ABB RER620 Product Manual - page 40
40
R E R6 20 A DVA NCED R ECLOSER PROTEC TION & CONTROL
29. Certificates
All type test certificates are available upon request.
30. References
The download area on the right hand side of the
web page (www.abb.com/substationautomation)
contains the latest product documentation, such as
technical Reference manual, installation manual,
operators manual, etc. The selection tool on the
web page helps you find the documents by the doc-
ument category and language.
The Features and Application tabs contain product
related information in a compact format.
The www.abb.com/substationautomation portal
offers you information about the distribution auto-
mation product and service range.
You will find the latest relevant information on the
RER620 protection relay on the product page.
—
Table 57. RER620 1.1 Function List
Function name
Configuration
IEC61850
IEC60617
ANSI/C37.2 Description
RA01 and RA02
Current protection
SPHLPTOC1
3I>(1)
51P
Three-phase non-directional time overcurrent protection with
1-ph trip option, low stage
Y
SPHLPTOC2
3I>(2)
50P-1
Three-phase non-directional time overcurrent protection with
1-ph trip option, high stage 1
Y
SPHHPTOC1
3I>>(1)
50P-2
Three-phase non-directional time overcurrent protection with
1-ph trip option, high stage 2
Y
SPHIPTOC1
3I>>>(1)
50P-3
Three-phase non-directional instantneous overcurrent
protection with 1-ph trip option
Y
XEFLPTOC2
Io>(2)
51N
Non-directional time overcurrent ground-fault protection, low
stage
Y
XEFLPTOC3
Io>(3)
50N-1
Non-directional time overcurrent ground-fault protection, high
stage 1
Y
XEFHPTOC3
Io>>(3)
50N-2
Non-directional time overcurrent ground-fault protection, high
stage 2
Y
XEFIPTOC2
Io>>>(2)
50N-3
Non-directional instantaneous time overcurrent ground-fault
protection
Y
EFLPTOC3
Io>(3)
50SEF
Non-directional sensitive earth-fault
Y
XNSPTOC1
I2 >(1)
46-1
Negative sequence non-directional time overcurrent protection 1 Y
XNSPTOC2
I2 >(2)
46-2
Negative sequence non-directional time overcurrent protection 2 Y
PDNSPTOC1
I2/I1>
46PD
Phase discontinuity protection
Y
INPHAR
3I2f >
INR
Three-phase inrush detector
Y
SDPHLPDOC1
3I >->(1)
67/51P-1
Three-phase directional overcurrent protection, low stage 1
Y
SDPHLPDOC2
3I >->(2)
67/51P-2
Three-phase directional overcurrent protection, low stage 2
Y
XDEFLPDEF1
Io>->(1)
67/51N-1
Directional ground-fault protection, low stage 1
Y
XDEFLPDEF2
Io>->(1)
67/51N-2
Directional ground-fault protection, low stage 2
Y
SDPHLPDOC1
3I >->(1)
67/51P-1
Three-phase directional overcurrent protection, low stage 1
Y
SDPHLPDOC2
3I >->(2)
67/51P-2
Three-phase directional overcurrent protection, low stage 2
Y
XDEFLPDEF1
Io>->(1)
67/51N-1
Directional ground-fault protection, low stage 1
Y
XDEFLPDEF2
Io>->(1)
67/51N-2
Directional ground-fault protection, low stage 2
Y
Total current protection functions included
17
Cold load timers
TPSGAPC1
TPS(1)
62CLD-1
Cold load timer 1 Phase A (in seconds)
Y
TPMGAPC1
TPM(1)
62CLD-2
Cold load timer 2 Phase A (in minutes)
Y
TPSGAPC2
TPS(2)
62CLD-3
Cold load timer 1 Phase B (in seconds)
Y
TPMGAPC2
TPM(2)
62CLD-4
Cold load timer 2 Phase B (in minutes)
Y
TPSGAPC3
TPS(3)
62CLD-5
Cold load timer 1 Phase C (in seconds)
Y
TPMGAPC3
TPM(3)
62CLD-6
Cold load timer 2 Phase C (in minutes)
Y
Total cold load timers
6
31. Functions, codes, and symbols