Ablerex MSII-RT User Manual

Manual is about: Parallel Redundancy On-Line UPS 6Kva

Summary of MSII-RT

  • Page 1

    Ablerex msii-rt parallel redundancy on-line ups user’s manual 6kva 1 table of contents 1. Important safety instruction....................................................................2 1.1. An important notice................................................................................2 1.2. S...

  • Page 2

    2 1. Important safety instruction 1.1. An important notice 1.1.1. To ensure safety in all applications where a ups is hard wired to the electrical supply, ensure that the system is installed by a qualified electrical contractor. 1.1.2. The ups has its own internal energy source (battery). Should the...

  • Page 3

    4 branch circuit over-current protection for 30 amperes rating in accordance with the national electric code, ansi/nfpa 70. 1.1.26. Caution - to reduce the risk of fire, unit input connect only to a circuit provided with branch circuit over-current protection for 40 amperes rating in accordance with...

  • Page 4

    6 2.1.12. Revolutionary battery management circuit analyzes battery discharging status to adjust battery cut-off point and extend the life of batteries. 2.1.13. Intelligent temperature-controlled fan may not only extend the life of the fan, but also reduce annoying noise because of sudden fan spin. ...

  • Page 5

    8 17 next page 18 special function log in /out 19 enter or reconfirmed 20 utility input normal led 21 bypass input normal led 22 ups under redundancy mode 23 ups under eco mode 24 ups fault or abnormal warning led 25 epo emergency power off 26 er05 battery weak or dead 27 er06 output short circuit 2...

  • Page 6

    10 go to next page go to previous page or change the setting of the ups. To re-confirm the change of ups setting 2.3.2. Rear panel explanation a terminal resistor for parallel function b rs232 port c external battery connector d utility input breaker e can bus connection port for parallel system f m...

  • Page 7

    12 3. Installation and operation the packing condition and the external outlook of the unit should be inspected carefully before installation. Retain the packing material for future use. 3.1. Unpacking 3.1.1. Take out the ups module, battery module or isolation transformer with/without maintenance b...

  • Page 8

    14 3.3. Installation 3.3.1 tower installation 3.3.1.1 power module + battery module step1: installation of the foot covers of the power module step2: installation of the power module and the battery module 15 3.3.1.2 power module+ isolation transformer module+ battery module step1: installation of t...

  • Page 9

    16 3.3.2 rack installation 3.3.2.1 power module+ battery module step1: installation of the ear covers 17 step2: installation of the ear covers to power module, isolation transformer module and battery module step3: installation of the rail kit to rack cabinet.

  • Page 10

    18 step5: installation of the power module to the rack cabinet 19 3.3.2.2 power module+ isolation transformer module+ battery module step1: installation of the isolation transformer module to the rail step2 : installation of the power module to the rack cabinet.

  • Page 11

    20 3.4 terminal block explanation ● l12-n1: the terminal for utility input to provide the power source when the ups is working under utility mode. ● g1: the terminal for ups input ground. ● l21、n22: the terminals for ups output. ● g2: the terminal for ups output ground. Remarks: 1. When the isolatio...

  • Page 12

    22 (3a1) (3a2) b. For 100/110/115/120vac system, you may connect as shown in below. 23 (b) c. For 200/100vac, 220/110vac, 230v/115vac, or 240/120vac system, you may connect as shown in below. (c) d. For 240/208/120vac system, you may connect as shown in below..

  • Page 13

    24 (d) 4. When the isolation transformer is installed but maintenance bypass switch isn’t installed: a. For 200/220/230/240vac system, you may connect as shown in below. (4a1) 25 (4a2) b. For 100/110/115/120vac system, you may connect as shown in below. (b) c. For 200/100vac, 220/110vac, 230v/115vac...

  • Page 14

    26 (c) d. For 240/208/120vac system, you may connect as shown in below. (d) ● to fix the cables, you are recommended to use cable ties. 27 3.5. Operation test and installation instruction 3.5.1. Start up in normal mode 3.5.1.1 open the terminal block cover on the rear panel (refer to 2.3.2) before s...

  • Page 15

    28 d * it shows “test”. E1 * it shows “ok” in self-test e2 * it shows “fail” in self-test f * it shows “220vac” in utility input. 3.5.1.8 in case of failure in self-test, the lcd display will illustrate from drawing d to drawing e2, then an error code or error status will be shown on the screen. 29 ...

  • Page 16

    30 3.5.3 check measured values & figures detected by ups 3.5.3.1 if you would like to check the measured values & figures detected by the ups, please use scroll up and scroll down key pads. When you use scroll down key pad, the lcd display will illustrate as drawing c(voltage from utility input) Ædr...

  • Page 17

    32 3.5.4 ups default data and special function execution 3.5.4.1 after ups completely starts up, press key pad to change the lcd display screen to drawing q1. Q1 * it shows buzzer “on”. Q2 * it shows buzzer “off” . 3.5.4.2 press key pad to scroll down the screen and check the ups settings.The lcd di...

  • Page 18

    34 v1 * it shows the ups is operated in “normal mode”. V2 * it shows the ups is operated in “eco mode”. V3 * it shows the ups is operated in “cvcf 50hz mode”. P.S: if you want to set be a frequency converter, it shall be required by a qualified technician. V4 * it shows the ups is operated in “cvcf ...

  • Page 19

    36 3.5.5.3 except buzzer(as drawing q1 & q2) and self-test(as drawings r1 & r2), all the rest default settings may be changed by pressing scroll up key pad. 3.5.5.4 drawings s1 and s2 mean the bypass input acceptable window, it can be 184vac~260vac or 195vac~260vac. 3.5.5.5 drawing t means the bypas...

  • Page 20

    38 4. Troubleshooting guide 4.1. Trouble shooting when the ups malfunctions during operation, you may check the followings: a. Are the wirings of input and output correct? B. If the input voltage of the utility is within the input window of the ups? In case problems or symptoms still exist, please p...

  • Page 21

    40 5. Bundled software installation guide 5.1. Hardware installation 1. Connect the male connector of rs232 cable to the ups communication port. 2. Connect the female connector of the rs232 cable to a dedicated rs232 port of the computer. 3. For optional interface cards, you may refer to chapter 6 f...

  • Page 22

    42 6.4. Use(usb) card 6.4.1. Cn1 for usb and cn3 for epo. 6.4.2. For communication protocol, please see the definition below: comply with usb version 1.0,1.5mbps comply with usb hid version 1.0. The pin assignments of the use card: 6.4.3. Installation position: slot1 or slot 2. 6.4.4. Adapted flat c...

  • Page 23

    44 2 3 45 7. Hot swappable battery replacement 1. Remove the screw covers as well as screws as shown in step 1. 2. Remove the front panel as indicated in step 2. 3. Remove the screws of the battery module as shown in step 3..

  • Page 24

    46 4. Unplug the hot swappable battery connectors as shown in step 4. 5. Remove the battery packs from the battery module as shown in step 5. 47 8. Specifications model 4500va 6000va input voltage window 160~280vac* frequency 45 ~ 65 hz phase/wire single, line + neutral + ground power factor up to 0...

  • Page 25

    48 physical dimensions(wxdxh)mm 440x88x660(ups module) input/output connection hardwire external battery connection plug-in & play net weight(kgs) 24(ups module) battery bank dimensions convertible(rack/tower) bbc20j0007(20pcs 12v/7ah) 440x133x660(3u) battery bank net weight convertible(rack/tower) ...

  • Page 26

    50 51 192321142000000