ABB REU615 Product Manual

Manual is about: Modbus Point List

Summary of REU615

  • Page 1

    Relion ® 615 series voltage protection and control reu615 product guide.

  • Page 2

    Contents 1. Description.....................................................................3 2. Standard configurations.................................................3 3. Protection functions........................................................6 4. Application.....................................

  • Page 3

    1. Description the voltage protection and control ied, reu615 is available in two standard configurations, denoted a and b. Configuration a is preadapted for voltage and frequency-based protection schemes in utility and industrial power systems and distribution systems including networks with distri...

  • Page 4

    Table 2. Supported functions functionality a b protection 1) three-phase non-directional overcurrent protection, low stage, instance 1 - ● three-phase non-directional overcurrent protection, high stage, instance 1 - ● three-phase non-directional overcurrent protection, instantaneous stage, instance ...

  • Page 5

    Table 2. Supported functions, continued functionality a b multi-purpose protection, instance 6 4) - o 5) load shedding and restoration, instance 1 ● - load shedding and restoration, instance 2 ● - load shedding and restoration, instance 3 ● - load shedding and restoration, instance 4 ● - load sheddi...

  • Page 6

    Table 2. Supported functions, continued functionality a b rtd/ma measurement - o frequency measurement ● - ● = included, o = optional at the time of order 1) the instances of a protection function represent the number of identical function blocks available in a standard configuration. By setting the...

  • Page 7

    And the timers of the protection function can be set to operate when the input values are below or exceeds the set values. Guid-5e258df3-b410-4fee-9925-a8fc9c3617ce v2 en figure 1. Protection function overview of standard configuration a voltage protection and control 1mrs757058 d reu615 product ver...

  • Page 8

    Guid-dca293f5-58d2-4ce8-9602-842a6498f9ed v2 en figure 2. Protection function overview of standard configuration b 4. Application standard configuration a the a configuration of reu615 is intended to be used in medium voltage switchgear, supplied with a dedicated voltage measurement cubicle. The a c...

  • Page 9

    Guid-ca7b4d3e-1269-450f-a061-5a404ff52455 v2 en figure 3. Busbar protection and supervision using reu615 with the standard configuration a. The arc protection schemes of reu615 and ref615 are employed for busbar protection for the voltage measurement bay and related parts of the busbar. Apart from t...

  • Page 10

    Guid-a90b4035-68b9-4264-83c5-dd791ddedab0 v2 en figure 4. Tap changer control and power transformer thermal overload protection using reu615 with the standard configuration b. The tap changer position information is received as a ma-signal from the tap changer operation mechanism. The position value...

  • Page 11

    Diagrams, thus enabling convenient information accessibility. To enhance personnel safety, the web hmi also enables remote access to substation devices and processes. Furthermore, com600 can be used as a local data warehouse for technical documentation of the substation and for network data collecte...

  • Page 12

    Guid-6984d893-45d5-427a-babf-f1e1015c18e2 v3 en figure 6. Industrial power system example using 615 series ieds, grid automation controller com600 and system 800xa 6. Control the ied offers control of one circuit breaker with dedicated push-buttons for circuit breaker opening and closing. Further, t...

  • Page 13

    Remotely using the web-browser based user interface. 8. Disturbance recorder the ied is provided with a disturbance recorder featuring up to 12 analog and 64 binary signal channels. The analog channels can be set to record either the waveform or the trend of the currents and voltage measured. The an...

  • Page 14

    15. Current circuit supervision current circuit supervision is used for detecting faults in the current transformer secondary circuits. On detecting of a fault the current circuit supervision function activates an alarm led and blocks certain protection functions to avoid unintended operation. The c...

  • Page 15

    18. Station communication the ied supports a range of communication protocols including iec 61850, iec 60870-5-103, modbus ® and dnp3. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between ...

  • Page 16

    Connections are supported. Termination and pull- up/down resistors can be configured with jumpers on the communication card so external resistors are not needed. The ied supports the following time synchronization methods with a time-stamping resolution of 1 ms: ethernet-based: • sntp (simple networ...

  • Page 17

    Table 5. Supported station communication interfaces and protocols interfaces/protocols ethernet serial 100base-tx rj-45 100base-fx lc rs-232/rs-485 fibre-optic st iec 61850 ● ● - - modbus rtu/ascii - - ● ● modbus tcp/ip ● ● - - dnp3 (serial) - - ● ● dnp3 tcp/ip ● ● - - iec 60870-5-103 - - ● ● ● = su...

  • Page 18

    19. Technical data table 6. Dimensions description value width frame 177 mm case 164 mm height frame 177 mm (4u) case 160 mm depth 201 mm (153 + 48 mm) weight complete ied 4.1 kg plug-in unit only 2.1 kg table 7. Power supply description type 1 type 2 u aux nominal 100, 110, 120, 220, 240 v ac, 50 a...

  • Page 19

    Table 8. Energizing inputs description value rated frequency 50/60 hz ± 5 hz current inputs rated current, i n 1/5 a 1) thermal withstand capability: • continuously 20 a • for 1 s 500 a dynamic current withstand: • half-wave value 1250 a input impedance voltage inputs rated voltage 60...210 v ac vol...

  • Page 20

    Table 10. Rtd/ma measurement (xrggio130) description value rtd inputs supported rtd sensors 100 Ω platinum 250 Ω platinum 100 Ω nickel 120 Ω nickel 250 Ω nickel 10 Ω copper tcr 0.00385 (din 43760) tcr 0.00385 tcr 0.00618 (din 43760) tcr 0.00618 tcr 0.00618 tcr 0.00427 supported resistance range 0......

  • Page 21

    Table 12. Signal outputs and irf output description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 15 a breaking capacity when the control-circuit time constant l/ r 1 a/0.25 a/0.15 a minimum contact load 10 ma at 5 v ac/dc table 13. D...

  • Page 22

    Table 16. Station communication link, fibre-optic connector fibre type 1) wave length max. Distance permitted path attenuation 2) lc mm 62.5/125 or 50/125 μm glass fibre core 1300 nm 2 km st mm 62.5/125 or 50/125 μm glass fibre core 820-900 nm 1 km 1) (mm) multi-mode fibre, (sm) single-mode fibre 2)...

  • Page 23

    Table 21. Environmental tests description type test value reference dry heat test • 96 h at +55ºc • 16 h at +85ºc 1) iec 60068-2-2 dry cold test • 96 h at -25ºc • 16 h at -40ºc iec 60068-2-1 damp heat test • 6 cycles (12 h + 12 h) at +25°c… +55°c, humidity >93% iec 60068-2-30 change of temperature t...

  • Page 24

    Table 22. Electromagnetic compatibility tests description type test value reference 1 mhz/100 khz burst disturbance test: iec 61000-4-18 iec 60255-22-1, class iii ieee c37.90.1-2002 • common mode 2.5 kv • differential mode 2.5 kv 3 mhz, 10 mhz and 30 mhz burst disturbance test: iec 61000-4-18 iec 60...

  • Page 25

    Table 22. Electromagnetic compatibility tests, continued description type test value reference voltage dips and short interruptions: 30%/10 ms 60%/100 ms 60%/1000 ms >95%/5000 ms iec 61000-4-11 power frequency immunity test: • common mode • differential mode binary inputs only 300 v rms 150 v rms ie...

  • Page 26

    Table 25. Product safety description reference lv directive 2006/95/ec standard en 60255-27 (2005) en 60255-1 (2009) table 26. Emc compliance description reference emc directive 2004/108/ec standard en 50263 (2000) en 60255-26 (2007) table 27. Rohs compliance description complies with rohs directive...

  • Page 27

    Protection functions table 28. Three-phase non-directional overcurrent protection (phxptoc) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz phlptoc ±1.5% of the set value or ±0.002 x i n phhptoc and phiptoc ±1.5% of set value or ±0.002 x i n (at ...

  • Page 28

    Table 29. Three-phase non-directional overcurrent protection (phxptoc) main settings parameter function value (range) step start value phlptoc 0.05...5.00 x i n 0.01 phhptoc 0.10...40.00 x i n 0.01 phiptoc 1.00...40.00 x i n 0.01 time multiplier phlptoc 0.05...15.00 0.01 phhptoc 0.05...15.00 0.01 op...

  • Page 29

    Table 31. Three-phase overvoltage protection (phptov) main settings parameter function value (range) step start value phptov 0.05...1.60 x u n 0.01 time multiplier phptov 0.05...15.00 0.01 operate delay time phptov 40...300000 ms 10 operating curve type 1) phptov definite or inverse time curve type:...

  • Page 30

    Table 34. Positive-sequence undervoltage protection (psptuv) characteristic value operation accuracy depending on the frequency of the voltage measured: f n ±2 hz ±1.5% of the set value or ±0.002 x u n start time 1)2) minimum typical maximum u fault = 0.99 x set start value u fault = 0.9 x set start...

  • Page 31

    Table 37. Negative-sequence overvoltage protection (nsptov) main settings parameter function value (range) step start value nsptov 0.010...1.000 x u n 0.001 operate delay time nsptov 40...120000 ms 1 table 38. Frequency protection (frpfrq) characteristic value operation accuracy f>/f ±10 mhz df/dt ±...

  • Page 32

    Table 40. Thermal overload protection, two time constants (t2pttr) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz current measurement: ±1.5% of the set value or ±0.002 x i n (at currents in the range of 0.01...4.00 x i n ) operate time accuracy ...

  • Page 33

    Table 43. Residual overvoltage protection (rovptov) main settings parameter function value (range) step start value rovptov 0.010...1.000 x u n 0.001 operate delay time rovptov 40...300000 ms 1 table 44. Arc protection (arcsarc) characteristic value operation accuracy ±3% of the set value or ±0.01 x...

  • Page 35

    Table 50. Operation characteristics parameter values (range) operating curve type 1=ansi ext. Inv. 2=ansi very. Inv. 3=ansi norm. Inv. 4=ansi mod inv. 5=ansi def. Time 6=l.T.E. Inv. 7=l.T.V. Inv. 8=l.T. Inv. 9=iec norm. Inv. 10=iec very inv. 11=iec inv. 12=iec ext. Inv. 13=iec s.T. Inv. 14=iec l.T. ...

  • Page 36

    Control functions table 51. Synchrocheck (secrsyn) characteristic value operation accuracy depending on the frequency of the voltage measured: f n ±1 hz voltage: ±3.0% of the set value or ±0.01 x u n frequency: ±10 mhz phase angle: ±3° reset time reset ratio typical 0.96 operate time accuracy in def...

  • Page 37

    Table 52. Synchronism and energizing check (secrsyn) main settings parameter values (range) unit step default description live dead mode -1=off 1=both dead 2=live l, dead b 3=dead l, live b 4=dead bus, l any 5=dead l, bus any 6=one live, dead 7=not both live 1=both dead energizing check mode differe...

  • Page 38

    Table 52. Synchronism and energizing check (secrsyn) main settings, continued parameter values (range) unit step default description maximum syn time 100...6000000 ms 10 2000 maximum time to accept synchronizing energizing time 100...60000 ms 10 100 time delay for energizing check closing time of cb...

  • Page 39

    Table 54. On-load tap changer control with voltage regulator (olatcc) main settings parameter function value (range) step band center voltage olatcc 0.000...2.000 x un 0.001 control delay time 1 olatcc 1000...300000 ms 100 control delay time 2 olatcc 1000...300000 ms 100 line drop v ris olatcc 0.0.....

  • Page 40

    Measurement functions table 55. Three-phase current measurement (cmmxu) characteristic value operation accuracy depending on the frequency of the current measured: f n ±2 hz ±0.5% or ±0.002 x i n (at currents in the range of 0.01...4.00 x i n ) suppression of harmonics dft: -50 db at f = n x f n , w...

  • Page 42

    Supervision functions table 62. Current circuit supervision (ccrdif) characteristic value operate time 1) 1) including the delay of the output contact. Table 63. Current circuit supervision (ccrdif) main settings parameter values (range) unit description start value 0.05...0.20 x i n minimum operate...

  • Page 43

    20. Local hmi the ied is available with two optional displays, a large one and a small one. The large display is suited for ied installations where the front panel user interface is frequently used and a single line diagram is required. The small display is suited for remotely controlled substations...

  • Page 44

    Table 66. Large display character size 1) rows in the view characters per row small, mono-spaced (6x12 pixels) 10 20 large, variable width (13x14 pixels) 8 8 or more 1) depending on the selected language 21. Mounting methods by means of appropriate mounting accessories the standard ied case for the ...

  • Page 45

    22. Ied case and ied plug-in unit for safety reasons, the ied cases for current measuring ieds are provided with automatically operating contacts for short-circuiting the ct secondary circuits when a ied unit is withdrawn from its case. The ied case is further provided with a mechanical coding syste...

  • Page 46

    # description 9 - 10 communication modules (serial/ethernet) serial rs-485, incl. An input for irig-b + ethernet 100base-fx (1 x lc) aa serial rs-485, incl. An input for irig-b + ethernet 100base-tx (1 x rj-45) ab serial rs-485, incl. An input for irig-b an serial glass fibre (st), incl. An rs-485 c...

  • Page 47

    # description 12 language english 1 english and german 3 english and swedish 4 english and spanish 5 english and russian 6 english and polish 7 english and portuguese (brazilian) 8 english and italian a english and french c english and czech e 13 front panel small lcd a large lcd with single line di...

  • Page 48

    24. Accessories and ordering data table 67. Cables item order number cable for optical sensors for arc protection 1.5 m 1mrs120534-1.5 cable for optical sensors for arc protection 3.0 m 1mrs120534-3.0 cable for optical sensors for arc protection 5.0 m 1mrs120534-5.0 table 68. Mounting accessories it...

  • Page 49

    25. Tools the ied is delivered as a pre-configured unit. The default parameter setting values can be changed from the front-panel user interface, the web- browser based user interface (webhmi) or the pcm600 tool in combination with the ied-specific connectivity package. The protection and control ie...

  • Page 50

    Table 70. Supported functions function webhmi pcm600 basic/ engineering pcm600 engineering pro ied parameter setting ● ● ● saving of ied parameter settings in the ied ● ● ● signal monitoring ● ● ● disturbance recorder handling ● ● ● alarm led viewing ● ● ● access control management ● ● ● ied signal ...

  • Page 51

    26. Terminal diagrams guid-b89bfff3-08f0-40d3-8f12-99fb21b3900f v1 en figure 14. Terminal diagram of standard configuration a voltage protection and control 1mrs757058 d reu615 product version: 4.0 abb 51.

  • Page 52

    Guid-e5fa44b9-524f-4b19-a002-49d39df6d6d5 v1 en figure 15. Terminal diagram of standard configuration b voltage protection and control 1mrs757058 d reu615 product version: 4.0 52 abb.

  • Page 53

    27. References the www.Abb.Com/substationautomation portal offers you information about the distribution automation product and service range. You will find the latest relevant information on the reu615 protection ied on the product page . The download area on the right hand side of the web page con...

  • Page 54

    28. Functions, codes and symbols table 71. Reu615 functions, codes and symbols function iec 61850 iec 60617 iec-ansi protection three-phase non-directional overcurrent protection, low stage phlptoc1 3i> (1) 51p-1 (1) three-phase non-directional overcurrent protection, high stage phhptoc1 3i>> (1) 51...

  • Page 55

    Table 71. Reu615 functions, codes and symbols, continued function iec 61850 iec 60617 iec-ansi multi-purpose protection mapgapc1 map (1) map (1) mapgapc2 map (2) map (2) mapgapc3 map (3) map (3) mapgapc4 map (4) map (4) mapgapc5 map (5) map (5) mapgapc6 map (6) map (6) load shedding and restoration ...

  • Page 56

    Table 71. Reu615 functions, codes and symbols, continued function iec 61850 iec 60617 iec-ansi residual voltage measurement resvmmxu1 uo vn sequence voltage measurement vsmsqi1 u1, u2, u0 u1, u2, u0 three-phase power and energy measurement pemmxu1 p, e p, e rtd/ma measurement xrggio130 x130 (rtd) x1...

  • Page 57

    57.

  • Page 60

    Contact us abb oy distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/substationautomation 1mrs757058 d © copyright 2012 abb. All rights reserved..