ABB SPA-ZC 402 Installation And Commissioning Manual

Manual is about: spa/ethernet adapter SPA to IEC 61850 Gateway

Summary of SPA-ZC 402

  • Page 1

    Ethernet adapter spa-zc 402 spa-zc 402 spa/tcp bridge installation and commissioning manual.

  • Page 3

    3 contents copyrights ................................................................................. 5 1. Introduction ..............................................................7 1.1. This manual .............................................................. 7 1.2. Use of symbols ...............

  • Page 4

    7. Technical data ........................................................ 35 7.1. Interfaces ............................................................... 35 7.2. Test and conditions .................................................. 36 8. Maintenance and service ....................................

  • Page 5

    5 copyrights the information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may appear in this document. In no event shall abb oy be liable for direct, indirect, special, incidental or c...

  • Page 6

    6.

  • Page 7

    7 1. Introduction 1.1. This manual this manual provides thorough information on the spa-zc 402 ethernet adapter and the central concepts related to it. Spa-zc 402 ethernet is used for connecting any intelligent electronic devices (ied), which provides fibre-optic spa bus, to the spa/tcp bridge. In t...

  • Page 8

    1.4. Product documentation name of the manual document id spa-zc 402 configuration cd 1mrs151049 cap 505 user's guide 1mrs752292-mum spa-zf optical glass fibres, multimode granded index type 1mrs755371 plastic-core fibre-optic cables, features and instructions for mounting 1mrs752089 1.5. Document c...

  • Page 9

    9 1.6. Revision history version date history a 30.06.2006 document created b 20.05.2009 spa-zc 402 2.1.2 additions ethernet adapter spa/tcp bridge installation and commissioning manual spa-zc 402 spa-zc 402 1mrs756019.

  • Page 10

    10

  • Page 11

    11 2. Safety information non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed. The device contains components whic...

  • Page 12

    12.

  • Page 13

    13 3. Product overview spa-zc 402 is used to connect ieds with the spa protocol over the tcp/ip network using the same ethernet link. Ref 610 com600 a090000 fig. 3.-1 conceptual picture of a typical system setup it is not allowed to connect multiple spa devices to spa-zc 402 in the spa loop because ...

  • Page 14

    Media converters: * ruggedcom rmc-100-mm * imc mcbasic mm1300 * allied telesyn at-mc302-20 more tested devices can be found on the abb web site http://www.Abb.Com/substationautomation. 3.1. Features spa-zc 402 has the following features: * auxiliary power supply * support of communication over tcp/i...

  • Page 15

    15 3.2. Transmission control protocol (tcp) the transmission control protocol (tcp) is the most commonly used protocol for exchanging data between communication devices using ethernet. Unlike udp, the tcp protocol guarantees reliable transmission between applications. Tcp also distinguishes data for...

  • Page 16

    16.

  • Page 17

    17 4. Installation this chapter describes the installation of the spa-zc 402 module and the communication engineering tool (cet) for spa-zc 40x. For additional information, such as technical data, maintenance and service, refer to section 7. Technical data and section 8. Maintenance and service. 4.1...

  • Page 18

    4.3.2. Installing communication engineering tool for spa-zc 40x 1. Uninstall the previous version. 2. Close all the open programs and insert the communication engineering tool (cet) for spa-zc 40x installation cd to the cd-rom drive of your pc. 3. The installation program starts automatically. If th...

  • Page 19

    19 4.3.3. Uninstalling communication engineering tool for spa-zc 40x 1. Open the add or remove programs dialog by selecting start > settings > control panel > add or remove programs. 2. Select communication engineering tool (cet) for spa-zc 40x and click remove. Uninstall cet for spa-zc 40x in order...

  • Page 20

    A060241 fig. 4.4.1.-1 changing ip address 4.4.2. Checking connection to spa-zc 402 check the connection to spa-zc 402 by using the ping command: 1. Open the run dialog. 2. Type cmd to the open box, see fig. 4.4.2.-1. A060242 fig. 4.4.2.-1 starting command prompt 3. Click ok to run the command prompt...

  • Page 21

    21 4. Type ping 192.168.2.10, see fig. 4.4.2.-2. Fig. 4.4.2.-2 pinging spa-zc 402 spa-zc 402responds to the ping command if the computer and spa-zc 402 are on the same network. 5. If spa-zc 402 responds with the ip address, the connection is established between the computer and spa-zc 402. Ethernet ...

  • Page 22

    22.

  • Page 23

    23 5. Engineering this section guides when performing the engineering tasks required before using spa-zc 402. Note that all the possible engineering scenarios are not included in this manual. You must have engineering rights to be able to perform the tasks described in this section. 5.1. Overview of...

  • Page 24

    * direct connection via serial cable or fibre (conventional usage of spa bus) * conventional modem connection, when used as a direct connection, running on the spa protocol only * gsm modem connection, when used as a direct connection, running on the spa protocol only * serial connection over tcp/ip...

  • Page 25

    25 a040014b fig. 5.3.-2 creating a new project 5.4. Restarting use this function to restart the spa-zc 402 at runtime. 1. Select ied and tools > reset tool to open the restart panel, see fig. 5.4.-1 2. Click reset. The results are reported to the ui text box. Do not use the restart function while do...

  • Page 26

    5.5. Building object tree after creating the project you need to build and configure an object tree in the communication engineering tool (cet) for spa-zc 40x to define the communication structure. Fig. 5.5.-1 shows an example of the object tree when it has been built. In the example tree you can se...

  • Page 27

    27 3. Logical node objects 4. Data objects 5.5.1. Adding device object to build the object tree: 1. Add a spazc40x_spa device object in the communication structure by selecting the project name. In the example, the project protocol test is selected. 2. Right-click protocol test 3. Select new > tunne...

  • Page 28

    5.6. Configuring by using imported cid file if you have to configure several spa-zc 402 with the similar settings, it is possible to import a previously generated cid file and change the communication addresses, typically by changing the ip address. Create a new project and add a spazc40x_spa device...

  • Page 29

    29 5.7.1. Uplink network settings a051857 fig. 5.7.1.-1 uplink network settings * default gateway the ip address default gateway defines the gateway address that forwards the ip traffic between the local subnet and the outside world. The default ip address is 192.168.2.1 and this has to be changed a...

  • Page 30

    * subnet mask the subnet mask address defines which addresses have access to the default gateway. * tcp-keepalive the status of the tcp/ip connection is monitored by transmitting keep alive- messages at configured intervals. This is done invisibly to the user. The value is in minutes and the default...

  • Page 31

    31 * 9600 bps * 19200 bps * 38400 bps * receive timeout receive timeout defines how long spa-zc 402 waits for the slave ’s respond before it considers the slave to be non-responding. The unit is milliseconds. * retransmissions retransmissions defines how many times a message is resent after connecti...

  • Page 32

    A060033 fig. 5.8.-1 downloading the device's configuration if spa-zc 402 is connected to a system where the connection to it can be obtained, the export function tries to determine the spa-zc 402 version and exports the export file accordingly. If the connection is disabled, prompt the correct versi...

  • Page 33

    33 6. Commissioning the downloaded configuration file is taken into use when spa-zc 402 is restarted automatically. Normally, the device is reset automatically after the configuration is downloaded with communication engineering tool (cet) for spa-zc 40x. After downloading the configuration you can ...

  • Page 34

    34.

  • Page 35

    35 7. Technical data 7.1. Interfaces ied interface * st multimode glass fibre transmitter/receiver pair or * snap-in multimode plastic fibre transmitter/receiver pair ethernet interface * multimode mt-rj * multimode lc * rj-45 for stp cat5e optical fibres * see fibre-optic guides: * spa-zf optical g...

  • Page 36

    Dimensions and weight 115 35 190 175 use m5 mounting screws spa-zc 402 ethernet adapter 1msc971 158e external power l n + plastic glass 24-60 vdc 110-220 vdc, 100-240 vac diag rx tx link power u aux tx rx ethernet lan iec 61850 spa / tcp modbus / tcp a040027b fig. 7.1.-1 dimensions of the spa-zc 402...

  • Page 37

    37 general requirements table 7.2.-1 environmental test and conditions recommended service temperature range (continuous) -10...+55 ˚c limited temperature range (short-term) -40...+85 ˚c transport and storage temperature range -40...+70 ˚c according to the iec 60068-2-48 dry heat test according to t...

  • Page 38

    Table 7.2.-3 standard tests mechanical tests vibration tests (sinusoidal) according to the iec 60255-21-1, class i shock and bump test according to the iec 60255-21-2, class i table 7.2.-4 auxiliary power supplies type spa-zc 402 xxxa spa-zc 402 xxxc input voltage ac 110/120/220/240 v - input voltag...

  • Page 39

    39 8. Maintenance and service if the spa-zc 402 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. 8.1. Led indicators table 8.1.-1 led indicators led color state sequence number description power green on power on link lan green on indication...

  • Page 40

    Sntp servers:10.58.125.150 127.0.0.1 sw_spatype: spa-zc40x sw_number: 1mrs118533 sw_build: 110 sw_revision: b compiler date_time: nov 28 2005 12:38:02 to use the ip query tool: 1. Select tools > ip query tool to start the tool, see fig. 8.3.-1. Query activates devices from the network until it is st...

  • Page 41

    41 a060128 fig. 8.3.-2 selecting network adapter 3. Click start to start the query. 4. Click stop to stop the query. Connected devices are displayed in the output pane, fig. 8.3.-2. Additional information depends on the spa-zc 40x version. If version 1.1.1 is used, only mac address is displayed. If ...

  • Page 42

    The version information can be read from the device's label. If the device is updated afterwards, use cet's ip query to get the correct version information from the device memory. For more information about ip query, refer to section 8.3. Ip query. 8.5. Obtaining error logs the following session tra...

  • Page 43

    43 9. Ordering information spa-zc402mmpa ethernet connector type m = mtrj l = lc r = rj-45 protocol type m = modbus/tcp e = iec 61850 s = spa/tcp device type optical transmitter and receiver for spa bus p = plastic fibre cable g = glass fibre cable auxiliary voltage a = 100-240 v ac, 110-220 v dc c ...

  • Page 44

    44.

  • Page 45

    45 10. Terminology term description communication engineering tool also known as cet. Software for configuring and monitor- ing communication gateways or communication front ends. Intelligent electronic device also known as ied. Devices containing advanced logics such as meters, protection and contr...

  • Page 46

    46.

  • Page 47

    47 11. Abbreviations abbreviation description cd change detect; compact disk cet communication engineering tool cid configured ied description doi data object instance emc electromagnetic compatibility ftp file transfer protocol ied intelligent electronic device ip internet protocol lan local area n...

  • Page 52

    Abb oy distribution automation p.O. Box 699 fi-65101 vaasa finland +358 10 2211 +358 10 224 1080 www.Abb.Com/substationautomation 1mrs75601 9 e n 5 /2009.