ABB Relion 650 series RET650 Product Manual

Manual is about: Transormer protection

Summary of Relion 650 series RET650

  • Page 1

    Relion ® 650 series transformer protection ret650 product guide.

  • Page 2

    Contents 1. 650 series overview..............................................3 2. Application...........................................................3 3. Available functions...............................................7 4. Differential protection.........................................17 5. Cu...

  • Page 3

    1. 650 series overview the 650 series ieds provide optimum 'off-the- shelf', ready-to-use solutions. It is configured with complete protection functionality and default parameters to meet the needs of a wide range of applications for generation transmission and sub-transmission grids. The 650 series...

  • Page 4

    Disturbance recording is available to allow independent post-fault analysis after primary disturbances. Three packages have been defined for the following applications: • two-winding transformer in single breaker arrangements (a01) • three-winding transformer in single breaker arrangements (a05) • t...

  • Page 5

    T2w pdif 87t 3id/i cc rbrf 50bf 3i> bf cc rbrf 50bf 3i> bf oc4 ptoc 50/51 3i> oc4 ptoc 51/67 3i> cc rpld 52pd pd ef4 ptoc 51n in> cc rpld 52pd pd tr pttr 49 ith c msqi meter. V mmxu meter. C mmxu meter. Cv mmxn meter. Tcs scbr cond tcs scbr cond spvn zbat cond tr8 atcc 90 u tcm yltc 84 uv2 ptuv 27 u...

  • Page 6

    Ret650 a05 - 3 winding transformer protection 20ai 2*(6i+4u) w1 t3w pdif 87t 3id/i cc rbrf 50bf 3i> bf cc rbrf 50bf 3i> bf oc4 ptoc 50/51 3i> oc4 ptoc 51/67 3i> cc rpld 52pd pd cc rbrf 50bf 3i> bf cc rpld 52pd pd ef4 ptoc 51n in> cc rpld 52pd pd tr pttr 49 ith tr pttr 49 ith v msqi meter. C msqi met...

  • Page 7

    Ret650 a07 – oltc control for 1 or 2 transformers 10ai (6i+4u) tr pttr 49 ith ef4 ptoc 50n/51n in> cv mmxn meter. T1 oc4 ptoc 50/51 3i> etp mmtr meter. Rov ptov 59n 3u0> t2 trx atcc 90 u uv2 ptov 27 u ov2 ptov 59 u> tr pttr 49 ith ef4 ptoc 50n/51n in> cv mmxn meter. Oc4 ptoc 50/51 3i> etp mmtr meter...

  • Page 8

    3. Available functions main protection functions iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc differential protection t2wpdif 87t transformer differential protection, two winding 1 t3wpdif 87t transformer differential ...

  • Page 9

    Back-up protection functions iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc current protection phpioc 50 instantaneous phase overcurrent protection 2 3 oc4ptoc 51/67 four step directional phase overcurrent protection 2 3...

  • Page 10

    Iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc saptuf 81 underfrequency function 4 4 4 saptof 81 overfrequency function 4 4 4 sapfrc 81 rate-of-change frequency protection 2 2 4 transformer protection ret650 1mrk 504 127...

  • Page 11

    Control and monitoring functions iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc control qcbay bay control 1 1 1 locrem handling of lr-switch positions 1 1 1 locremctrl lhmi control of permitted source to operate (psto) 1...

  • Page 12

    Iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc logic smpptrc 94 tripping logic 2 3 2 tmaggio trip matrix logic 12 12 12 or configurable logic blocks, or gate 283 283 283 inverter configurable logic blocks, inverter gate ...

  • Page 13

    Iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc cmmxu phase current measurement 10 10 10 vmmxu phase-phase voltage measurement 6 6 6 cmsqi current sequence component measurement 6 6 6 vmsqi voltage sequence measurement 6 ...

  • Page 14

    Iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc i103fltprot function status fault protection for iec60870-5-103 1 1 1 i103ied ied status for iec60870-5-103 1 1 1 i103superv supervison status for iec60870-5-103 1 1 1 i103u...

  • Page 15

    Designed to communicate iec 61850/ function block name ansi function description transformer ret650 (a01) 2w/1cb ret650 (a05) 3w/1cb ret650 (a07) oltc station communication iec 61850 communication protocol, lan1 1 1 1 dnp3.0 for tcp/ip communication protocol, lan1 1 1 1 iec61870-5-103 iec60870-5-103...

  • Page 16

    Basic ied functions iec 61850/ function block name function description basic functions included in all products interrsig self supervision with internal event list 1 selfsupevlst self supervision with internal event list 1 sntp time synchronization 1 timesynchgen time synchronization 1 dtsbegin, dt...

  • Page 17

    4. Differential protection transformer differential protection t2wpdif/t3wpdif the transformer differential protection, two- winding (t2wpdif) and transformer differential protection, three-winding (t3wpdif) are provided with internal ct ratio matching and vector group compensation and settable, zer...

  • Page 18

    Voltage dependent resistor externally to the ied. Hzpdif can be used as high impedance ref protection. 5. Current protection instantaneous phase overcurrent protection phpioc the instantaneous three phase overcurrent function has a low transient overreach and short tripping time to allow use as a hi...

  • Page 19

    Ccrbrf can be current based, contact based, or an adaptive combination of these two principles. A current check with extremely short reset time is used as check criterion to achieve a high security against unnecessary operation. A contact check criteria can be used where the fault current through th...

  • Page 20

    Outages or as long-time delayed back-up to primary protection. Uv2ptuv has two voltage steps, where step 1 is settable as inverse or definite time delayed. Step 2 is always definite time delayed. Two step overvoltage protection ov2ptov overvoltages may occur in the power system during abnormal condi...

  • Page 21

    8. Secondary system supervision breaker close/trip circuit monitoring tcsscbr the trip circuit supervision function tcsscbr is designed to supervise the control circuit of the circuit breaker. The invalidity of a control circuit is detected by using a dedicated output contact that contains the super...

  • Page 22

    Logic rotating switch for function selection and lhmi presentation slggio the logic rotating switch for function selection and lhmi presentation function (slggio) (or the selector switch function block) is used to get a selector switch functionality similar to the one provided by a hardware selector...

  • Page 23

    • gate function block is used for whether or not a signal should be able to pass from the input to the output. • xor function block. • loopdelay function block used to delay the output signal one execution cycle. • timerset function has pick-up and drop- out delayed outputs related to the input sign...

  • Page 24

    Disturbance report drprdre, always included in the ied, acquires sampled data of all selected analog input and binary signals connected to the function block that is, maximum 40 analog and 96 binary signals. The disturbance report functionality is a common name for several functions: • event list • ...

  • Page 25

    Disturbance recorder drprdre the disturbance recorder function supplies fast, complete and reliable information about disturbances in the power system. It facilitates understanding system behavior and related primary and secondary equipment during and after a disturbance. Recorded information is use...

  • Page 26

    The function contains a blocking functionality. It is possible to block the function outputs, if desired. 12. Metering pulse counter logic pcggio pulse counter (pcggio) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of en...

  • Page 27

    • status indication leds • alarm indication leds which can indicate three states with the colors green, yellow and red, with user printable label. All leds are configurable from the pcm600 tool • liquid crystal display (lcd) • keypad with push buttons for control and navigation purposes, switch for ...

  • Page 28

    Authority check athchck to safeguard the interests of our customers, both the ied and the tools that are accessing the ied are protected, by means of authorization handling. The authorization handling of the ied and the pcm600 is implemented at both access points to the ied: • local, through the loc...

  • Page 29

    This is typically used for sending apparatus position indications for interlocking or reservation signals for 1-of-n control. Goose can also be used to exchange any boolean, integer, double point and analog measured values between ieds. Dnp3 protocol dnp3 (distributed network protocol) is a set of c...

  • Page 30

    Rack mounting the ied a c b e d iec09000676.Ai iec09000676 v1 en figure 9. Rack mounted ied a 224 mm + 12 mm with ring-lug connector b 25.5 mm c 482.6 mm (19") d 265.9 mm (6u) e 13 mm a b c e d iec09000677.Ai iec09000677 v1 en figure 10. Two rack mounted ieds side by side a 224 mm + 12 mm with ring-...

  • Page 31

    17. Connection diagrams 1mrk006501-fb 2 pg 1.1 iec v1 en figure 13. Designation for 6u, 1/2x19" casing with 1 trm and 1 aim (a05) module slot rear position com pcom x0, x1, x4, x9,x304 psm ppsm x307, x309, x410 trm p2 x101, x102 aim p4 x103, x104 bio p5 x331, x334 bio p6 x336, x339 transformer prote...

  • Page 32

    1mrk006501-gb 2 pg 1.1 iec v1 en figure 14. Designation for 6u, 1/2x19" casing with 1 trm (a01/a07) module slot rear position com pcom x0, x1, x4, x9,x304 psm ppsm x307, x309, x410 trm p2 x101, x102 bio p3 x321, x324 bio p4 x326, x329 bio p5 x331, x334 bio p6 x336, x339 transformer protection ret650...

  • Page 33

    Connection diagrams for ret650 a01 1mrk006501-gb 3 pg 1.1 iec v1 en figure 15. Communication module (com) 1mrk006501-gb 4 pg 1.1 iec v1 en figure 16. Power supply module (psm) 48-125v dc 1mrk006501-gb 5 pg 1.1 iec v1 en figure 17. Power supply module (psm), 110-250v dc 1mrk006501-gb 6 pg 1.1 iec v1 ...

  • Page 34

    1mrk006501-gb 7 pg 1.1 iec v1 en figure 19. Binary input/output (bio) option (terminal x321, x324) 1mrk006501-gb 8 pg 1.1 iec v1 en figure 20. Binary input/output (bio) option (terminal x326, x329) connection diagrams for ret650 a05 1mrk006501-fb 3 pg 1.1 iec v1 en figure 21. Communication module (c...

  • Page 35

    1mrk006501-fb 5 pg 1.1 iec v1 en figure 23. Power supply module (psm), 110-250v dc 1mrk006501-fb 6 pg 1.1 iec v1 en figure 24. Transformer module (trm) 1mrk006501-fb 7 pg 1.1 iec v1 en figure 25. Analog input module (aim) 1mrk006501-fb 8 pg 1.1 iec v1 en figure 26. Binary input/output (bio) option (...

  • Page 36

    1mrk006501-fb 9 pg 1.1 iec v1 en figure 27. Binary input/output (bio) option (terminal x336, x339) connection diagrams for ret650 a07 1mrk006501-eb 3 pg 1.1 iec v1 en figure 28. Communication module (com) 1mrk006501-eb 4 pg 1.1 iec v1 en figure 29. Power supply module (psm) 48-125v dc 1mrk006501-eb ...

  • Page 37

    1mrk006501-eb 6 pg 1.1 iec v1 en figure 31. Transformer module (trm) 1mrk006501-eb 7 pg 1.1 iec v1 en figure 32. Binary input/output (bio) option (terminal x321, x324) 1mrk006501-eb 8 pg 1.1 iec v1 en figure 33. Binary input/output (bio) option (terminal x326, x329) transformer protection ret650 1mr...

  • Page 38

    18. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 39

    Analog inputs table 2. Energizing inputs description value rated frequency 50/60 hz operating range rated frequency ± 5 hz current inputs rated current, i n 0.1/0.5 a 1) 1/5 a 2) thermal withstand capability: • continuously 4 a 20 a • for 1 s 100 a 500 a • for 10 s 20 a 100 a dynamic current withsta...

  • Page 40

    Auxiliary dc voltage table 3. Power supply description type 1 type 2 u aux nominal 100, 110, 120, 220, 240 v ac, 50 and 60 hz 48, 60, 110, 125 v dc 110, 125, 220, 250 v dc u aux variation 85...110% of u n (85...264 v ac) 80...120% of u n (38.4...150 v dc) 80...120% of u n (88...300 v dc) maximum loa...

  • Page 41

    Table 5. Signal output and irf output irf relay change over - type signal output relay description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 30 a breaking capacity when the control-circuit time constant l/r v dc ≤0.5 a/≤0.1 a/≤0.0...

  • Page 42

    Table 8. Ethernet interfaces ethernet interface protocol cable data transfer rate lan/hmi port (x0) 1) - cat 6 s/ftp or better 100 mbits/s lan1 (x1) tcp/ip protocol fibre-optic cable with lc connector 100 mbits/s 1) only available for the external hmi option. Table 9. Fibre-optic communication link ...

  • Page 43

    Table 14. Environmental conditions description value operating temperature range -25...+55ºc (continuous) short-time service temperature range -40...+70ºc ( note: degradation in mtbf and hmi performance outside the temperature range of -25...+55ºc relative humidity atmospheric pressure 86...106 kpa ...

  • Page 44

    Type tests according to standards table 16. Electromagnetic compatibility tests description type test value reference 100 khz and 1 mhz burst disturbance test iec 61000-4-18 iec 60255-22-1, level 3 • common mode 2.5 kv • differential mode 1.0 kv electrostatic discharge test iec 61000-4-2 iec 60255-2...

  • Page 45

    Table 16. Electromagnetic compatibility tests, continued description type test value reference power frequency immunity test • common mode • differential mode 300 v rms 150 v rms iec 60255-22-7, class a iec 61000-4-16 voltage dips and short interruptions dips: 40%/200 ms 70%/500 ms interruptions: 0-...

  • Page 46

    Table 17. Insulation tests description type test value reference dielectric tests: iec 60255-5 • test voltage 2 kv, 50 hz, 1 min 1 kv, 50 hz, 1 min, communication impulse voltage test: iec 60255-5 • test voltage 5 kv, unipolar impulses, waveform 1.2/50 μs, source energy 0.5 j 1 kv, unipolar impulses...

  • Page 47

    Emc compliance table 20. Emc compliance description reference emc directive 2004/108/ec standard en 50263 (2000) en 60255-26 (2007) transformer protection ret650 1mrk 504 127-ben - product version: 1.1 issued: february 2011 abb 47.

  • Page 48

    Differential protection table 21. Transformer differential protection t2wpdif, t3wpdif function range or value accuracy operating characteristic adaptable ± 1.0% of ir for i ± 1.0% of ir for i > ir reset ratio >94% - unrestrained differential current limit (1.00-50.00)x ibase on high voltage winding...

  • Page 49

    Table 22. Restricted earth fault protection, low impedance refpdif function range or value accuracy operate characteristic adaptable ± 1.0% of ir r for i ± 1.0% of i for i > ir reset ratio >95% - base sensitivity function (4.0-100.0)% of ibase ± 1.0% of i r directional characteristic, for zero seque...

  • Page 50

    Current protection table 24. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 35 ms typically at 2 to 0...

  • Page 51

    Table 25. Four step phase overcurrent protection oc4ptoc function setting range accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% - min. Operating current (1-10000)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r independent time ...

  • Page 52

    Table 26. Instantaneous residual overcurrent protection efpioc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 30 ms typically at 2 to 0 x i set - criti...

  • Page 53

    Table 27. Four step residual overcurrent protection ef4ptoc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate current for directional comparison (1–100)% of lbase ± 1.0% of i r min. Operating current (1-100...

  • Page 54

    Table 28. Thermal overload protection, two time constants trpttr function range or value accuracy base current 1 and 2 (30–250)% of ibase ± 1.0% of i r operate time: 2 2 2 2 ln p b i i t i i t æ ö - ç ÷ = × ç ÷ - è ø equation1356 v1 en (equation 1) i = i measured i p = load current before overload o...

  • Page 55

    Table 30. Pole discordance protection ccrpld function range or value accuracy operate value, current asymmetry level (0-100) % ± 1.0% of i r reset ratio >95% - time delay (0.000-60.000) s ± 0.5% ± 25 ms table 31. Directional over/underpower protection goppdop, guppdup function range or value accurac...

  • Page 56

    Table 32. Negative sequence based overcurrent function dnsptoc function range or value accuracy operate current (2.0 - 5000.0) % of ibase ± 1.0% of i r at i r ± 1.0% of i at i > i r reset ratio > 95 % - low voltage level for memory (0.0 - 5.0) % of ubase r relay characteristic angle (-180 - 180) deg...

  • Page 57

    Voltage protection table 33. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1–100)% of ubase ± 0.5% of u r reset ratio - inverse time characteristics for low and high step, see table 65 - see table 65 definite time delay, step 1 (0.00 - ...

  • Page 58

    Table 35. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 (1-200)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r operate voltage, step 2 (1–100)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r reset ratio >95% - inverse time cha...

  • Page 59

    Frequency protection table 37. Under frequency protection saptuf function range or value accuracy operate value, start function (35.00-75.00) hz ± 2.0 mhz operate value, restore frequency (45 - 65) hz ± 2.0 mhz operate time, start function at 50 hz: 200 ms typically at f set +0.5 hz to f set -0.5 hz...

  • Page 60

    Table 39. Rate-of-change frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ± 10.0 mhz/s operate value, restore enable frequency (45.00 - 65.00) hz ± 2.0 mhz timers (0.000 - 60.000) s operate time, start function at 50 hz: 100 ms typically ...

  • Page 61

    Control table 41. Voltage control tr8atcc, tcmyltc function range or value accuracy transformer reactance on atcc side (0.1–200.0)Ω, primary - time delay for lower command when fast step down mode is activated (1.0–100.0) s - voltage control set voltage (85.0–120.0)% of ub2 ±0.5% of u r outer voltag...

  • Page 62

    Table 41. Voltage control tr8atcc, tcmyltc, continued function range or value accuracy alarm level of reactive power in forward and reverse direction (-9999.99–9999.99) mvar ± 1.0% of s r time delay for alarms from power supervision (1–6000) s ± 0.5% ± 110 ms tap position for lowest and highest volt...

  • Page 63

    Table 43. Configurable logic blocks logic block quantity with cycle time range or value accuracy 5 ms 20 ms 100 ms and 60 60 160 - - or 60 60 160 - - xor 10 10 20 - - inverter 30 30 80 - - srmemory 10 10 20 - - rsmemory 10 10 20 - - gate 10 10 20 - - pulsetimer 10 10 20 (0.000–90000.000) s ± 0.5% ± ...

  • Page 64

    Table 45. Event counter cntggio function range or value accuracy counter value 0-10000 - max. Count up speed 10 pulses/s - transformer protection ret650 1mrk 504 127-ben - product version: 1.1 issued: february 2011 64 abb.

  • Page 65

    Table 46. Disturbance report drprdre function range or value accuracy current recording - ± 1,0% of i r at i ≤ i r ± 1,0% of i at i > ir voltage recording - ± 1,0% of u r at u ≤ u r ± 1,0% of u at u > u r pre-fault time (0.05–3.00) s - post-fault time (0.1–10.0) s - limit time (0.5–8.0) s - maximum ...

  • Page 66

    Table 47. Event list drprdre function value buffer capacity maximum number of events in the list 1000 resolution 1 ms accuracy depending on time synchronizing table 48. Indications drprdre function value buffer capacity maximum number of indications presented for single disturbance 96 maximum number...

  • Page 67

    Table 51. Disturbance recorder drprdre function value buffer capacity maximum number of analog inputs 40 maximum number of binary inputs 96 maximum number of disturbance reports 100 maximum total recording time (3.4 s recording time and maximum number of channels, typical value) 340 seconds (100 rec...

  • Page 68

    Table 55. Circuit breaker condition monitoring sscbr function range or value accuracy alarm levels for open and close travel time (0-200) ms ± 0.5% ± 25 ms alarm levels for number of operations (0 - 9999) - setting of alarm for spring charging time (0.00-60.00) s ± 0.5% ± 25 ms time delay for gas pr...

  • Page 69

    Dimensions table 60. Dimensions description value width 220 mm height 265.9 mm (6u) depth 249.5 mm weight box weight lhmi 1.3 kg (6u) inverse time characteristics table 61. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = + × - æ ö ç ÷ ç ÷ è ø p a ...

  • Page 70

    Table 62. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 - iec normal inverse a=0.14, p=0.02 iec 60255-151, class 5 + 40 ms iec very inver...

  • Page 71

    Table 64. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 unless otherwise stated class 5 +40 ms type b curve: 2.0 480 32 0.5 0.035...

  • Page 72

    Table 65. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = uv measured k = (0.05-1.10) in steps of 0.01 unless otherwise stated class 5 +40 ms type b curve: 2.0 480 0.055 32 0.5 × = + × ...

  • Page 73

    Table 66. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 class 5 +40 ms type b curve: 2.0 480 32 0.5 0.035 = × - > × - - ...

  • Page 74

    19. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the example below. Exem...

  • Page 75

    Casing #5 notes and rules rack casing, 6 u 1/2 x 19" b selection for position #5. B mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x rack mounting kit for 6 u 1/2 x 19" a wall mounting kit for 6u 1/2 x 19" d flush mounting kit for 6u 1/2 x 19" e w...

  • Page 76

    Connection type for analog modules #9 notes and rules compression terminals s ringlug terminals r analog system slot position: p2 transformer module, 6i + 4u, 1/5a, 100/220v a1 only in a05 and a07 transformer module, 8i + 2u, 1/5a, 100/220v a2 only in a01 slot position: p4 analog input module, 6i + ...

  • Page 77

    Led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals note: one (1) ied connect cd containing user documentation (operation manual, technical manual, installation manual, commissioning manual, application manual, communicati...

  • Page 78

    Reference information for our reference and statistics we would be pleased to be provided with the following application data: country: end user: station name: voltage level: kv related documents documents related to ret650 identity number application manual 1mrk 504 124-uen technical manual 1mrk 50...

  • Page 79

    79.

  • Page 80