- DL manuals
- ABB
- Adapter
- SPA-ZC 400
- Installation And Commissioning Manual
ABB SPA-ZC 400 Installation And Commissioning Manual
Summary of SPA-ZC 400
Page 1
Ethernet adapter spa-zc 400 modbus/tcp brigde installation and commissioning manual.
Page 3
3 contents copyrights ................................................................................. 5 1. Introduction.... ................................................................ ..... 7 1.1. This manual.................................................................... ...... 7 1.2. Us...
Page 4
7.1. Interfaces.... .................................................................... .... 37 7.2. Test and conditions.... .................................................... .... 38 8. Maintenance and service................................................. 41 8.1. Led indicators.... .............
Page 5
5 copyrights the information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may appear in this document. In no event shall abb oy be liable for direct, indirect, special, incidental or c...
Page 6
6.
Page 7
7 1. Introduction 1.1. This manual this manual provides thorough information on the spa-zc 400 ethernet adapter and the central concepts related to it. Spa-zc 400 ethernet adapter is used for connecting ref 541/3/5, rem 543/5 and ret 541/3/5 intelligent electronic devices (ied) to the modbus/tcp bri...
Page 8
1.4. Product documentation name of the manual document id spa-zc 400 configuration cd 1mrs151048 cap 505 user's guide 1mrs752292-mum spa-zf optical glass fibres, multimode granded index type 1mrs755371 plastic-core fibre-optic cables, features and instructions for mounting 1mrs752089 1.5. Document c...
Page 9
9 example: mif349 * variables are shown using lowercase letters: sequence name 1.6. Revision history version date history a 30.06.2006 document created 1mrs756014 ethernet adapter modbus/tcp brigde installation and commissioning manual spa-zc 400
Page 10
10
Page 11
11 2. Safety information non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed. The device contains components whic...
Page 12
12.
Page 13
13 3. Product overview spa-zc 400 is used to connect one ref 541/3/5, rem 543/5 or ret 541/3/5 device with the modbus protocol over the tcp/ip network using the same ethernet link. Spa-zc400mmp and spa-zc400mmg versions provide simultaneous dual port communication for fibre-optic spa and lon. 3rd pa...
Page 14
Media converters: * ruggedcom rmc-100-mm * imc mcbasic mm1300 * allied telesyn at-mc302-20 more tested devices can be found on the abb web site (http://www.Abb.Com/substationautomation). 3.1. Spa-zc400mmp and spa-zc400mmg the optional interface provides a connection between the ref 541/3/5, rem 543/...
Page 15
15 3.2. Features spa-zc 400 has the following features: * simultaneous dual port communication (spa-zc400mmp and spa- zc400mmg versions) for modbus and lon/spa (excluding event polling) * support of modbus communication over tcp/ip 1 4 3 2 5 a040138b fig. 3.2.-1 parts of spa-zc 400 1 ethernet connec...
Page 16
A data message sent as a tcp/ip message means that the higher layer transmission control protocol assembles the message or file into smaller packets. These are then transmitted over the internet and received by a tcp layer which reassembles the packets into the original message. 16 spa-zc 400 ethern...
Page 17
17 4. Installation this chapter describes the installation of the spa-zc 400 module and the communication engineering tool (cet) for spa-zc 40x. For additional information, such as technical data, maintenance and service, refer to section 7. Technical data and section 8. Maintenance and service. 4.1...
Page 18
5. The cet for spa-zc 40x installation program starts. In this dialog, click next. * with the back button you can return to the previous dialog, and with the cancel button, exit the installation wizard. This applies to all the dialogs in the installation wizard. 6. Read the license agreement, select...
Page 19
19 uninstall cet for spa-zc 40xin order to install a new version and to update the software. Uninstallation does not remove the microsoft sql server and .Net framework. Removing these programs can affect the functionality of the other abb applications. Detailed instructions for upgrading the softwar...
Page 20
A060241 fig. 4.3.1.-1 changing ip address 4.3.2. Checking connection to spa-zc 400 check the connection to spa-zc 400 by using the ping command: 1. Open the run dialog. 2. Type cmd to the open box, see fig. 4.3.2.-1. A060242 fig. 4.3.2.-1 starting command prompt 3. Click ok to run the command prompt...
Page 21
21 4. Type ping 192.168.2.10, see fig. 4.3.2.-2. Fig. 4.3.2.-2 pinging spa-zc 400 spa-zc 400 responds to the ping command if the computer and spa-zc 400 are on the same network. 5. If spa-zc 400 responds with the ip address, the connection is established between the computer and spa-zc 400. 1mrs7560...
Page 22
22.
Page 23
23 5. Engineering this section guides when performing the engineering tasks required before using spa-zc 400. Note that all the possible engineering scenarios are not included in this manual. You must have engineering rights to be able to perform the tasks described in this section. 5.1. Overview of...
Page 24
A040013b fig. 5.2.-1 opening a project a040014b fig. 5.2.-2 creating a new project 5.3. Restarting use this function to restart the spa-zc 400 at runtime. 1. Select ied and tools > reset tool to open the restart pane, see fig. 5.3.-1 2. Click reset. The results are reported to the ui text box. Do no...
Page 25
25 a060396 fig. 5.3.-1 restarting 5.4. Building object tree after creating the project you need to build and configure an object tree in the communication engineering tool (cet) for spa-zc 40x to define the communication structure. Fig. 5.4.-1 shows an example of the object tree when it has been bui...
Page 26
A051858 fig. 5.4.-1 example view of the spa-zc 40x communication engineering tool you have several possible ways to add objects to the object tree in the communication structure: * you can use the right mouse button (right-click) to select the object to which you want to add a child object. * you ca...
Page 27
27 5.4.1. Adding device object to build the object tree: 1. Add a spazc40x_modbus device object in the communication structure by selecting the project name. In the example the project protocol test is selected. 2. Right-click protocol test 3. Select new > tunneling > spazc40x_modbus, see fig. 5.4.1...
Page 28
Create a new project and add a spazc40x_modbus device. Select the cid import function by right-clicking the ld1 logical device. In the cid import dialog you can select the right cid file from the workstation directory and import it to a previously created logical device. 5.6. Configuring communicati...
Page 29
29 * default gateway the ip address default gateway defines the gateway address that forwards the ip traffic between the local subnet and the outside world. The default ip address is 192.168.2.1 and this has to be changed according to the planned network structure. * ip address the ip address identi...
Page 30
5.6.2. Communication parameters for modbus a051854 fig. 5.6.2.-1 modbus communication parameters * baud rate the possible communication speed settings of the modbus bus are: * 1200 bps * 2400 bps * 4800 bps * 9600 bps * 19200 bps * 38400 bps * receive timeout receive timeout defines how long spa-zc ...
Page 31
31 * retransmissions retransmissions defines how many times a message is resent after connection is considered to be temporarily broken. * modbus-timesynch if enabled, spa-zc 400 sends time synchronization messages to the relay. If spa-zc 400 is not connected to a sntp server, time synchronization t...
Page 32
A051856 fig. 5.7.-1 downloading the device's configuration if spa-zc 400 is connected to a system where the connection to it can be obtained, the export function tries to determine the spa-zc 400 version and exports the export file accordingly. If the connection is disabled, prompt the correct versi...
Page 33
33 you can export a configuration in cid format from cid export tool to hard drive. This scl is usually used by system configuration tool. It is possible to export a dataset in scl files in different levels. If you select to export a dataset in fcd level, for example an information report from spa-z...
Page 34
34.
Page 35
35 6. Commissioning the downloaded cid file is taken into use when spa-zc 400 is restarted automatically . Normally, the device is reset automatically after the configuration is downloaded with communication engineering tool (cet) for spa-zc 40x. After downloading the configuration you can check the...
Page 36
36.
Page 37
37 7. Technical data 7.1. Interfaces spa-zc 400 - ied interfaces * fixed mechanics and fixed connectors for ref 541/3/5, rem 543/5 and ret 541/3/5 protection relays * d-type subminiature connector for simultaneous dual port communication (optional, see table 3.1.-1). Lon/spa interface (optional) * f...
Page 38
Lon/spa diagnostic led * rx dimensions and weight 43 195 ip 00-0c-02-b0-cc-00 50 20.4 26 spa-zc 400 ethernet adapter power link tx rx diag lan service pin ethernet rx tx plastic glass iec 61850 modbus / tcp spa / tcp a040130b fig. 7.1.-1 dimensions of the spa-zc 400 module table 7.1.-1 dimensions an...
Page 39
39 table 7.2.- 1 envi ronmen tal test and cond itions recommended service temperature range (continuous) -10...+55 ˚c transport and storage temperature range -40...+70 ˚c according to the iec 60068-2- 48 dry heat test according to the iec 60068-2-2 dry cold test according to the iec iec 60068-2-1 da...
Page 40
Table 7.2.-4 standard tests supply current consumption running 340 ma start up 430 ma 40 spa-zc 400 ethernet adapter modbus/tcp brigde installation and commissioning manual 1mrs756014.
Page 41
41 8. Maintenance and service if the spa-zc 400 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to table 9.-1. 8.1. Led indicators table 8.1.-1 led indicators led color state sequence number description power green o...
Page 42
The following ied-specific settings have to be checked when setting up ref 541/3/5, rem 543/5 or ret 541/3/5: * protocol selection for spa-zc 400 table 8.2.-1 explains the possible port configurations of ref 541/3/5, rem 543/5 or ret 541/3/5. The protocol selection is active only after rebooting the...
Page 43
43 only one spa client can be configured to poll spa events from the device. By default spa-zc 400 is configured to poll spa events. In this case, it is not allowed to poll spa events from another spa client. * spa command timeout in ied spa command timeout should be use. * spa baud rate and spa sla...
Page 44
A060128 fig. 8.3.-2 selecting network adapter 3. Click start to start the query. 4. Click stop to stop the query. Connected devices are displayed in the output pane, fig. 8.3.-2. Additional information depends on the spa-zc 40x version. If version 1.1.1 is used, only mac address is displayed. If ver...
Page 45
45 the version information can be read from the device's label. If the device is updated afterwards, use cet's ip query to get the correct version information from the device memory. For more information about ip query, refer to section 8.3. Ip query. 8.5. Obtaining error logs the following session ...
Page 46
46.
Page 47
47 9. Ordering information spa-zc400mmg ethernet connector type m = mtrj l = lc r = rj-45 protocol type m = modbus/tcp e = iec 61850 s = spa/tcp device type optical transmitter and receiver for spa/lon bus p = plastic fibre cable g = glass fibre cable - = no fibre option a060158 fig. 9.-1 ordering i...
Page 48
48.
Page 49
49 10. Terminology term description communication engineering tool also known as cet. Software for configuring and monitoring communication gateways or communica- tion front ends. Intelligent electronic device also known as ied. Devices containing advanced logics such as meters, protection and contr...
Page 50
50
Page 51
51 11. Abbreviations abbreviation description cet communication engineering tool cid configured ied description emc electromagnetic compatibility icd ied capability description ied intelligent electronic device ip internet protocol lan local area network ld logical device led light-emitting diode ln...
Page 56
Abb oy distribution automation p.O. Box 699 fi-65101 vaasa finland +358 10 2211 +358 10 224 1080 www.Abb.Com/substationautomation 1mrs75601 4 e n 6 /2006.