Abb ab / jokab safety varlabergsvägen 11, se-434 39 kungsbacka, sweden www.Abb.Com/jokabsafety original instructions tina 7a adaptor unit.
2tlc172139m0201, rev. B 2 www.Abb.Com/ jokabsafety 2013-03-02 read and understand this document please read and understand this document before using the products. Please consult your abb/jokab safety representative if you have any questions or comments. Warranty abb/jokab safety’s exclusive warrant...
2tlc172139m0201, rev. B 3 www.Abb.Com/ljokabsafety 2013-03-02 table of contents 1 introduction ......................................................................................................................................... 4 scope ..............................................................
2tlc172139m0201, rev. B 4 www.Abb.Com/ jokabsafety 2013-03-02 1 introduction scope the purpose of these instructions is to describe the adaptor unit tina 7a and to provide the necessary information required for installation and operation. Audience this document is intended for authorized installatio...
2tlc172139m0201, rev. B 5 www.Abb.Com/ljokabsafety 2013-03-02 2 overview general description abb/jokab safety adaptor units are used to adapt conventional safety sensors where the safety relies on e.G. One- or two-channel static signals, ossd outputs, or short circuit detection, to the dynamic safet...
2tlc172139m0201, rev. B 6 www.Abb.Com/ jokabsafety 2013-03-02 3 connections nb: shielded cable is recommended between this unit and the rest of the safety circuits. Caution! The safety loop cables (connected to terminals 6-9) should not be longer than 150 mm. The cables should be as short as possibl...
2tlc172139m0201, rev. B 7 www.Abb.Com/ljokabsafety 2013-03-02 connection examples caution! All cable colours according to abb/jokab safety standard cables..
2tlc172139m0201, rev. B 8 www.Abb.Com/ jokabsafety 2013-03-02 4 installation and maintenance installation precautions first attach the unit on a 35 mm din rail. Then attach the safety-loop to the connection block (nr 6-9). Finally, attach the cables to the connection block (nr 1-5). Warning! All the...
2tlc172139m0201, rev. B 9 www.Abb.Com/ljokabsafety 2013-03-02 5 operation led indication led indication description input signal on pin-2 led on tina green safety circuit closed (protection ok) dynamic signal in green-red (flash) safety circuit open (protection ok) no dynamic signal in or 0 vdc in r...
2tlc172139m0201, rev. B 10 www.Abb.Com/ jokabsafety 2013-03-02 6 technical data manufacturer address abb ab / jokab safety varlabergsvägen 11 se-434 39 kungsbacka sweden article number/ordering data tina 7a: 2tla020054r0700 power supply operating voltage 24 vdc +15 %, -25 % total current consumption...
2tlc172139m0201, rev. B 11 www.Abb.Com/ljokabsafety 2013-03-02 dimensions tina 7a nb: all measurements in millimetres. The jokab safety branded product with article number beginning with 2tlj is fully compatible with the abb branded product with article number beginning with 2tla..
2tlc172139m0201, rev. B 12 www.Abb.Com/ jokabsafety 2013-03-02 7 ec declaration of conformity abb ab / jokab safety varlabergsvägen 11, se-434 39 kungsbacka, sweden www.Abb.Com/jokabsafety.