ABB REM615 ANSI Product manual

Other manuals for REM615 ANSI: List Manual
Manual is about: Motor Protection and Control

Summary of REM615 ANSI

  • Page 1

    Relion 615 ® series motor protection and control rem615 ansi product guide.

  • Page 2

    Abb 2 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 contents disclaimer th e information in this document is subject to change without notice and should not be construed as a commitment by abb inc. Abb inc. Assumes no responsibility for any errors that may...

  • Page 3

    Abb 3 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 1. Description th e rem615 is a dedicated motor protection and control ied perfectly aligned for the protection, control, measurement and supervision of asynchronous motors in manufacturing and process in...

  • Page 4

    Abb 4 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 2. Standard confi gurations th e rem615 relay main application is protection, control, metering and monitoring of asynchronous motors and off ers two standard confi gurations whose relay functions and fea...

  • Page 5

    Abb 5 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 included = •, optional =  analog inputs 3 ct + ground ct 3 ct + ground ct + 5 vt order code aa ca protection ansi phase overcurrent, 2 elements 51p, 50p • • ground overcurrent 51g • • directional neutral...

  • Page 6

    Abb 6 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 3. Protection functions th e rem615 relay off ers all the functionality needed to manage motor starts and normal drive operations also including protection and fault clearance in abnormal situations. Th e...

  • Page 7

    Abb 7 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 4. Application the rem615 relay constitutes main protection for asynchronous motors and the associated drives. Typically, the motor relay is used with circuit-breaker or contactor-controlled distribution ...

  • Page 8

    Abb 8 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 5. Supported abb solutions abb’s 615 series protection and control ieds together with the com600 station automation device constitute a genuine iec 61850 solution for reliable power distribution in utilit...

  • Page 9

    Abb 9 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 com600 peer-to-peer goose communication peer-to-peer goose communication iec 61850-8-1 iec 61850-8-1 ethernet switch pcm600 pcm600 rem615 ref615 ret615 red615 ethernet switch ret615 red615 rem615 ref615 f...

  • Page 10

    Abb 10 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 6. Control th e relay off ers status and control of one circuit breaker with dedicated push-buttons on the front panel local human machine interface (lhmi) for opening and closing of that breaker. Flexib...

  • Page 11

    Abb 11 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 11. Circuit-breaker condition monitoring for continuous knowledge of the operational availability of the rem615 features, a comprehensive set of monitoring functions to supervise the relay health, the tr...

  • Page 12

    Abb 12 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 16. Access control to protect the ied from unauthorized access and to maintain information integrity, the ied is provided with a four-level, role-based authentication system with administrator programmab...

  • Page 13

    Abb 13 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 18. Communication th e relay supports three diff erent communication protocols: iec 61850 , dnp3.0 level 2+ and modbus®. Operational information and controls are available through these protocols. Unique...

  • Page 14

    Abb 14 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 19. Technical data table 7. Power supply description type 1 type 2 v nominal (v n ) 100, 110, 120, 220, 240 v ac, 60 and 50 hz 48, 60, 110, 125, 220, 250 v dc 24, 30, 48, 60 v dc v n variation 38...110% ...

  • Page 15

    Abb 15 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 8. Analog inputs description value rated frequency 60/50 hz ± 5 hz current inputs rated current, i n 5/1 a 1) 0.2 a 2) th ermal withstand capability: • continuously • for 1 s • for 10 s 20 a 500 a ...

  • Page 16

    Abb 16 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 12. Self-diagnostics alarm signal output (so) [typical operation time: 5...8 ms] description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carr...

  • Page 17

    Abb 17 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 16. Degree of protection of fl ush-mounted relay description value front side ip 54 back side, connection terminals ip 20 table 17. Environmental conditions description value continuous operating t...

  • Page 18

    Abb 18 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 19. Electromagnetic compatibility tests th e emc immunity test level meets the requirements listed below: description type test value reference 1 mhz burst disturbance test, class iii: • common mod...

  • Page 19

    Abb 19 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 20. Insulation tests description value dielectric tests: according to iec 60255-5 • test voltage 2 kv, 50 hz, 1 min 500 v, 50 hz, 1min, communication impulse voltage test: according to iec 60255-5 ...

  • Page 20

    Abb 20 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 23. Product safety complies with the lv directive 2006/95/ec standards en 60255-27 (2005), en 60255-6 (1994) table 25. Ethernet interfaces ethernet interface protocol cable data transfer rate front...

  • Page 21

    Abb 21 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 27. Th ree-phase non-directional overcurrent protection (50p, 51p) main settings parameter function value (range) step pickup range 51p 0.05...5.00 x i n 0.01 50p 0.10...40.00 x i n 0.01 time multi...

  • Page 22

    Abb 22 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 30.Directional ground fault protection (67/51n) characteristic value pickup accuracy depending on the frequency of the current meas- ured: f n ±2hz 67/51n current: ±1.5% of the set value or ±0.002 ...

  • Page 23

    Abb 23 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 31. Directional ground fault protection (67/51n) main settings parameter function value (range) step pickup range 67/51n 0.05...5.00 x i n 0.01 directional mode 67/51n 1=non-directional 2=forward 3...

  • Page 24

    Abb 24 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 33. Th ree-phase overvoltage protection (59) main settings parameter function value (range) step pickup range 59 0.05...1.60 x u n 0.01 time multiplier 59 0.05...15.00 0.05 defi nite time delay 59 ...

  • Page 25

    Abb 25 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 36. Positive sequence undervoltage protection (27ps) characteristic value pickup accuracy depending on the frequency of the voltage measured: fn ±2hz ±1.5% of the set value or ±0.002 x u n pickup t...

  • Page 26

    Abb 26 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 39. Negative sequence overvoltage protection (47) main settings parameter function value (range) step pickup range 47 0.010...1.000 x u n 0.001 defi nite time delay 47 40...120000 ms 1 table 42. Ne...

  • Page 27

    Abb 27 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 44. Loss of load supervision (37) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2hz ±1.5% of the set value or ±0.002 x i n start time typical 300 ...

  • Page 28

    Abb 28 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 47. Phase reversal protection (46r) main settings parameter function value (range) step start value 46r 0.05...1.00 x i n 0.01 operate delay time 46r 100...60000 ms 10 operation 46r off on - table ...

  • Page 29

    Abb 29 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 52. Th ermal overload protection for motors (49m) main settings parameter function value (range) step env temperature mode 49m flc only use rtd set amb temp - env temperature set 49m -20.0...70.0 °...

  • Page 30

    Abb 30 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 measurement functions table 58. Th ree-phase current measurements (ia, ib, ic) characteristic value pickup accuracy depending on the frequency of the current measured: fn ±2hz ±0.5% or ±0.002 x in (at cu...

  • Page 31

    Abb 31 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 table 60. Th ree-phase voltage measurements (va, vb, vc) characteristic value pickup accuracy depending on the frequency of the voltage measured: fn ±2hz (at voltages in range 0.01...1.15 x un) ±0.5% or ...

  • Page 32

    Abb 32 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 table 68. Motor run time counter (optm) description value motor run-time measurement accuracy1) ±0.5% supervision functions table 65. Current circuit supervision (ccm) characteristic value trip time 1) 1...

  • Page 33

    Abb 33 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 20. Display the relay’s local hmi includes a large lcd screen standard. Th e large lcd display off ers full front-panel user-interface functionality with menu navigation and menu views. Th e large displa...

  • Page 34

    Abb 34 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 fig. 7: flush mounting fig. 8: semi-fl ush mounting fig. 9: semi-fl ush with a 25º tilt 21. Mounting methods by means of appropriate mounting accessories the standard relay case for the 615 series relays c...

  • Page 35

    Abb 35 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 23. Selection and ordering data the relay type and serial number label identifies t h e p r o t e c t i o n r e l a y. T h e l a b e l i s p l a c e d above the hmi on the upper part of the draw- out uni...

  • Page 36

    Abb 36 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 24. Accessories and ordering data table 70. Accessories and ordering data. Item order number tools pcm600 v2.0 user tool pcm600-20 cables cable for optical sensors for arc protection 1.5 m 1mrs120534-1.5...

  • Page 37

    Abb 37 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 25. Tools th e relay is delivered as a pre-confi gured unit. Th e default parameter setting values can be changed from the front- panel user interface, the web-browser based user interface (whmi) or the ...

  • Page 38

    Abb 38 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 26. Terminal diagrams 16 15 19 18 10 11 12 13 14 22 23 24 so2 tcm-2 po4 so1 tcm-1 po3 17 21 20 x120 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ig ia ib bi 4 bi 3 bi 2 bi 1 ic rem615 ansi a b c s 1 s 2 p1 p 2 52 b ...

  • Page 39

    Abb 39 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 16 15 19 18 10 11 12 13 14 22 23 24 so2 tcm-2 po4 so1 tcm-1 po3 17 21 20 x120 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ig ia ib bi 4 bi 3 bi 2 bi 1 ic x130 1 2 5 6 7 8 9 10 vb va bi 4 bi 3 bi 1 vg vc 12 13 11 re...

  • Page 40

    Abb 40 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 27. Certifi cates 28. References kema has issued an iec 61850 certifi cate level a1 for ref615. Certifi cate number: 30710144-consulting 08-0115 th e rem615 is a ul listed product per ul file e103204 for...

  • Page 41

    Abb 41 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 29. Functions, codes and symbols table 72. Rem615 functions, codes and symbols function iec 61850 ansi c37.2-2008 protection th ree-phase non-directional time overcurrent phlptoc 51p th ree-phase non-dir...

  • Page 42

    Abb 42 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 function iec 61850 ansi c37.2-2008 measurement digital fault recorder (dfr) rdre1 dfr th ree-phase currents cmmxu1 ia, ib, ic sequence currents csmsqi1 i 1 , i 2 , i 0 ground current rescmmxu1 ig th ree-...

  • Page 43

    Abb 43 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010 30. Document revision history table 73. Document revision history a/ march 01, 2010 v2.0 initial product version release.

  • Page 44

    Abb 44 1mac251744 -pg rev. A issued: 03.01.2010 motor protection rem615 ansi product version 2.0 31. Notes.

  • Page 45

    Abb 45 motor protection rem615 ansi product version 2.0 1mac251744 -pg rev. A issued: 03.01.2010

  • Page 46

    Contact us 1mac251744 -pg rev . A mar ch 2010 abb inc. Distribution automation 4300 coral ridge drive coral springs, florida 33065 phone: +1 954-752-6700 fax: +1 954-345-5329 www.Abb.Com/substationautomation all sales are subject to abb inc. General terms and conditions of sale. While every effort h...