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode parame...

  • Page 192

    Table 136: teiggio logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - - cmd mode parameter...

  • Page 193

    7.9 logical nodes for metering and measurement 7.9.1 metering mmtr 7.9.1.1 function for energy calculation and demand handling etpmmtr ln type ln prefix ln class function block name etpmmtr (revision 3) etp mmtr etpmmtr table 137: etpmmtr logical node data do name do type da name fc t signal mon/c m...

  • Page 194

    Do name do type da name fc t signal mon/c md description maxdmdrs v1_dspc oper.T co - - cmd command parameter for iec61850 oper.Test co - - cmd command parameter for iec61850 oper.Check co - - cmd command parameter for iec61850 stracc v1_dsps stval st - accst mon start of accumulating energy values ...

  • Page 195

    Do name do type da name fc t signal mon/c md description wsaccfwd v2_dbcr actval st - eafacc mon accumulated forward active energy value q st - eafacc mon accumulated forward active energy value t st - eafacc mon accumulated forward active energy value wsaccrev v2_dbcr actval st - earacc mon accumul...

  • Page 196

    Table 138: cvmmxn logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter oper.Origin.Orcat co - - cmd mode parameter oper.Origin.Orident co - - cmd mode parameter oper.Ctlnum co - - cmd mode parameter oper.T co - - cmd mode paramet...

  • Page 197

    Do name do type da name fc t signal mon/c md description hz a_dmv rangec.Llim.F cf - frlowlim - low limit (physical value) rangec.Lllim.F cf - frlowlowlim - low low limit (physical value) rangec.Max.F cf - frmax - maximum value rangec.Min.F cf - frmin - minimum value submag.F sv - - - substituted va...

  • Page 198

    Do name do type da name fc t signal mon/c md description vol a_dmv submag.F sv - - - substituted value mag.F mx - u mon calculated voltage magnitude of deadband value range mx - u_range mon calcuated voltage range q mx - u mon calculated voltage magnitude of deadband value t mx - u mon calculated vo...

  • Page 199

    Do name do type da name fc t signal mon/c md description volampr a_dmv range mx - q_range mon reactive power range q mx - q mon reactive power magnitude of deadband value t mx - q mon reactive power magnitude of deadband value subena sv - - - enable substitution db cf - qdbrepint - cycl: report inte...

  • Page 200

    7.9.3 measurement mmxu 7.9.3.1 phase current measurement cmmxu ln type ln prefix ln class function block name cmmxu (revision 1) c mmxu cmmxu table 139: cmmxu logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Or...

  • Page 201

    Do name do type da name fc t signal mon/c md description a a_dwye rangec.Min.F cf - ilmin - minimum value rangec.Max.F cf - ilmax - maximum value rangec.Max.F cf - ilmax - maximum value rangec.Max.F cf - ilmax - maximum value cval.Mag.F mx - i_a mon ia amplitude cval.Mag.F mx - i_b mon ib amplitude ...

  • Page 202

    Table 140: vmmxu logical node data do name do type da name fc t signal mon/c md description ppv a_ddel rangec.Hhlim.F cf - vlhihillim - high high limit (physical value) rangec.Hhlim.F cf - vlhihillim - high high limit (physical value) rangec.Hhlim.F cf - vlhihillim - high high limit (physical value)...

  • Page 203

    Do name do type da name fc t signal mon/c md description ppv a_ddel subena sv - - - enable substitution subena sv - - - enable substitution db cf - vldbrepint - cycl: report interval (s), db: in % of range, int db: in %s db cf - vldbrepint - cycl: report interval (s), db: in % of range, int db: in %...

  • Page 204

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlnum co - - cmd mode parameter for 61850 oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status parameter for 61850...

  • Page 205

    Do name do type da name fc t signal mon/c md description phv a_dwye range mx - vc_range mon v_c amplitude range range mx - va_range mon v_a amplitude range range mx - vb_range mon v_b amplitude range q mx - v_c mon v_c amplitude, magnitude of reported value q mx - v_b mon v_b amplitude, magnitude of...

  • Page 206

    Table 142: cmsqi logical node data do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlval co - - cmd mode parameter for 61850 oper.Origin.Orcat co - - cmd mode parameter for 61850 oper.Origin.Orident co - - cmd mode parameter for 61850 oper.Ctlnum co - - cmd mode parameter f...

  • Page 207

    Do name do type da name fc t signal mon/c md description seqa a_dseq rangec.Max.F cf - i2max - maximum value subcval.Mag.F sv - - - substituted value subcval.Mag.F sv - - - substituted value range mx - i2rang mon i2 magnitude range range mx - 3i0rang mon 3i0 magnitude range range mx - i1rang mon i1a...

  • Page 208

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlnum co - - cmd mode parameter for 61850 oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status parameter for 61850...

  • Page 209

    Do name do type da name fc t signal mon/c md description seqv a_dseq range mx - v1rang mon v1 magnitude range q mx - v2 mon u2 amplitude q mx - v1 mon u1 amplitude q mx - 3v0 mon 3u0 amplitude t mx - 3v0 mon 3u0 amplitude t mx - v1 mon u1 amplitude t mx - v2 mon u2 amplitude subena sv - - - enable s...

  • Page 210

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlnum co - - cmd mode parameter for 61850 oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status parameter for 61850...

  • Page 211

    Do name do type da name fc t signal mon/c md description inatmdcnt v1_dins stval st - nooprday mon the number of days cb has been inactive q st - nooprday mon the number of days cb has been inactive t st - nooprday mon the number of days cb has been inactive rmnlifpha v1_dins stval st - cblife_a mon...

  • Page 212

    Do name do type da name fc t signal mon/c md description rssprchatm v1_dspc oper.Origin.Orcat co - - cmd command parameter for iec61850 oper.Origin.Orident co - - cmd command parameter for iec61850 oper.Ctlnum co - - cmd command parameter for iec61850 oper.T co - - cmd command parameter for iec61850...

  • Page 213

    Do name do type da name fc t signal mon/c md description lontmalm v1_dsps t st - noopralm mon cb 'not operated for long time' alarm sprchaalm v1_dsps stval st - sprchral mon spring charging time has crossed the set value q st - sprchral mon spring charging time has crossed the set value t st - sprch...

  • Page 214

    Do name do type da name fc t signal mon/c md description accapwrphb v2_dmv mag.F mx - iacc_b mon accumulated currents power (iyt), phase b q mx - iacc_b mon accumulated currents power (iyt), phase b t mx - iacc_b mon accumulated currents power (iyt), phase b accapwrphc v2_dmv mag.F mx - iacc_c mon a...

  • Page 215

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlnum co - - cmd mode parameter for 61850 oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status parameter for 61850...

  • Page 216

    7.10.3 insulation medium supervision (liquid) siml 7.10.3.1 insulation liquid monitoring function ssiml (71) ln type ln prefix ln class function block name ssiml (revision 0) s siml ssiml (71) table 147: ssiml (71) logical node data do name do type da name fc t signal mon/c md description mod a_dinc...

  • Page 217

    Do name do type da name fc t signal mon/c md description tmp b_dmv t mx - temp mon temperature of the insulation medium lors v1_dspc oper.Ctlval co - - cmd command parameter for iec61850 oper.Origin.Orcat co - - cmd command parameter for iec61850 oper.Origin.Orident co - - cmd command parameter for ...

  • Page 218

    Do name do type da name fc t signal mon/c md description beh a_dins stval st - beh mon behaviour parameter for 61850 q st - beh mon behaviour parameter for 61850 t st - beh mon behaviour parameter for 61850 blkcls a_dspc oper.Ctlval co - - cmd special block command value oper.Origin.Orcat co - - cmd...

  • Page 219

    Do name do type da name fc t signal mon/c md description pos c_ddpc q st - position mon apparatus position indication t st - position mon apparatus position indication subena sv - - - substitute enable subval sv - - - substituted double position value cbopcap h_dins stval st - - mon breaker operatin...

  • Page 220

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Ctlnum co - - cmd mode parameter for 61850 oper.T co - - cmd mode parameter for 61850 oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status value parameter for...

  • Page 221

    Do name do type da name fc t signal mon/c md description loc a_dsps q st - - mon indication that the function is in local mode (process level) t st - - mon indication that the function is in local mode (process level) opcnt b_dins stval st - cnt_val mon operation counter value q st - cnt_val mon ope...

  • Page 222

    7.12 logical nodes for power transformers 7.12.1 tap changer yltc 7.12.1.1 tap changer control and supervision, 6 binary inputs tcmyltc (84) ln type ln prefix ln class function block name tcmyltc (revision 5) tcm yltc tcmyltc (84) table 150: tcmyltc (84) logical node data do name do type da name fc ...

  • Page 223

    Do name do type da name fc t signal mon/c md description tapchg b_dbsc t st - tcpos mon integer value corresponding to actual tap position opcnt b_dins stval st - cnt_val mon number of operations on tap changer q st - cnt_val mon number of operations on tap changer t st - cnt_val mon number of opera...

  • Page 224

    Do name do type da name fc t signal mon/c md description invposchg v1_dsps t st - invalpos mon last position change was an invalid change tapchgflt v1_dsps stval st - tcerral mon alarm for none or illegal tap position change q st - tcerral mon alarm for none or illegal tap position change t st - tce...

  • Page 225

    Do name do type da name fc t signal mon/c md description mod a_dinc oper.Test co - - cmd mode parameter for 61850 oper.Check co - - cmd mode parameter for 61850 stval st - - mon mode status parameter for 61850 q st - - mon mode status parameter for 61850 t st - - mon mode status parameter for 61850 ...

  • Page 226

    220

  • Page 227

    Section 8 goose receive blocks 8.1 interlock receive - intlkrcv 8.1.1 horizontal communication via goose for interlocking gooseintlkrcv ln type ln prefix ln class function block name intgrec instance 1 (revision 0) int grec gooseintlkrcv table 152: gooseintlkrcv logical node data (instance 1) do nam...

  • Page 228

    Do name do type da name fc t signal mon/c md description tagapp12 a_ddps stval st - - mon internal parameter tag to handle 61850 mapping tagapp13 a_ddps stval st - - mon internal parameter tag to handle 61850 mapping tagapp14 a_ddps stval st - - mon internal parameter tag to handle 61850 mapping tag...

  • Page 229

    Do name do type da name fc t signal mon/c md description tagbinout7 a_dsps stval st - - mon internal parameter tag to handle 61850 mapping tagbinout8 a_dsps stval st - - mon internal parameter tag to handle 61850 mapping tagbinout9 a_dsps stval st - - mon internal parameter tag to handle 61850 mappi...

  • Page 230

    Do name do type da name fc t signal mon/c md description in_lodare v11_dmv q mx - - mon real part of load current (horizontal communication) t mx - - mon real part of load current (horizontal communication) in_busv v12_dmv mag.F mx - - mon busbar voltage (horizontal communication) q mx - - mon busba...

  • Page 231

    Table 155: goosedprcv logical node data (instance 1) do name do type da name fc t signal mon/c md description tagdpout a_ddps stval st - - mon internal parameter tag to handle 61850 mapping q st - - mon internal parameter tag to handle 61850 mapping 8.5 integer receive - intrcv 8.5.1 goose function ...

  • Page 232

    Table 157: goosemvrcv logical node data (instance 1) do name do type da name fc t signal mon/c md description tagmvout a_dmv mag.F mx - - mon internal parameter tag to handle 61850 mapping q mx - - mon internal parameter tag to handle 61850 mapping 8.7 single point receive (sp) - sprcv 8.7.1 goose f...

  • Page 233

    Section 9 glossary ac alternating current acc actual channel act application configuration tool within pcm600 a/d converter analog-to-digital converter adbs amplitude deadband supervision ai analog input ansi american national standards institute ar autoreclosing asct auxiliary summation current tra...

  • Page 234

    Comtrade standard common format for transient data exchange format for disturbance recorder according to ieee/ansi c37.111, 1999 / iec60255-24 cot cause of transmission cpu central processing unit cr carrier receive crc cyclic redundancy check crob control relay output block cs carrier send ct curre...

  • Page 235

    Emi electromagnetic interference enfp end fault protection epa enhanced performance architecture esd electrostatic discharge f-sma type of optical fibre connector fan fault number fcb flow control bit; frame count bit fox 20 modular 20 channel telecommunication system for speech, data and protection...

  • Page 236

    Iec 60870-5-103 communication standard for protective equipment. A serial master/slave protocol for point-to-point communication iec 61850 substation automation communication standard iec 61850–8–1 communication protocol standard ieee institute of electrical and electronics engineers ieee 802.12 a n...

  • Page 237

    Irig-b: interrange instrumentation group time code format b, standard 200 itu international telecommunications union lan local area network lcd liquid crystal display ldd local detection device led light-emitting diode lnt lon network tool mcb miniature circuit breaker mval value of measurement ncc ...

  • Page 238

    Pt ratio potential transformer or voltage transformer ratio putt permissive underreach transfer trip rca relay characteristic angle risc reduced instruction set computer rms value root mean square value rs422 a balanced serial interface for the transmission of digital data in point-to-point connecti...

  • Page 239

    Tc trip coil tcs trip circuit supervision tcp transmission control protocol. The most common transport layer protocol used on ethernet and the internet. Tcp/ip transmission control protocol over internet protocol. The de facto standard ethernet protocols incorporated into 4.2bsd unix. Tcp/ip was dev...

  • Page 240

    Coordinated universal time is expressed using a 24-hour clock, and uses the gregorian calendar. It is used for aeroplane and ship navigation, where it is also sometimes known by the military name, "zulu time." "zulu" in the phonetic alphabet stands for "z", which stands for longitude zero. Uv underv...

  • Page 241

    235.

  • Page 242

    Contact us for more information please contact: abb ab grid automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 www.Abb.Com/protection-control note: we reserve the right to make technical changes or modify the contents of this document without prior notice. Abb ab does not accep...