B&R Industries Power Panel 300 User Manual

Other manuals for Power Panel 300: User Manual

Summary of Power Panel 300

  • Page 1

    1 power panel 300/400 user's manual v 2.10 power panel 300/400 user's manual version: 2.10 (april 2010) model number: mapp300.400-eng all information contained in this manual is current as of its creation/publication. We reserve the right to change the contents of this manual without warning. The in...

  • Page 2

    2 power panel 300/400 user's manual v 2.10

  • Page 3: Chapter 2: Technical Data

    3 power panel 300/400 user's manual v 2.10 chapter 1: general information chapter 2: technical data chapter 3: commissioning chapter 4: software chapter 5: standards and certifications chapter 6: accessories.

  • Page 4

    4 power panel 300/400 user's manual v 2.10

  • Page 5: Appendix A

    5 power panel 300/400 user's manual v 2.10 chapter 7: maintenance / servicing appendix a figure index table index model number index index.

  • Page 6

    6 power panel 300/400 user's manual v 2.10

  • Page 7

    7 power panel 300/400 user's manual v 2.10 table of contents chapter 1: general information ..................................................... 21 1. Manual history .................................................................................................................... 21 2. Safety gui...

  • Page 8

    8 power panel 300/400 user's manual v 2.10 table of contents 2.2.1 device label ............................................................................................................ 52 2.2.2 serial number sticker ...................................................................................

  • Page 9

    9 power panel 300/400 user's manual v 2.10 table of contents 2.10.3 dimensions ......................................................................................................... 100 2.10.4 cutout installation .......................................................................................

  • Page 10

    10 power panel 300/400 user's manual v 2.10 table of contents 3.7.4 cutout installation ................................................................................................. 143 3.7.5 contents of delivery ......................................................................................

  • Page 11

    11 power panel 300/400 user's manual v 2.10 table of contents 4.4.4 cutout installation ................................................................................................. 186 4.4.5 contents of delivery ......................................................................................

  • Page 12

    12 power panel 300/400 user's manual v 2.10 table of contents 4.12.3 dimensions ......................................................................................................... 233 4.12.4 cutout installation ......................................................................................

  • Page 13

    13 power panel 300/400 user's manual v 2.10 table of contents 4.20.2 temperature humidity diagram ........................................................................... 283 4.20.3 dimensions ...........................................................................................................

  • Page 14

    14 power panel 300/400 user's manual v 2.10 table of contents 4.28.1 technical data ..................................................................................................... 330 4.28.2 temperature humidity diagram .............................................................................

  • Page 15

    15 power panel 300/400 user's manual v 2.10 table of contents 6. Block diagram ................................................................................................................... 385 6.1 power panel 300 (with no apci slots) ...............................................................

  • Page 16

    16 power panel 300/400 user's manual v 2.10 table of contents 1.4.4 motherboard device configuration ......................................................................... 427 1.4.5 memory and cache optimization ........................................................................... 434 1.4.6...

  • Page 17

    17 power panel 300/400 user's manual v 2.10 table of contents 3.6.2 procedure ............................................................................................................. 467 3.6.3 where do i get ms-dos? ..................................................................................

  • Page 18

    18 power panel 300/400 user's manual v 2.10 table of contents 5.3 shock during operation ............................................................................................... 495 5.4 shock during transport (packaged) ............................................................................

  • Page 19

    19 power panel 300/400 user's manual v 2.10 table of contents 6.3.1 temperature humidity diagram - operation and storage ...................................... 520 6.4 dimensions .................................................................................................................. 521 7....

  • Page 20

    20 power panel 300/400 user's manual v 2.10 table of contents.

  • Page 21: 1. Manual History

    General information • manual history ch apte r 1 genera l in forma tion 21 power panel 300/400 user's manual v 2.10 chapter 1 • general information 1. Manual history information: b&r does its best to keep the printed versions of its user's manuals as current as possible. However, any newer versions ...

  • Page 22

    22 general information • manual history power panel 300/400 user's manual v 2.10 1.10 2007-02-22 - rear view of device 5pp320.1505-39 added. - driver support information modified. - section "automation runtime and smc" removed. - images of battery exchange changed. - compactflash 8192 mb ssi is enab...

  • Page 23

    General information • manual history ch apte r 1 genera l in forma tion 23 power panel 300/400 user's manual v 2.10 1.60 2008-11-05 - change to automation device interface (adi) control center on page 481. - b&r key editor moved from chapter 4 "software" to chapter "appendix" on page 545. - informat...

  • Page 24

    24 general information • manual history power panel 300/400 user's manual v 2.10 1.90 2009-07-02 - model numbers of the power panel 452 compact devices corrected. - text changed for the power button on the automation runtime devices (page 110 and page 171). - general information concerning power pan...

  • Page 25: 2. Safety Guidelines

    General information • safety guidelines ch apte r 1 genera l in forma tion 25 power panel 300/400 user's manual v 2.10 2. Safety guidelines 2.1 intended use programmable logic controllers (plcs), operating and monitoring devices (industrial pcs, power panels, mobile panels, etc.), and b&r uninterrup...

  • Page 26

    26 general information • safety guidelines power panel 300/400 user's manual v 2.10 • electrostatic discharges should be avoided on the components (e.G. Through charged plastics). • a minimum distance of 10 cm must be kept from monitors and tv sets. • measurement devices and equipment must be ground...

  • Page 27

    General information • safety guidelines ch apte r 1 genera l in forma tion 27 power panel 300/400 user's manual v 2.10 2.5 installation • installation must take place according to the documentation, using suitable equipment and tools. • devices must be installed without voltage applied and by qualif...

  • Page 28

    28 general information • safety guidelines power panel 300/400 user's manual v 2.10 2.6.3 programs, viruses and dangerous programs the system is subject to potential danger each time data is exchanged or software is installed from a data medium (e.G. Diskette, cd-rom, usb flash drive, etc.), a netwo...

  • Page 29: 4. Guidelines

    General information • organization of safety notices ch apte r 1 genera l in forma tion 29 power panel 300/400 user's manual v 2.10 3. Organization of safety notices the safety notices in this manual are organized as follows: 4. Guidelines european dimension standards apply to all dimensions (e.G. D...

  • Page 30: 5. Model Numbers

    30 general information • model numbers power panel 300/400 user's manual v 2.10 5. Model numbers 5.1 power panel 300 with bios model number short description note 5pp320.0571-29 power panel pp320 bios 5.7" qvga, touch screen 5.7" qvga color lc display with touch screen (resistive), 256 mb sdram; com...

  • Page 31

    General information • model numbers ch apte r 1 genera l in forma tion 31 power panel 300/400 user's manual v 2.10 5.2 power panel 300 with automation runtime model number short description note 4pp320.0571-01 power panel pp320 5.7" qvga, touch screen 5.7" qvga monochrome lc display with touch scree...

  • Page 32

    32 general information • model numbers power panel 300/400 user's manual v 2.10 5.3 power panel 400 with automation runtime model number short description note 4pp420.0571-45 power panel pp420 5.7" qvga, 1 apci, touch screen 5.7" qvga monochrome lc display with touch screen (resistive), 1 apci slot;...

  • Page 33

    General information • model numbers ch apte r 1 genera l in forma tion 33 power panel 300/400 user's manual v 2.10 4pp420.1505-b5 power panel pp420 15" xga, 2 apci, touch screen 15" xga color tft display with touch screen (resistive), 2 apci slots; 128 mb sdram; 512 kb sram, compactflash slot (type ...

  • Page 34

    34 general information • model numbers power panel 300/400 user's manual v 2.10 4pp452.0571-75 power panel pp452 5.7" qvga, 1 apci, keys 5.7" qvga color tft display; 20 function and 20 system keys; 1 apci slot; 128 mb sdram; 512 kb sram; compactflash slot (type i); eth 10/100; rs232; 2xusb; battery;...

  • Page 35

    General information • model numbers ch apte r 1 genera l in forma tion 35 power panel 300/400 user's manual v 2.10 5.4 power panel 400 light / compact model number short description note 4pp420:0571-l05 power panel pp420 light lcd monochrome, can, touch screen set power panel pp420 light can; 5.7'' ...

  • Page 36

    36 general information • model numbers power panel 300/400 user's manual v 2.10 5.5 software 4pp451:0571-c25 power panel pp451 compact lcd color, can, keys set power panel pp451 compact can; 5.7'' qvga lcd color; 128 mb sdram; 512 kb sram; eth 10/100. See page 373 4pp451:0571-c65 power panel pp451 c...

  • Page 37

    General information • model numbers ch apte r 1 genera l in forma tion 37 power panel 300/400 user's manual v 2.10 5.6 accessories 5swwce.0821-eng wince6.0 pro pp300 lx800 microsoft windows ce 6.0 professional, english, including license; for pp300 bios devices 5pp320.0571-29, 5pp320.0571-39, 5pp320...

  • Page 38

    38 general information • model numbers power panel 300/400 user's manual v 2.10 5ac900.104x-01 legend strip 1x 10.4" horizontal2 legend strip template for power panel 4pp482.1043-75. For 1 device. See page 511 5ac900.104x-02 legend strips 3x 10.4" horizontal1 legend strip template for power panel 4p...

  • Page 39: Chapter 2 • Technical Data

    Technical data • general information chap ter 2 te chn ica l da ta 39 power panel 300/400 user's manual v 2.10 chapter 2 • technical data 1. General information the new power panel 300/400 generation expands upon b&r's proven power panel 100/200 line. With more than twice the computing power, the ne...

  • Page 40

    40 technical data • general information power panel 300/400 user's manual v 2.10 1.1 features • 24 vdc supply voltage • 2 usb 2.0 connections • ethernet 10/100 mbit interface • compactflash card (type i) slot • rs232 interface, modem-capable, not electrically isolated • 2 operating mode switches (2 ...

  • Page 41

    Technical data • general information chap ter 2 te chn ica l da ta 41 power panel 300/400 user's manual v 2.10 1.2 advantages of power panel 300/400 over power panel 100/200 1.2.1 electrical • more powerful processor (geode lx800 = more than twice the performance) • 180° rotated power supply plug • ...

  • Page 42: 2. Power Panel 300 With Bios

    42 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2. Power panel 300 with bios 2.1 device interfaces the following section provides a description of all interfaces and plugs possible with a powerpanel 300 device with bios. 2.1.1 supply voltage input voltage: 18 -...

  • Page 43

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 43 power panel 300/400 user's manual v 2.10 2.1.2 functional grounding clip next to the supply voltage plug there is a functional grounding clip. The grounding clip (functional ground) must be connected with a central grounding...

  • Page 44

    44 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.1.3 serial interface com the power panel is equipped with a pc-compatible serial interface with a 16-byte fifo buffer. This non-electrically isolated interface is primarily intended for programming power panel d...

  • Page 45: Warning!

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 45 power panel 300/400 user's manual v 2.10 2.1.4 usb port the power panel 300/400 devices have a usb 2.0 (universal serial bus) host controller with multiple usb ports, two of which are on the outside for easy user access. Uni...

  • Page 46

    46 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.1.5 mode / node switches power panel devices are equipped with 2 hex switches that serve as operating mode switches. Switch positions 01 to fd are available for any purpose in an application and can be evaluated...

  • Page 47: Warning!

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 47 power panel 300/400 user's manual v 2.10 2.1.6 bios boot mode switch power panel devices are equipped with a bios boot mode switch. Figure 5: bios boot mode switch switch position function description right (toward cf slot) ...

  • Page 48

    48 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 os mode • standard boot screen (see section 1 "power panel 300 with bios" on page 397) • bios setup can be started by pressing the "del" key. • when the switch is in the "00" position, the setup default values wil...

  • Page 49

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 49 power panel 300/400 user's manual v 2.10 2.1.7 status leds power panels are equipped with two status leds that are visible on the outside. 2.1.8 ethernet connection status leds led color meaning 1x three-color, 1x one-color ...

  • Page 50: Warning!

    50 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.1.9 power button due to the complete atx power supply support, the power button serves a number of functions, which can be configured in bios setup. 2.1.10 reset button power button the power button can be press...

  • Page 51: Caution!

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 51 power panel 300/400 user's manual v 2.10 2.1.11 compactflash slot power panel devices are equipped with a compactflash slot that is accessible from the side. Type i compactflash cards are supported. It is possible to secure ...

  • Page 52

    52 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.2 stickers 2.2.1 device label the following sticker can be found in a suitable location on the power panel device: 2.2.2 serial number sticker general information each b&r device is given a unique serial number ...

  • Page 53

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 53 power panel 300/400 user's manual v 2.10 information on the internet information about each device can also be found on the b&r homepage. Enter the device's serial number in the serial number search field on the start page w...

  • Page 54

    54 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.3 device 5pp320.0571-29 figure 10: front view - 5pp320.0571-29 figure 11: rear view - 5pp320.0571-29 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 55

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 55 power panel 300/400 user's manual v 2.10 2.3.1 technical data features 5pp320.0571-29 boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 56

    56 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.0571-29 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max. 500 ma per con...

  • Page 57

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 57 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.0571-29 outer dimensions width height depth 212 mm 156 mm 55.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 58

    58 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.3.2 temperature humidity diagram 2.3.3 dimensions figure 12: temperature humidity diagram - 5pp320.0571-29 figure 13: dimensions - 5pp320.0571-29 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 59

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 59 power panel 300/400 user's manual v 2.10 2.3.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 60

    60 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.4 device 5pp320.0571-39 figure 15: front view - 5pp320.0571-39 figure 16: rear view - 5pp320.0571-39 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 61

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 61 power panel 300/400 user's manual v 2.10 2.4.1 technical data features 5pp320.0571-39 5pp320.0571-39 ≥ rev. D0 boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fp...

  • Page 62

    62 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.0571-39 5pp320.0571-39 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) t...

  • Page 63

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 63 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.0571-39 5pp320.0571-39 ≥ rev. D0 outer dimensions width height depth 212 mm 156 mm 55.5 mm front frame design membrane dark gray border around displa...

  • Page 64

    64 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.4.2 temperature humidity diagram 2.4.3 dimensions figure 17: temperature humidity diagram - 5pp320.0571-39 figure 18: dimensions - 5pp320.0571-39 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 65

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 65 power panel 300/400 user's manual v 2.10 2.4.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 66

    66 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.5 device 5pp320.0573-39 figure 20: front view - 5pp320.0573-39 figure 21: rear view - 5pp320.0573-39 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 67

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 67 power panel 300/400 user's manual v 2.10 2.5.1 technical data features 5pp320.0573-39 boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 68

    68 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.0573-39 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max. 500 ma per con...

  • Page 69

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 69 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.0573-39 outer dimensions width height depth 212 mm 156 mm 55.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 70

    70 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.5.2 temperature humidity diagram 2.5.3 dimensions figure 22: temperature humidity diagram - 5pp320.0573-39 figure 23: dimensions - 5pp320.0573-39 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 71

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 71 power panel 300/400 user's manual v 2.10 2.5.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 72

    72 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.6 device 5pp320.0573-3b figure 25: front view - 5pp320.0573-3b figure 26: rear view - 5pp320.0573-3b compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 73

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 73 power panel 300/400 user's manual v 2.10 2.6.1 technical data features 5pp320.0573-3b boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 74

    74 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.0573-3b usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max. 500 ma per con...

  • Page 75

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 75 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.0573-3b outer dimensions width height depth 212 mm 156 mm 55.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 76

    76 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.6.2 temperature humidity diagram 2.6.3 dimensions figure 27: temperature humidity diagram - 5pp320.0573-3b figure 28: dimensions - 5pp320.0573-3b 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 77

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 77 power panel 300/400 user's manual v 2.10 2.6.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 78

    78 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.7 device 5pp320.1043-39 figure 30: front view - 5pp320.1043-39 figure 31: rear view - 5pp320.1043-39 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 79

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 79 power panel 300/400 user's manual v 2.10 2.7.1 technical data features 5pp320.1043-39 boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 80

    80 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.1043-39 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max. 500 ma per con...

  • Page 81

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 81 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.1043-39 outer dimensions width height depth 323 mm 260 mm 65.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 82

    82 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.7.2 temperature humidity diagram 2.7.3 dimensions figure 32: temperature humidity diagram - 5pp320.1043-39 figure 33: dimensions - 5pp320.1043-39 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 83

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 83 power panel 300/400 user's manual v 2.10 2.7.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 84

    84 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.8 device 5pp320.1214-39 figure 35: front view - 5pp320.1214-39 figure 36: rear view - 5pp320.1214-39 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 85

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 85 power panel 300/400 user's manual v 2.10 2.8.1 technical data features 5pp320.1214-39 boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 86

    86 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.1214-39 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max. 500 ma per con...

  • Page 87

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 87 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.1214-39 outer dimensions width height depth 362 mm 284 mm 65.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 88

    88 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.8.2 temperature humidity diagram 2.8.3 dimensions figure 37: temperature humidity diagram - 5pp320.1214-39 figure 38: dimensions - 5pp320.1214-39 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 89

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 89 power panel 300/400 user's manual v 2.10 2.8.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 90

    90 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.9 device 5pp320.1505-39 figure 40: front view - 5pp320.1505-39 figure 41: rear view - 5pp320.1505-39 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gro...

  • Page 91

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 91 power panel 300/400 user's manual v 2.10 2.9.1 technical data features 5pp320.1505-39 boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 92

    92 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.1505-39 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max. 500 ma per con...

  • Page 93

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 93 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.1505-39 outer dimensions width height depth 435 mm 330 mm 71.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 94

    94 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.9.2 temperature humidity diagram 2.9.3 dimensions figure 42: temperature humidity diagram - 5pp320.1505-39 figure 43: dimensions - 5pp320.1505-39 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10 5 ...

  • Page 95

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 95 power panel 300/400 user's manual v 2.10 2.9.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in...

  • Page 96

    96 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.10 device 5pp320.1505-3b figure 45: front view - 5pp320.1505-3b figure 46: rear view - 5pp320.1505-3b compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb supply voltage gr...

  • Page 97

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 97 power panel 300/400 user's manual v 2.10 2.10.1 technical data features 5pp320.1505-3b boot loader / operating system bios processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode ...

  • Page 98

    98 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 features 5pp320.1505-3b usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s), to high speed (480 mbit/s) 4) type a max. 500 ma per co...

  • Page 99

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 99 power panel 300/400 user's manual v 2.10 mechanical characteristics 5pp320.1505-3b outer dimensions width height depth 435 mm 330 mm 71.5 mm front frame design membrane dark gray border around display light background gasket...

  • Page 100

    100 technical data • power panel 300 with bios power panel 300/400 user's manual v 2.10 2.10.2 temperature humidity diagram 2.10.3 dimensions figure 47: temperature humidity diagram - 5pp320.1505-3b figure 48: dimensions - 5pp320.1505-3b 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -30 -20 -10...

  • Page 101

    Technical data • power panel 300 with bios chap ter 2 te chn ica l da ta 101 power panel 300/400 user's manual v 2.10 2.10.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included ...

  • Page 102: Warning!

    102 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3. Power panel 300 with automation runtime 3.1 device interfaces the following section provides a description of all interfaces and plugs possible with a power panel 300 device with automation runti...

  • Page 103

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 103 power panel 300/400 user's manual v 2.10 3.1.2 functional grounding clip next to the supply voltage plug there is a functional grounding clip. The grounding clip (functional ground) must be connected with a ce...

  • Page 104

    104 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.1.3 serial interface com the power panel is equipped with a pc-compatible serial interface with a 16-byte fifo buffer. This non-electrically isolated interface is primarily intended for programmin...

  • Page 105: Warning!

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 105 power panel 300/400 user's manual v 2.10 3.1.4 usb port the power panel 300/400 devices have a usb 2.0 (universal serial bus) host controller with multiple usb ports, two of which are on the outside for easy u...

  • Page 106

    106 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.1.5 mode / node switches power panel devices are equipped with 2 hex switches that serve as operating mode switches. Switch positions 01 to fd are available for any purpose in an application and c...

  • Page 107: Warning!

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 107 power panel 300/400 user's manual v 2.10 3.1.6 bios boot mode switch power panel devices are equipped with a bios boot mode switch. Figure 52: bios boot mode switch switch position function description right (...

  • Page 108

    108 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 os mode • standard boot screen (see section 1 "power panel 300 with bios" on page 397) • bios setup can be started by pressing the "del" key. • when the switch is in the "00" position, the setup def...

  • Page 109

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 109 power panel 300/400 user's manual v 2.10 3.1.7 status leds power panels are equipped with two status leds that are visible on the outside. 3.1.8 ethernet connection status leds led color meaning 1x three-color...

  • Page 110: Warning!

    110 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.1.9 power button 3.1.10 reset button power button the power button can be pressed with a pointed object (i.E. Paper clip or tip of a pen). If the power button is pushed, the power panel is switche...

  • Page 111: Caution!

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 111 power panel 300/400 user's manual v 2.10 3.1.11 compactflash slot power panel devices are equipped with a compactflash slot that is accessible from the side. Type i compactflash cards are supported. It is poss...

  • Page 112

    112 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.2 stickers 3.2.1 device label the following sticker can be found in a suitable location on the power panel device: 3.2.2 serial number sticker general information each b&r device is given a unique...

  • Page 113

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 113 power panel 300/400 user's manual v 2.10 information on the internet information about each device can also be found on the b&r homepage. Enter the device's serial number in the serial number search field on t...

  • Page 114

    114 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.3 device 4pp320.0571-01 figure 57: front view - 4pp320.0571-01 figure 58: rear view - 4pp320.0571-01 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb sup...

  • Page 115

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 115 power panel 300/400 user's manual v 2.10 3.3.1 technical data features 4pp320.0571-01 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit...

  • Page 116

    116 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp320.0571-01 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 3) type a max....

  • Page 117

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 117 power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp320.0571-01 outer dimensions width height depth 212 mm 156 mm 55.5 mm front frame design membrane dark gray border around display light ba...

  • Page 118

    118 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.3.2 temperature humidity diagram 3.3.3 dimensions figure 59: temperature humidity diagram - 4pp320.0571-01 figure 60: dimensions 4pp320.0571-01 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -...

  • Page 119

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 119 power panel 300/400 user's manual v 2.10 3.3.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 120

    120 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.4 device 4pp320.0571-35 figure 62: front view - 4pp320.0571-35 figure 63: rear view - 4pp320.0571-35 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb sup...

  • Page 121

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 121 power panel 300/400 user's manual v 2.10 3.4.1 technical data features 4pp320.0571-35 4pp320.0571-35 ≥ d0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache...

  • Page 122

    122 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp320.0571-35 4pp320.0571-35 ≥ d0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mb...

  • Page 123

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 123 power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp320.0571-35 4pp320.0571-35 ≥ d0 outer dimensions width height depth 212 mm 156 mm 55.5 mm front frame design membrane dark gray border aro...

  • Page 124

    124 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.4.2 temperature humidity diagram 3.4.3 dimensions figure 64: temperature humidity diagram - 4pp320.0571-35 figure 65: dimensions 4pp320.0571-35 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -...

  • Page 125

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 125 power panel 300/400 user's manual v 2.10 3.4.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 126

    126 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.5 device 4pp320.1043-31 figure 67: front view - 4pp320.1043-31 figure 68: rear view - 4pp320.1043-31 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb sup...

  • Page 127

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 127 power panel 300/400 user's manual v 2.10 3.5.1 technical data features 4pp320.1043-31 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit...

  • Page 128

    128 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp320.1043-31 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 3) type a max....

  • Page 129

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 129 power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp320.1043-31 outer dimensions width height depth 323 mm 260 mm 65.5 mm front frame design membrane dark gray border around display light ba...

  • Page 130

    130 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.5.2 temperature humidity diagram 3.5.3 dimensions figure 69: temperature humidity diagram - 4pp320.1043-31 figure 70: dimensions 4pp320.1043-31 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -...

  • Page 131

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 131 power panel 300/400 user's manual v 2.10 3.5.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 132

    132 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.6 device 4pp320.1505-31 figure 72: front view - 4pp320.1505-31 figure 73: rear view - 4pp320.1505-31 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds com ethernet reset button usb sup...

  • Page 133

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 133 power panel 300/400 user's manual v 2.10 3.6.1 technical data features 4pp320.1505-31 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit...

  • Page 134

    134 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp320.1505-31 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 3) type a max....

  • Page 135

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 135 power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp320.1505-31 outer dimensions width height depth 435 mm 330 mm 71.5 mm front frame design membrane dark gray border around display light ba...

  • Page 136

    136 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.6.2 temperature humidity diagram 3.6.3 dimensions figure 74: temperature humidity diagram - 4pp320.1505-31 figure 75: dimensions 4pp320.1505-31 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40 -...

  • Page 137

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 137 power panel 300/400 user's manual v 2.10 3.6.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 138

    138 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.7 device 4pp351.0571-01 figure 77: front view - 4pp351.0571-01 figure 78: rear view - 4pp351.0571-01 keys can be labeled using legend strips keys can be labeled using legend strips compactflash sl...

  • Page 139

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 139 power panel 300/400 user's manual v 2.10 3.7.1 technical data features 4pp351.0571-01 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit...

  • Page 140

    140 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp351.0571-01 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 3) type a max....

  • Page 141

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 141 power panel 300/400 user's manual v 2.10 electrical characteristics 4pp351.0571-01 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 212 mm 245 mm 55.5 mm front frame design...

  • Page 142

    142 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.7.2 temperature humidity diagram 3.7.3 dimensions figure 79: temperature humidity diagram - 4pp351.0571-01 figure 80: dimensions - 4pp351.0571-01 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40...

  • Page 143

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 143 power panel 300/400 user's manual v 2.10 3.7.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 144

    144 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.8 device 4pp351.0571-35 figure 82: front view - 4pp351.0571-35 figure 83: rear view - 4pp351.0571-35 keys can be labeled using legend strips keys can be labeled using legend strips compactflash sl...

  • Page 145

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 145 power panel 300/400 user's manual v 2.10 3.8.1 technical data features 4pp351.0571-35 4pp351.0571-35 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 ...

  • Page 146

    146 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp351.0571-35 4pp351.0571-35 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (4...

  • Page 147

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 147 power panel 300/400 user's manual v 2.10 electrical characteristics 4pp351.0571-35 4pp351.0571-35 ≥ rev. D0 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 212 mm 245 mm 5...

  • Page 148

    148 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.8.2 temperature humidity diagram 3.8.3 dimensions figure 84: temperature humidity diagram - 4pp351.0571-35 figure 85: dimensions - 4pp351.0571-35 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40...

  • Page 149

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 149 power panel 300/400 user's manual v 2.10 3.8.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 150

    150 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.9 device 4pp352.0571-35 figure 87: front view - 4pp352.0571-35 figure 88: rear view - 4pp352.0571-35 keys can be labeled using legend strips compactflash slot (with latch) sw1 (x16) sw2 (x1) statu...

  • Page 151

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 151 power panel 300/400 user's manual v 2.10 3.9.1 technical data features 4pp352.0571-35 4pp352.0571-35 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 ...

  • Page 152

    152 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp352.0571-35 4pp352.0571-35 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (4...

  • Page 153

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 153 power panel 300/400 user's manual v 2.10 electrical characteristics 4pp352.0571-35 4pp352.0571-35 ≥ rev. D0 power supply rated voltage rated current starting current power consumption electrical isolation 18 -...

  • Page 154

    154 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.9.2 temperature humidity diagram 3.9.3 dimensions figure 89: temperature humidity diagram - 4pp352.0571-35 figure 90: dimensions - 4pp352.0571-35 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50 -40...

  • Page 155

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 155 power panel 300/400 user's manual v 2.10 3.9.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining cl...

  • Page 156

    156 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.10 device 4pp381.1043-31 figure 92: front view - 4pp381.1043-31 figure 93: rear view - 4pp381.1043-31 keys can be labeled using legend strips keys can be labeled using legend strips compactflash s...

  • Page 157

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 157 power panel 300/400 user's manual v 2.10 3.10.1 technical data features 4pp381.1043-31 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point uni...

  • Page 158

    158 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp381.1043-31 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 3) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 3) type a max....

  • Page 159

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 159 power panel 300/400 user's manual v 2.10 features 4pp381.1043-31 display type diagonal colors resolution contrast viewing angle (see page 536) horizontal vertical background lighting brightness half-brightness...

  • Page 160

    160 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp381.1043-31 front frame design membrane dark gray border around display light background orange keys dark gray keys legend strips (gray) gasket aluminum, naturally anod...

  • Page 161

    Technical data • power panel 300 with automation runtime chap ter 2 te chn ica l da ta 161 power panel 300/400 user's manual v 2.10 3.10.2 temperature humidity diagram 3.10.3 dimensions figure 94: temperature humidity diagram - 4pp381.1043-31 figure 95: dimensions - 4pp381.1043-31 0 0 10 20 30 40 50...

  • Page 162

    162 technical data • power panel 300 with automation runtime power panel 300/400 user's manual v 2.10 3.10.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 3.1...

  • Page 163: Warning!

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 163 power panel 300/400 user's manual v 2.10 4. Power panel 400 with automation runtime 4.1 device interfaces the following section provides a description of all interfaces and plugs possible with a power panel 40...

  • Page 164

    164 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.1.2 functional grounding clip next to the supply voltage plug there is a functional grounding clip. The grounding clip (functional ground) must be connected with a central grounding point on the s...

  • Page 165

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 165 power panel 300/400 user's manual v 2.10 4.1.3 serial interface com the power panel is equipped with a pc-compatible serial interface with a 16-byte fifo buffer. This non-electrically isolated interface is pri...

  • Page 166: Warning!

    166 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.1.4 usb port the power panel 300/400 devices have a usb 2.0 (universal serial bus) host controller with multiple usb ports, two of which are on the outside for easy user access. Universal serial b...

  • Page 167

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 167 power panel 300/400 user's manual v 2.10 4.1.5 mode / node switches power panel devices are equipped with 2 hex switches that serve as operating mode switches. Switch positions 01 to fd are available for any p...

  • Page 168: Warning!

    168 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.1.6 bios boot mode switch power panel devices are equipped with a bios boot mode switch. Figure 99: bios boot mode switch switch position function description right (toward cf slot) os mode the po...

  • Page 169

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 169 power panel 300/400 user's manual v 2.10 os mode • standard boot screen (see section 1 "power panel 300 with bios" on page 397) • bios setup can be started by pressing the "del" key. • when the switch is in th...

  • Page 170

    170 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.1.7 status leds power panels are equipped with two status leds that are visible on the outside. 4.1.8 ethernet connection status leds led color meaning 1x three-color, 1x one-color power green on ...

  • Page 171: Warning!

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 171 power panel 300/400 user's manual v 2.10 4.1.9 power button 4.1.10 reset button power button the power button can be pressed with a pointed object (i.E. Paper clip or tip of a pen). If the power button is push...

  • Page 172: Caution!

    172 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.1.11 compactflash slot power panel devices are equipped with a compactflash slot that is accessible from the side. Type i compactflash cards are supported. It is possible to secure the compactflas...

  • Page 173

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 173 power panel 300/400 user's manual v 2.10 4.2 stickers 4.2.1 device label the following sticker can be found in a suitable location on the power panel device: 4.2.2 serial number sticker general information eac...

  • Page 174

    174 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 information on the internet information about each device can also be found on the b&r homepage. Enter the device's serial number in the serial number search field on the start page www.Br-automatio...

  • Page 175

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 175 power panel 300/400 user's manual v 2.10 4.3 device 4pp420.0571-45 figure 105: front view - 4pp420.0571-45 figure 106: rear view - 4pp420.0571-45 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 176

    176 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.3.1 technical data features 4pp420.0571-45 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode lx...

  • Page 177

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 177 power panel 300/400 user's manual v 2.10 features 4pp420.0571-45 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 178

    178 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0571-45 outer dimensions width height depth 212 mm 156 mm 76 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 179

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 179 power panel 300/400 user's manual v 2.10 4.3.2 temperature humidity diagram 4.3.3 dimensions figure 107: temperature humidity diagram - 4pp420.0571-45 figure 108: dimensions - 4pp420.0571-45 0 0 10 20 30 40 50...

  • Page 180

    180 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.3.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.3....

  • Page 181

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 181 power panel 300/400 user's manual v 2.10 4.4 device 4pp420.0571-65 figure 110: front view - 4pp420.0571-65 figure 111: rear view - 4pp420.0571-65 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 182

    182 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.4.1 technical data features 4pp420.0571-65 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode lx...

  • Page 183

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 183 power panel 300/400 user's manual v 2.10 features 4pp420.0571-65 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 184

    184 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0571-65 outer dimensions width height depth 212 mm 156 mm 76 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 185

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 185 power panel 300/400 user's manual v 2.10 4.4.2 temperature humidity diagram 4.4.3 dimensions figure 112: temperature humidity diagram - 4pp420.0571-65 figure 113: dimensions - 4pp420.0571-65 0 0 10 20 30 40 50...

  • Page 186

    186 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.4.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.4....

  • Page 187

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 187 power panel 300/400 user's manual v 2.10 4.5 device 4pp420.0571-75 figure 115: front view - 4pp420.0571-75 figure 116: rear view - 4pp420.0571-75 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 188

    188 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.5.1 technical data features 4pp420.0571-75 4pp420.0571-75 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu...

  • Page 189

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 189 power panel 300/400 user's manual v 2.10 features 4pp420.0571-75 4pp420.0571-75 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full spee...

  • Page 190

    190 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0571-75 4pp420.0571-75 ≥ rev. D0 outer dimensions width height depth 212 mm 156 mm 76 mm front frame design membrane dark gray border around display light backgroun...

  • Page 191

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 191 power panel 300/400 user's manual v 2.10 4.5.2 temperature humidity diagram 4.5.3 dimensions figure 117: temperature humidity diagram - 4pp420.0571-75 figure 118: dimensions - 4pp420.0571-75 0 0 10 20 30 40 50...

  • Page 192

    192 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.5.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.5....

  • Page 193

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 193 power panel 300/400 user's manual v 2.10 4.6 device 4pp420.0571-85 figure 120: front view - 4pp420.0571-85 figure 121: rear view - 4pp420.0571-85 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 194

    194 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.6.1 technical data features 4pp420.0571-a5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode lx...

  • Page 195

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 195 power panel 300/400 user's manual v 2.10 features 4pp420.0571-a5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 196

    196 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0571-a5 outer dimensions width height depth 212 mm 156 mm 98 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 197

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 197 power panel 300/400 user's manual v 2.10 4.6.2 temperature humidity diagram 4.6.3 dimensions figure 122: temperature humidity diagram - 4pp420.0571-85 figure 123: dimensions - 4pp420.0571-85 0 0 10 20 30 40 50...

  • Page 198

    198 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.6.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.6....

  • Page 199

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 199 power panel 300/400 user's manual v 2.10 4.7 device 4pp420.0571-a5 figure 125: front view - 4pp420.0571-a5 figure 126: rear view - 4pp420.0571-a5 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 200

    200 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.7.1 technical data features 4pp420.0571-a5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode lx...

  • Page 201

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 201 power panel 300/400 user's manual v 2.10 features 4pp420.0571-a5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 202

    202 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0571-a5 outer dimensions width height depth 212 mm 156 mm 98 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 203

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 203 power panel 300/400 user's manual v 2.10 4.7.2 temperature humidity diagram 4.7.3 dimensions figure 127: temperature humidity diagram - 4pp420.0571-a5 figure 128: dimensions - 4pp420.0571-a5 0 0 10 20 30 40 50...

  • Page 204

    204 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.7.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.7....

  • Page 205

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 205 power panel 300/400 user's manual v 2.10 4.8 device 4pp420.0571-b5 figure 130: front view - 4pp420.0571-b5 figure 131: rear view - 4pp420.0571-b5 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 206

    206 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.8.1 technical data features 4pp420.0571-b5 4pp420.0571-b5 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu...

  • Page 207

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 207 power panel 300/400 user's manual v 2.10 features 4pp420.0571-b5 4pp420.0571-b5 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full spee...

  • Page 208

    208 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0571-b5 4pp420.0571-b5 ≥ rev. D0 outer dimensions width height depth 212 mm 156 mm 98 mm front frame design membrane dark gray border around display light backgroun...

  • Page 209

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 209 power panel 300/400 user's manual v 2.10 4.8.2 temperature humidity diagram 4.8.3 dimensions figure 132: temperature humidity diagram - 4pp420.0571-b5 figure 133: dimensions - 4pp420.0571-b5 0 0 10 20 30 40 50...

  • Page 210

    210 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.8.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.8....

  • Page 211

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 211 power panel 300/400 user's manual v 2.10 4.9 device 4pp420.0573-75 figure 135: front view - 4pp420.0573-75 figure 136: rear view - 4pp420.0573-75 battery compartment compactflash slot (with latch) sw1 (x16) sw...

  • Page 212

    212 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.9.1 technical data features 4pp420.0573-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode lx...

  • Page 213

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 213 power panel 300/400 user's manual v 2.10 features 4pp420.0573-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 214

    214 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.0573-75 outer dimensions width height depth 212 mm 156 mm 76 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 215

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 215 power panel 300/400 user's manual v 2.10 4.9.2 temperature humidity diagram 4.9.3 dimensions figure 137: temperature humidity diagram - 4pp420.0573-75 figure 138: dimensions - 4pp420.0573-75 0 0 10 20 30 40 50...

  • Page 216

    216 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.9.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.9....

  • Page 217

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 217 power panel 300/400 user's manual v 2.10 4.10 device 4pp420.1043-75 figure 140: front view - 4pp420.1043-75 figure 141: rear view - 4pp420.1043-75 compactflash slot (with latch) sw1 (x16) battery compartment s...

  • Page 218

    218 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.10.1 technical data features 4pp420.1043-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 219

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 219 power panel 300/400 user's manual v 2.10 features 4pp420.1043-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 220

    220 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.1043-75 outer dimensions width height depth 323 mm 260 mm 86 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 221

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 221 power panel 300/400 user's manual v 2.10 4.10.2 temperature humidity diagram 4.10.3 dimensions figure 142: temperature humidity diagram - 4pp420.1043-75 figure 143: dimensions - 4pp420.1043-75 0 0 10 20 30 40 ...

  • Page 222

    222 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.10.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 223

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 223 power panel 300/400 user's manual v 2.10 4.11 device 4pp420.1043-b5 figure 145: front view - 4pp420.1043-b5 figure 146: rear view - 4pp420.1043-b5 compactflash slot (with latch) battery compartment sw1 (x16) s...

  • Page 224

    224 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.11.1 technical data features 4pp420.1043-b5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 225

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 225 power panel 300/400 user's manual v 2.10 features 4pp420.1043-b5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 226

    226 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.1043-b5 outer dimensions width height depth 323 mm 260 mm 108 mm front frame design membrane dark gray border around display light background gasket aluminum, natur...

  • Page 227

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 227 power panel 300/400 user's manual v 2.10 4.11.2 temperature humidity diagram 4.11.3 dimensions figure 147: temperature humidity diagram - 4pp420.1043-b5 figure 148: dimensions - 4pp420.1043-b5 0 0 10 20 30 40 ...

  • Page 228

    228 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.11.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 229

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 229 power panel 300/400 user's manual v 2.10 4.12 device 4pp420.1505-75 figure 150: front view - 4pp420.1505-75 figure 151: rear view - 4pp420.1505-75 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds ...

  • Page 230

    230 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.12.1 technical data features 4pp420.1505-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 231

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 231 power panel 300/400 user's manual v 2.10 features 4pp420.1505-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 232

    232 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.1505-75 outer dimensions width height depth 435 mm 330 mm 86 mm front frame design membrane dark gray border around display light background gasket aluminum, natura...

  • Page 233

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 233 power panel 300/400 user's manual v 2.10 4.12.2 temperature humidity diagram 4.12.3 dimensions figure 152: temperature humidity diagram - 4pp420.1505-75 figure 153: dimensions - 4pp420.1505-75 0 0 10 20 30 40 ...

  • Page 234

    234 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.12.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 235

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 235 power panel 300/400 user's manual v 2.10 4.13 device 4pp420.1505-b5 figure 155: front view - 4pp420.1505-b5 figure 156: rear view - 4pp420.1505-b5 compactflash slot (with latch) sw1 (x16) sw2 (x1) status leds ...

  • Page 236

    236 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.13.1 technical data features 4pp420.1505-b5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 237

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 237 power panel 300/400 user's manual v 2.10 features 4pp420.1505-b5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 238

    238 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420.1505-b5 outer dimensions width height depth 435 mm 330 mm 109 mm front frame design membrane dark gray border around display light background gasket aluminum, natur...

  • Page 239

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 239 power panel 300/400 user's manual v 2.10 4.13.2 temperature humidity diagram 4.13.3 dimensions figure 157: temperature humidity diagram - 4pp420.1505-b5 figure 158: dimensions - 4pp420.1505-b5 0 0 10 20 30 40 ...

  • Page 240

    240 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.13.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 241

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 241 power panel 300/400 user's manual v 2.10 4.14 device 4pp451.0571-45 figure 160: front view - 4pp451.0571-45 figure 161: rear view - 4pp451.0571-45 keys can be labeled using legend strips keys can be labeled us...

  • Page 242

    242 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.14.1 technical data features 4pp451.0571-45 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 243

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 243 power panel 300/400 user's manual v 2.10 features 4pp451.0571-45 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 244

    244 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.0571-45 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 212 mm 245 mm 76 mm front frame design membrane dark gray border aroun...

  • Page 245

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 245 power panel 300/400 user's manual v 2.10 4.14.2 temperature humidity diagram 4.14.3 dimensions figure 162: temperature humidity diagram - 4pp451.0571-45 figure 163: dimensions - 4pp451.0571-45 0 0 10 20 30 40 ...

  • Page 246

    246 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.14.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 247

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 247 power panel 300/400 user's manual v 2.10 4.15 device 4pp451.0571-65 figure 165: front view - 4pp451.0571-65 figure 166: rear view - 4pp451.0571-65 keys can be labeled using legend strips keys can be labeled us...

  • Page 248

    248 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.15.1 technical data features 4pp451.0571-65 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 249

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 249 power panel 300/400 user's manual v 2.10 features 4pp451.0571-65 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 250

    250 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.0571-65 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 212 mm 245 mm 76 mm front frame design membrane dark gray border aroun...

  • Page 251

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 251 power panel 300/400 user's manual v 2.10 4.15.2 temperature humidity diagram 4.15.3 dimensions figure 167: temperature humidity diagram - 4pp451.0571-65 figure 168: dimensions - 4pp451.0571-65 0 0 10 20 30 40 ...

  • Page 252

    252 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.15.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 253

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 253 power panel 300/400 user's manual v 2.10 4.16 device 4pp451.0571-75 figure 170: front view - 4pp451.0571-75 figure 171: rear view - 4pp451.0571-75 keys can be labeled using legend strips keys can be labeled us...

  • Page 254

    254 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.16.1 technical data features 4pp451.0571-75 4pp451.0571-75 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fp...

  • Page 255

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 255 power panel 300/400 user's manual v 2.10 features 4pp451.0571-75 4pp451.0571-75 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full spee...

  • Page 256

    256 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.0571-75 4pp451.0571-75 ≥ rev. D0 power supply rated voltage rated current starting current power consumption electrical isolation 18 - 30 vdc 0.63 a max. 1.2 a typi...

  • Page 257

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 257 power panel 300/400 user's manual v 2.10 4.16.2 temperature humidity diagram 5) at +25°c ambient temperature. Reducing the brightness by 50% can result in an approximate 50% increase of the half-brightness tim...

  • Page 258

    258 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.16.3 dimensions figure 173: dimensions - 4pp451.0571-75 2.9 8 196 212 245 67 6 9.9 140 82 97 13.2 28 3 nominal measurement general tolerance from range din iso 2768 medium up to 6 mm over 6 to 30 ...

  • Page 259

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 259 power panel 300/400 user's manual v 2.10 4.16.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining c...

  • Page 260

    260 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.17 device 4pp451.0571-85 figure 175: front view - 4pp451.0571-85 figure 176: rear view - 4pp451.0571-85 keys can be labeled using legend strips keys can be labeled using legend strips compactflash...

  • Page 261

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 261 power panel 300/400 user's manual v 2.10 4.17.1 technical data features 4pp451.0571-85 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point uni...

  • Page 262

    262 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp451.0571-85 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (480 mbit/s) 4) type a max....

  • Page 263

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 263 power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.0571-85 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 212 mm 245 mm 98 mm front frame design m...

  • Page 264

    264 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.17.2 temperature humidity diagram 4.17.3 dimensions figure 177: temperature humidity diagram - 4pp451.0571-85 figure 178: dimensions - 4pp451.0571-85 0 0 10 20 30 40 50 60 70 80 90 -80 -70 -60 -50...

  • Page 265

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 265 power panel 300/400 user's manual v 2.10 4.17.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining c...

  • Page 266

    266 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.18 device 4pp451.0571-b5 figure 180: front view - 4pp451.0571-b5 figure 181: back view - 4pp451.0571-b5 keys can be labeled using legend strips keys can be labeled using legend strips compactflash...

  • Page 267

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 267 power panel 300/400 user's manual v 2.10 4.18.1 technical data features 4pp451.0571-b5 4pp451.0571-b5 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2...

  • Page 268

    268 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp451.0571-b5 4pp451.0571-b5 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (4...

  • Page 269

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 269 power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.0571-b5 4pp451.0571-b5 ≥ rev. D0 power supply rated voltage rated current starting current power consumption electrical isolation 18 -...

  • Page 270

    270 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.18.2 temperature humidity diagram 5) at +25°c ambient temperature. Reducing the brightness by 50% can result in an approximate 50% increase of the half-brightness time. 6) the functions of the key...

  • Page 271

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 271 power panel 300/400 user's manual v 2.10 4.18.3 dimensions figure 183: dimensions - 4pp451.0571-b5 212 24 5 6 89 9.9 14 0 82 97 13 .2 28 3 196 2.9 8 nominal measurement general tolerance from range din iso 276...

  • Page 272

    272 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.18.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 273

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 273 power panel 300/400 user's manual v 2.10 4.19 device 4pp451.1043-75 figure 185: front view - 4pp451.1043-75 figure 186: rear view - 4pp451.1043-75 keys can be labeled using legend strips keys can be labeled us...

  • Page 274

    274 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.19.1 technical data features 4pp451.1043-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 275

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 275 power panel 300/400 user's manual v 2.10 features 4pp451.1043-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 276

    276 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.1043-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 323 mm 358 mm 86 mm front frame design membrane dark gray border aroun...

  • Page 277

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 277 power panel 300/400 user's manual v 2.10 4.19.2 temperature humidity diagram 4.19.3 dimensions figure 187: temperature humidity diagram - 4pp451.1043-75 figure 188: dimensions - 4pp451.1043-75 0 0 10 20 30 40 ...

  • Page 278

    278 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.19.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.1...

  • Page 279

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 279 power panel 300/400 user's manual v 2.10 4.20 device 4pp451.1043-b5 figure 190: front view - 4pp451.1043-b5 figure 191: rear view - 4pp451.1043-b5 keys can be labeled using legend strips keys can be labeled us...

  • Page 280

    280 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.20.1 technical data features 4pp451.1043-b5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 281

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 281 power panel 300/400 user's manual v 2.10 features 4pp451.1043-b5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 282

    282 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp451.1043-b5 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 323 mm 358 mm 108 mm front frame design membrane dark gray border arou...

  • Page 283

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 283 power panel 300/400 user's manual v 2.10 4.20.2 temperature humidity diagram 4.20.3 dimensions figure 192: temperature humidity diagram - 4pp451.1043-b5 figure 193: dimensions - 4pp451.1043-b5 0 0 10 20 30 40 ...

  • Page 284

    284 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.20.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 285

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 285 power panel 300/400 user's manual v 2.10 4.21 device 4pp452.0571-45 figure 195: front view - 4pp452.0571-45 figure 196: rear view - 4pp452.0571-45 keys can be labeled using legend strips compactflash slot (wit...

  • Page 286

    286 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.21.1 technical data features 4pp452.0571-45 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 287

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 287 power panel 300/400 user's manual v 2.10 features 4pp452.0571-45 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 288

    288 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp452.0571-45 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 302 mm 187 mm 76 mm front frame design membrane dark gray border aroun...

  • Page 289

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 289 power panel 300/400 user's manual v 2.10 4.21.2 temperature humidity diagram 4.21.3 dimensions figure 197: temperature humidity diagram - 4pp452.0571-45 figure 198: dimensions - 4pp452.0571-45 0 0 10 20 30 40 ...

  • Page 290

    290 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.21.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 291

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 291 power panel 300/400 user's manual v 2.10 4.22 device 4pp452.0571-65 figure 200: front view - 4pp452.0571-65 figure 201: rear view - 4pp452.0571-65 keys can be labeled using legend strips compactflash slot (wit...

  • Page 292

    292 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.22.1 technical data features 4pp452.0571-65 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 293

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 293 power panel 300/400 user's manual v 2.10 features 4pp452.0571-65 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 294

    294 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp452.0571-65 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 302 mm 187 mm 76 mm front frame design membrane dark gray border aroun...

  • Page 295

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 295 power panel 300/400 user's manual v 2.10 4.22.2 temperature humidity diagram 4.22.3 dimensions figure 202: temperature humidity diagram - 4pp452.0571-65 figure 203: dimensions - 4pp452.0571-65 0 0 10 20 30 40 ...

  • Page 296

    296 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.22.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 297

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 297 power panel 300/400 user's manual v 2.10 4.23 device 4pp452.0571-75 figure 205: front view - 4pp452.0571-75 figure 206: rear view - 4pp452.0571-75 keys can be labeled using legend strips compactflash slot (wit...

  • Page 298

    298 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.23.1 technical data features 4pp452.0571-75 4pp452.0571-75 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fp...

  • Page 299

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 299 power panel 300/400 user's manual v 2.10 features 4pp452.0571-75 4pp452.0571-75 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full spee...

  • Page 300

    300 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp452.0571-75 4pp452.0571-75 ≥ rev. D0 power supply rated voltage rated current starting current power consumption electrical isolation 18 - 30 vdc 0.63 a max. 1.2 a typi...

  • Page 301

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 301 power panel 300/400 user's manual v 2.10 4.23.2 temperature humidity diagram 5) at +25°c ambient temperature. Reducing the brightness by 50% can result in an approximate 50% increase of the half-brightness tim...

  • Page 302

    302 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.23.3 dimensions figure 208: dimensions - 4pp452.0571-75 196 286 302 187 171 82 31 8 67 47 11.9 6 2.9 8 3 nominal measurement general tolerance from range din iso 2768 medium up to 6 mm over 6 to 3...

  • Page 303

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 303 power panel 300/400 user's manual v 2.10 4.23.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining c...

  • Page 304

    304 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.24 device 4pp452.0571-b5 figure 210: front view - 4pp452.0571-b5 figure 211: rear view - 4pp452.0571-b5 keys can be labeled using legend strips compactflash slot (with latch) sw1 (x16) sw2 (x1) st...

  • Page 305

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 305 power panel 300/400 user's manual v 2.10 4.24.1 technical data features 4pp452.0571-b5 4pp452.0571-b5 ≥ rev. D0 boot loader / operating system automation runtime processor type expanded command set l1 cache l2...

  • Page 306

    306 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 features 4pp452.0571-b5 4pp452.0571-b5 ≥ rev. D0 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high speed (4...

  • Page 307

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 307 power panel 300/400 user's manual v 2.10 electrical characteristics 4pp452.0571-b5 4pp452.0571-b5 ≥ rev. D0 power supply rated voltage rated current starting current power consumption electrical isolation 18 -...

  • Page 308

    308 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.24.2 temperature humidity diagram 5) at +25°c ambient temperature. Reducing the brightness by 50% can result in an approximate 50% increase of the half-brightness time. 6) the functions of the key...

  • Page 309

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 309 power panel 300/400 user's manual v 2.10 4.24.3 dimensions figure 213: dimensions - 4pp452.0571-b5 nominal measurement general tolerance from range din iso 2768 medium up to 6 mm over 6 to 30 mm over 30 to 120...

  • Page 310

    310 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.24.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 311

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 311 power panel 300/400 user's manual v 2.10 4.25 device 4pp452.1043-75 figure 215: front view - 4pp452.1043-75 figure 216: rear view - 4pp452.1043-75 keys can be labeled using legend strips compactflash slot (wit...

  • Page 312

    312 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.25.1 technical data features 4pp452.1043-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 313

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 313 power panel 300/400 user's manual v 2.10 features 4pp452.1043-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 314

    314 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp452.1043-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 423 mm 288 mm 86 mm front frame design membrane dark gray border aroun...

  • Page 315

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 315 power panel 300/400 user's manual v 2.10 4.25.2 temperature humidity diagram 4.25.3 dimensions figure 217: temperature humidity diagram - 4pp452.1043-75 figure 218: dimensions - 4pp452.1043-75 0 0 10 20 30 40 ...

  • Page 316

    316 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.25.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 317

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 317 power panel 300/400 user's manual v 2.10 4.26 device 4pp480.1043-75 figure 220: front view - 4pp480.1043-75 figure 221: rear view - 4pp480.1043-75 keys can be labeled using legend strips keys can be labeled us...

  • Page 318

    318 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.26.1 technical data features 4pp480.1043-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 319

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 319 power panel 300/400 user's manual v 2.10 features 4pp480.1043-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 320

    320 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp480.1043-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 323 mm 260 mm 86 mm front frame design membrane dark gray border aroun...

  • Page 321

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 321 power panel 300/400 user's manual v 2.10 4.26.2 temperature humidity diagram 4.26.3 dimensions figure 222: temperature humidity diagram - 4pp480.1043-75 figure 223: dimensions - 4pp480.1043-75 0 0 10 20 30 40 ...

  • Page 322

    322 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.26.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 323

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 323 power panel 300/400 user's manual v 2.10 4.27 device 4pp480.1505-75 figure 225: front view - 4pp480.1505-75 figure 226: rear view - 4pp480.1505-75 keys can be labeled using legend strips keys can be labeled us...

  • Page 324

    324 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.27.1 technical data features 4pp480.1505-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 325

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 325 power panel 300/400 user's manual v 2.10 features 4pp480.1505-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 326

    326 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp480.1505-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 435 mm 330 mm 87 mm front frame design membrane dark gray border aroun...

  • Page 327

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 327 power panel 300/400 user's manual v 2.10 4.27.2 temperature humidity diagram 4.27.3 dimensions figure 227: temperature humidity diagram - 4pp480.1505-75 figure 228: dimensions - 4pp480.1505-75 0 0 10 20 30 40 ...

  • Page 328

    328 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.27.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 329

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 329 power panel 300/400 user's manual v 2.10 4.28 device 4pp480.1505-b5 figure 230: front view - 4pp480.1505-b5 figure 231: rear view - 4pp480.1505-b5 keys can be labeled using legend strips keys can be labeled us...

  • Page 330

    330 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.28.1 technical data features 4pp480.1505-b5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 331

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 331 power panel 300/400 user's manual v 2.10 features 4pp480.1505-b5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 332

    332 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp480.1505-b5 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 435 mm 330 mm 109 mm front frame design membrane dark gray border arou...

  • Page 333

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 333 power panel 300/400 user's manual v 2.10 4.28.2 temperature humidity diagram 4.28.3 dimensions figure 232: temperature humidity diagram - 4pp480.1505-b5 figure 233: dimensions - 4pp480.1505-b5 0 0 10 20 30 40 ...

  • Page 334

    334 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.28.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 335

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 335 power panel 300/400 user's manual v 2.10 4.29 device 4pp481.1043-75 figure 235: front view - 4pp481.1043-75 figure 236: rear view - 4pp481.1043-75 keys can be labeled using legend strips keys can be labeled us...

  • Page 336

    336 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.29.1 technical data features 4pp481.1043-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 337

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 337 power panel 300/400 user's manual v 2.10 features 4pp481.1043-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 338

    338 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp481.1043-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 323 mm 358 mm 86 mm front frame design membrane dark gray border aroun...

  • Page 339

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 339 power panel 300/400 user's manual v 2.10 4.29.2 temperature humidity diagram 4.29.3 dimensions figure 237: temperature humidity diagram - 4pp481.1043-75 figure 238: dimensions - 4pp481.1043-75 0 0 10 20 30 40 ...

  • Page 340

    340 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.29.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.2...

  • Page 341

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 341 power panel 300/400 user's manual v 2.10 4.30 device 4pp481.1043-b5 figure 240: front view - 4pp481.1043-b5 figure 241: rear view - 4pp481.1043-b5 keys can be labeled using legend strips keys can be labeled us...

  • Page 342

    342 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.30.1 technical data features 4pp481.1043-b5 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 343

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 343 power panel 300/400 user's manual v 2.10 features 4pp481.1043-b5 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 344

    344 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp481.1043-b5 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 323 mm 358 mm 108 mm front frame design membrane dark gray border arou...

  • Page 345

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 345 power panel 300/400 user's manual v 2.10 4.30.2 temperature humidity diagram 4.30.3 dimensions figure 242: temperature humidity diagram - 4pp481.1043-b5 figure 243: dimensions - 4pp481.1043-b5 0 0 10 20 30 40 ...

  • Page 346

    346 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.30.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.3...

  • Page 347

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 347 power panel 300/400 user's manual v 2.10 4.31 device 4pp481.1505-75 figure 245: front view - 4pp481.1505-75 figure 246: rear view - 4pp481.1505-75 keys can be labeled using legend strips keys can be labeled us...

  • Page 348

    348 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.31.1 technical data features 4pp481.1505-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 349

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 349 power panel 300/400 user's manual v 2.10 features 4pp481.1505-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 350

    350 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp481.1505-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 435 mm 430 mm 87 mm front frame design membrane dark gray border aroun...

  • Page 351

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 351 power panel 300/400 user's manual v 2.10 4.31.2 temperature humidity diagram 4.31.3 dimensions figure 247: temperature humidity diagram - 4pp481.1505-75 figure 248: dimensions - 4pp481.1505-75 0 0 10 20 30 40 ...

  • Page 352

    352 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.31.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.3...

  • Page 353

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 353 power panel 300/400 user's manual v 2.10 4.32 device 4pp482.1043-75 figure 250: front view - 4pp482.1043-75 figure 251: rear view - 4pp482.1043-75 keys can be labeled using legend strips compactflash slot (wit...

  • Page 354

    354 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.32.1 technical data features 4pp482.1043-75 boot loader / operating system automation runtime processor type expanded command set l1 cache l2 cache floating point unit (fpu) cooling method geode l...

  • Page 355

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 355 power panel 300/400 user's manual v 2.10 features 4pp482.1043-75 usb interface type amount transfer rate connection current load usb 1.1, usb 2.0 4) 2 low speed (1.5 mbit/s), full speed (12 mbit/s) to high spe...

  • Page 356

    356 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 electrical characteristics 4pp482.1043-75 bleeder resistance 0 Ω mechanical characteristics outer dimensions width height depth 423 mm 288 mm 86 mm front frame design membrane dark gray border aroun...

  • Page 357

    Technical data • power panel 400 with automation runtime chap ter 2 te chn ica l da ta 357 power panel 300/400 user's manual v 2.10 4.32.2 temperature humidity diagram 4.32.3 dimensions figure 252: temperature humidity diagram - 4pp482.1043-75 figure 253: dimensions - 4pp482.1043-75 0 0 10 20 30 40 ...

  • Page 358

    358 technical data • power panel 400 with automation runtime power panel 300/400 user's manual v 2.10 4.32.4 cutout installation the cutout hole is to be made according to the following dimensions for cutout installation. The device must be mounted using the retaining clips included in delivery. 4.3...

  • Page 359

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 359 power panel 300/400 user's manual v 2.10 5. Power panel light / compact power panel 400 light / compact series devices have qvga operator panels with an integrated controller. Power panel 400 light devices are primarily i...

  • Page 360

    360 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 features 4pp420:0571 -l05 4pp420:0571 -l45 4pp420:0571 -l25 4pp420:0571 -l65 4pp420:0571 -l35 4pp420:0571 -l75 battery type removable lifespan backup capacitor (for changing battery) buffer time renata 950 mah ...

  • Page 361

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 361 power panel 300/400 user's manual v 2.10 features 4pp420:0571 -l05 4pp420:0571 -l45 4pp420:0571 -l25 4pp420:0571 -l65 4pp420:0571 -l35 4pp420:0571 -l75 display type diagonal colors resolution contrast viewing angle (see p...

  • Page 362

    362 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 mechanical characteristics 4pp420:0571 -l05 4pp420:0571 -l45 4pp420:0571 -l25 4pp420:0571 -l65 4pp420:0571 -l35 4pp420:0571 -l75 housing metal weight approx. 1.7 kg (without apci interface modules) environmenta...

  • Page 363

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 363 power panel 300/400 user's manual v 2.10 5.1.2 temperature humidity diagram - pp420 light lcd monochrome the following diagram is valid for the devices 4pp420:0571-l05 and 4pp420:0571-l45. 5.1.3 temperature humidity diagr...

  • Page 364

    364 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 5.1.4 technical data - power panel 420 compact features 4pp420:0571 -c05 4pp420:0571 -c45 4pp420:0571 -c25 4pp420:0571 -c65 4pp420:0571 -c35 4pp420:0571 -c75 boot loader / operating system automation runtime pr...

  • Page 365

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 365 power panel 300/400 user's manual v 2.10 features 4pp420:0571 -c05 4pp420:0571 -c45 4pp420:0571 -c25 4pp420:0571 -c65 4pp420:0571 -c35 4pp420:0571 -c75 usb interface type amount transfer rate connection current load usb 1...

  • Page 366

    366 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 electrical characteristics 4pp420:0571 -c05 4pp420:0571 -c45 4pp420:0571 -c25 4pp420:0571 -c65 4pp420:0571 -c35 4pp420:0571 -c75 power supply rated voltage rated current starting current power consumption elect...

  • Page 367

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 367 power panel 300/400 user's manual v 2.10 5.1.5 temperature humidity diagram - pp420 compact lcd monochrome the following diagram is valid for the devices 4pp420:0571-c05 and 4pp420:0571-c45. 4) the actual value depends on...

  • Page 368

    368 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 5.1.6 temperature humidity diagram - pp420 compact lcd color and tft color the following diagram is valid for the devices 4pp420:0571-c25, 4pp420:0571-c65, 4pp420:0571-c35 and 4pp420:0571-c75. Figure 258: tempe...

  • Page 369

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 369 power panel 300/400 user's manual v 2.10 5.2 power panel 451 light / compact 5.2.1 technical data - power panel 451 light features 4pp451:0571-l25 4pp451:0571-l65 4pp451:0571-l35 4pp451:0571-l75 boot loader / operating sy...

  • Page 370

    370 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 features 4pp451:0571-l25 4pp451:0571-l65 4pp451:0571-l35 4pp451:0571-l75 serial interface type uart transfer rate connection rs232, modem-capable, not electrically isolated 16c550 compatible, 16-byte fifo max. ...

  • Page 371

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 371 power panel 300/400 user's manual v 2.10 features 4pp451:0571-l25 4pp451:0571-l65 4pp451:0571-l35 4pp451:0571-l75 keys/led 6) function keys soft keys cursor keys number block other keys key lifespan led brightness 16 with...

  • Page 372

    372 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 5.2.2 temperature humidity diagram environmental characteristics 4pp451:0571-l25 4pp451:0571-l65 4pp451:0571-l35 4pp451:0571-l75 protection type ip20 back side (only with installed compactflash card, inserted a...

  • Page 373

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 373 power panel 300/400 user's manual v 2.10 5.2.3 technical data - power panel 451 compact features 4pp451:0571-c25 4pp451:0571-c65 4pp451:0571-c35 4pp451:0571-c75 boot loader / operating system automation runtime processor ...

  • Page 374

    374 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 features 4pp451:0571-c25 4pp451:0571-c65 4pp451:0571-c35 4pp451:0571-c75 serial interface type uart transfer rate connection rs232, modem-capable, not electrically isolated 16c550 compatible, 16-byte fifo max. ...

  • Page 375

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 375 power panel 300/400 user's manual v 2.10 features 4pp451:0571-c25 4pp451:0571-c65 4pp451:0571-c35 4pp451:0571-c75 keys/led 6) function keys soft keys cursor keys number block other keys key lifespan led brightness 16 with...

  • Page 376

    376 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 5.2.4 temperature humidity diagram environmental characteristics 4pp451:0571-c25 4pp451:0571-c65 4pp451:0571-c35 4pp451:0571-c75 protection type ip20 back side (only with installed compactflash card, inserted a...

  • Page 377

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 377 power panel 300/400 user's manual v 2.10 5.3 power panel 452 light / compact 5.3.1 technical data - power panel 452 light features 4pp452:0571-l25 4pp452:0571-l65 4pp452:0571-l35 4pp452:0571-l75 boot loader / operating sy...

  • Page 378

    378 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 features 4pp452:0571-l25 4pp452:0571-l65 4pp452:0571-l35 4pp452:0571-l75 serial interface type uart transfer rate connection rs232, modem-capable, not electrically isolated 16c550 compatible, 16-byte fifo max. ...

  • Page 379

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 379 power panel 300/400 user's manual v 2.10 features 4pp452:0571-l25 4pp452:0571-l65 4pp452:0571-l35 4pp452:0571-l75 keys/led 6) function keys soft keys cursor keys number block other keys key lifespan led brightness 28 with...

  • Page 380

    380 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 5.3.2 temperature humidity diagram environmental characteristics 4pp452:0571-l25 4pp452:0571-l65 4pp452:0571-l35 4pp452:0571-l75 protection type ip20 back side (only with installed compactflash card, inserted a...

  • Page 381

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 381 power panel 300/400 user's manual v 2.10 5.3.3 technical data - power panel 452 compact features 4pp452:0571-c25 4pp452:0571-c65 4pp452:0571-c35 4pp452:0571-c75 boot loader / operating system automation runtime processor ...

  • Page 382

    382 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 features 4pp452:0571-c25 4pp452:0571-c65 4pp452:0571-c35 4pp452:0571-c75 serial interface type uart transfer rate connection rs232, modem-capable, not electrically isolated 16c550 compatible, 16-byte fifo max. ...

  • Page 383

    Technical data • power panel light / compact chap ter 2 te chn ica l da ta 383 power panel 300/400 user's manual v 2.10 features 4pp452:0571-c25 4pp452:0571-c65 4pp452:0571-c35 4pp452:0571-c75 keys/led 6) function keys soft keys cursor keys number block other keys key lifespan led brightness 28 with...

  • Page 384

    384 technical data • power panel light / compact power panel 300/400 user's manual v 2.10 5.3.4 temperature humidity diagram environmental characteristics 4pp452:0571-c25 4pp452:0571-c65 4pp452:0571-c35 4pp452:0571-c75 protection type ip20 back side (only with installed compactflash card, inserted a...

  • Page 385: 6. Block Diagram

    Technical data • block diagram chap ter 2 te chn ica l da ta 385 power panel 300/400 user's manual v 2.10 6. Block diagram the following block diagrams show the simplified system unit structure with a cpu board. 6.1 power panel 300 (with no apci slots) figure 263: block diagram - power panel 300 + -...

  • Page 386

    386 technical data • block diagram power panel 300/400 user's manual v 2.10 6.2 power panel 400 with 1 apci slot figure 264: block diagram - power panel 400 with 1 apci slot + - rxd, txd 5v rxd ,txd , r t s , cts , dtr, dsr, dcd , ri rxd, txd, rts, cts rs232 int. 4-pin bios flash 2 mb jtag ac97 head...

  • Page 387

    Technical data • block diagram chap ter 2 te chn ica l da ta 387 power panel 300/400 user's manual v 2.10 6.3 power panel 400 with 2 apci slots figure 265: block diagram - power panel 400 with 2 apci slots + - rxd, txd 5v rxd ,txd , r t s , cts , dtr, dsr, dcd , ri rxd, txd, rts, cts rs232 int. 4-pi...

  • Page 388

    388 technical data • block diagram power panel 300/400 user's manual v 2.10

  • Page 389: Chapter 3 • Commissioning

    Commissioning • mounting instructions chapter 3 com m is sio ning 389 power panel 300/400 user's manual v 2.10 chapter 3 • commissioning 1. Mounting instructions • the power panel must be mounted using the retaining clips included in delivery. Depending on the power panel version a corresponding num...

  • Page 390

    390 commissioning • mounting instructions power panel 300/400 user's manual v 2.10 side view rear view table 135: space for air circulation at least 80 mm air flo w at least 80 mm air flo w at least 80 mm at least 40 mm at least 40 mm.

  • Page 391: 2. Mounting Orientation

    Commissioning • mounting orientation chapter 3 com m is sio ning 391 power panel 300/400 user's manual v 2.10 2. Mounting orientation the following diagram displays the specified mounting orientation for the power panel device. The mounting orientation applies to all power panel versions (with/witho...

  • Page 392: Caution!

    392 commissioning • mounting orientation power panel 300/400 user's manual v 2.10 mounting orientation -45° mounting orientation +45° table 137: mounting orientation -45° and +45°. Caution! The maximum permitted ambient temperature can be found in the technical data for the respective power panel de...

  • Page 393: 3. Touch Screen Calibration

    Commissioning • touch screen calibration chapter 3 com m is sio ning 393 power panel 300/400 user's manual v 2.10 3. Touch screen calibration b&r touch screen devices are equipped with a touch controller, which supports hardware calibration. This means that the devices are pre-calibrated from stock ...

  • Page 394: 4. Screen Rotation

    394 commissioning • screen rotation power panel 300/400 user's manual v 2.10 4. Screen rotation it is possible to rotate the image content by 90° using the graphic driver's screen rotation function (must support the function). 4.1 windows xp embedded the graphics driver does not support the screen r...

  • Page 395

    Commissioning • user tips for increasing the display lifespan chapter 3 com m is sio ning 395 power panel 300/400 user's manual v 2.10 5. User tips for increasing the display lifespan 5.1 backlight the lifespan of the backlight is specified in "half brightness time". An operating time of 50,000 hour...

  • Page 396

    396 commissioning • user tips for increasing the display lifespan power panel 300/400 user's manual v 2.10

  • Page 397: Chapter 4 • Software

    Software • power panel 300 with bios ch apte r 4 soft w are 397 power panel 300/400 user's manual v 2.10 chapter 4 • software 1. Power panel 300 with bios 1.1 general information bios stands for "basic input output system". It is the most basic standardized communication between the user and the sys...

  • Page 398

    398 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.2 summary screen to deactivate this summary screen for vga, svga and xga variants, see "miscellaneous configuration" on page 416. To deactivate this summary screen for qvga variants, see "miscellaneous configuration"...

  • Page 399: Warning!

    Software • power panel 300 with bios ch apte r 4 soft w are 399 power panel 300/400 user's manual v 2.10 to make changes in the bios setup, the del key must be pressed when booting the power panel device as soon as the following message appears in the upper margin of the display (during the post): i...

  • Page 400

    400 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 - (minus) decreases the numerical value or selects the previous parameter value. + (plus) increases the numerical value or selects the next parameter value. Key function table 138: bios-relevant keys (forts.).

  • Page 401: Information:

    Software • power panel 300 with bios ch apte r 4 soft w are 401 power panel 300/400 user's manual v 2.10 1.3 bios settings for vga, svga and xga power panel devices 1.3.1 main menu immediately after the del button is pressed during startup, the main bios setup menu appears. The individual menu items...

  • Page 402

    402 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.2 time the currently configured system time is displayed here. The time is buffered by a battery (cmos battery) after the power panel device has been switched off. By selecting the item "time" and the confirming by...

  • Page 403: Information:

    Software • power panel 300 with bios ch apte r 4 soft w are 403 power panel 300/400 user's manual v 2.10 • 13:00:00 - confirm with enter • 01:00:00 pm - confirm with enter • 13: - confirm with enter 1.3.3 date the current system date is displayed here. The date is buffered by a battery (cmos battery...

  • Page 404

    404 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.4 motherboard device configuration figure 273: motherboard device configuration shortcut bios setup menu function a drive configuration settings for the floppy drive and compactflash card. B i/o configuration confi...

  • Page 405

    Software • power panel 300 with bios ch apte r 4 soft w are 405 power panel 300/400 user's manual v 2.10 motherboard device configuration - drive configuration figure 274: motherboard device configuration - drive configuration bios setting meaning setting options effect ide bios support displays the...

  • Page 406

    406 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 motherboard device configuration - i/o configuration figure 275: motherboard device configuration - i/o configuration bios setting meaning setting options effect com a configures the uart address range and the correspo...

  • Page 407

    Software • power panel 300 with bios ch apte r 4 soft w are 407 power panel 300/400 user's manual v 2.10 motherboard device configuration - video and flat panel com d configures the uart address range and the corresponding interrupt for the touch controller. Information: two ports cannot use the sam...

  • Page 408

    408 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 motherboard device configuration - pci configuration contrast setting for the contrast of the display. Auto the optimal contrast is automatically configured using the factory settings. A contrast value between 100% and...

  • Page 409

    Software • power panel 300 with bios ch apte r 4 soft w are 409 power panel 300/400 user's manual v 2.10 motherboard device configuration - usb configuration pci intd# irq setting for the usb interface. Disabled no irq is reserved. 3, 4, 5, 6, 7, 9, 10, 11, 12, 14 or 15 manual configuration of the i...

  • Page 410

    410 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 motherboard device configuration - thermal configuration overcurrent reporting this function enables an automatic message this function enables an automatic error message to be sent to the system when the usb hub is ov...

  • Page 411: Warning!

    Software • power panel 300 with bios ch apte r 4 soft w are 411 power panel 300/400 user's manual v 2.10 1.3.5 memory and cache optimization close submenu close submenu enter closes the submenu. Warning! The parameters in this screen are for system designers, service personnel, and technically compe...

  • Page 412

    412 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 figure 280: memory and cache optimization bios setting meaning setting options effect cache mode using cache mode, write accesses are determined on the cache. Write back the data is only written in the main memory if n...

  • Page 413

    Software • power panel 300 with bios ch apte r 4 soft w are 413 power panel 300/400 user's manual v 2.10 1.3.6 system clock/pll configuration figure 281: system clock/pll configuration bios setting meaning setting options effect clock determined by the processor clock can be set with this option. H/...

  • Page 414

    414 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.7 power management figure 282: power management bios setting meaning setting options effect bios pm at boot power management is already enabled in the boot phase. Enabled enables this function. Disabled disables th...

  • Page 415

    Software • power panel 300 with bios ch apte r 4 soft w are 415 power panel 300/400 user's manual v 2.10 1.3.8 device information figure 283: device information bios setting meaning setting options effect mtxc fpga the fpga firmware version is displayed here. None - mtcx px32 the mtcx firmware versi...

  • Page 416

    416 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.9 miscellaneous configuration user id displays the user id. This 8 digit hex value can be freely assigned by the user (e.G. To give the device a unique id) and can only be changed with using the "b&r control center...

  • Page 417

    Software • power panel 300 with bios ch apte r 4 soft w are 417 power panel 300/400 user's manual v 2.10 boot logo timeout defines the duration of the "press del for setup" message on the display and how much time the user has to change to the bios configuration. Information: by pressing any key the...

  • Page 418

    418 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.10 boot order figure 285: boot order xpressrom setup f1/alt+h:show help esc:exit alt+q:go to main menu enter:select +/-:choice boot order configuration 1. Usb floppy disk 2. Usb cd-rom drive 3 cf card info . Hard d...

  • Page 419

    Software • power panel 300 with bios ch apte r 4 soft w are 419 power panel 300/400 user's manual v 2.10 bios setting meaning setting options effect boot order configuration configures the order in which memory media is booted. If two identical devices are selected, a conflict warning is displayed. ...

  • Page 420

    420 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.11 load defaults under this bios menu item (shortcut "l"), by pressing any key you can load the values that were set at the time bios setup was opened. All changes made up to that point are lost as a result. Restor...

  • Page 421

    Software • power panel 300 with bios ch apte r 4 soft w are 421 power panel 300/400 user's manual v 2.10 1.3.12 save values without exit the bios values are saved using this menu item (shortcut "s") by pressing any key. The user can then make additional settings or exit bios setup. Figure 287: save ...

  • Page 422: Information:

    422 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.3.13 exit without save bios setup can be exited by selecting "yes" under this menu item (shortcut "q") without saving any changes that might have been made. The system is then automatically restarted. Figure 288: exi...

  • Page 423: Information:

    Software • power panel 300 with bios ch apte r 4 soft w are 423 power panel 300/400 user's manual v 2.10 1.3.14 save values and exit if "yes" is selected under this menu item (x shortcut), the system saves the settings, automatically exits bios setup, and reboots the system. Figure 289: save values ...

  • Page 424: Information:

    424 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4 bios settings for qvga power panel devices 1.4.1 main menu immediately after the del button is pressed during startup, the main bios setup menu appears. The individual menu items are explained in detail in the foll...

  • Page 425: Information:

    Software • power panel 300 with bios ch apte r 4 soft w are 425 power panel 300/400 user's manual v 2.10 1.4.2 time the currently configured system time is displayed here. The time is buffered by a battery (cmos battery) after the power panel device has been switched off. By selecting the item "time...

  • Page 426: Information:

    426 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.3 date the current system date is displayed here. The date is buffered by a battery (cmos battery) after the power panel device has been switched off. By selecting the item "date" and the confirming by pressing ent...

  • Page 427

    Software • power panel 300 with bios ch apte r 4 soft w are 427 power panel 300/400 user's manual v 2.10 1.4.4 motherboard device configuration figure 293: motherboard device configuration shortcut bios setup menu function a drive configuration settings for the floppy drive and compactflash card. B ...

  • Page 428

    428 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 motherboard device configuration - drive configuration figure 294: motherboard device configuration - drive configuration bios setting meaning setting options effect ide bios support displays the ide configuration of t...

  • Page 429

    Software • power panel 300 with bios ch apte r 4 soft w are 429 power panel 300/400 user's manual v 2.10 motherboard device configuration - i/o configuration figure 295: motherboard device configuration - i/o configuration bios setting meaning setting options effect com a configures the uart address...

  • Page 430

    430 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 motherboard device configuration - video and flat panel com d configures the uart address range and the corresponding interrupt for the touch controller. Information: two ports cannot use the same address range and int...

  • Page 431

    Software • power panel 300 with bios ch apte r 4 soft w are 431 power panel 300/400 user's manual v 2.10 motherboard device configuration - pci configuration contrast setting for the contrast of the display. Information: contrast settings can only be configured for passive displays. If the mode/node...

  • Page 432

    432 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 motherboard device configuration - usb configuration pci intc# activates irq for apci slot 2. First irq for apci slot 2 and irq for irq for apci slot 1. Disabled no irq is reserved. 3, 4, 5, 6, 7, 9, 10, 11, 12, 14 or ...

  • Page 433

    Software • power panel 300 with bios ch apte r 4 soft w are 433 power panel 300/400 user's manual v 2.10 motherboard device configuration - thermal configuration overcurrent reporting this function enables an automatic message this function enables an automatic error message to be sent to the system...

  • Page 434: Warning!

    434 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.5 memory and cache optimization warning! The parameters in this screen are for system designers, service personnel, and technically competent users only. Only modify those settings that you completely understand. I...

  • Page 435

    Software • power panel 300 with bios ch apte r 4 soft w are 435 power panel 300/400 user's manual v 2.10 1.4.6 system clock/pll configuration refresh rate the refresh cycle can be set here. Information: enter the clock frequency, the chipset does the rest. Auto value selected automatically. 15 μs, 3...

  • Page 436

    436 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.7 power management figure 302: power management bios setting meaning setting options effect bios pm at boot power management is already enabled in the boot phase. Enabled enables this function. Disabled disables th...

  • Page 437

    Software • power panel 300 with bios ch apte r 4 soft w are 437 power panel 300/400 user's manual v 2.10 1.4.8 device information figure 303: device information bios setting meaning setting options effect mtxc fpga the fpga firmware version is displayed here. None - mtcx px32 the mtcx firmware versi...

  • Page 438

    438 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.9 miscellaneous configuration eth the mac address of the ethernet interface is displayed here. None - figure 304: miscellaneous configuration bios setting meaning setting options effect boot logo 1) displays a boot...

  • Page 439

    Software • power panel 300 with bios ch apte r 4 soft w are 439 power panel 300/400 user's manual v 2.10 summary timeout defines how long the summary screen is displayed. Information: can be resumed before the timeout expires by pressing any button. 0 no waiting. 1-65535 [milliseconds] the manually ...

  • Page 440

    440 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.10 boot order figure 305: boot order boot order boot order configuration 2. Usb cd-rom drive 3. Hard drive 4. Usb hard/flash drv. Cf card info >>1. Usb floppy disk model:no cf card cap.: phy.: log.: xpressrom setup.

  • Page 441

    Software • power panel 300 with bios ch apte r 4 soft w are 441 power panel 300/400 user's manual v 2.10 bios setting meaning setting options effect boot order configuration configures the order in which memory media is booted. If two identical devices are selected, a conflict warning is displayed. ...

  • Page 442

    442 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.11 load defaults under this bios menu item (shortcut "l"), by pressing any key you can load the values that were set at the time bios setup was opened. All changes made up to that point are lost as a result. Restor...

  • Page 443

    Software • power panel 300 with bios ch apte r 4 soft w are 443 power panel 300/400 user's manual v 2.10 1.4.12 save values without exit the bios values are saved using this menu item (shortcut "s") by pressing any key. The user can then make additional settings or exit bios setup. 1.4.13 exit witho...

  • Page 444: Information:

    444 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.4.14 save values and exit if "yes" is selected under this menu item (x shortcut), the system saves the settings, automatically exits bios setup, and reboots the system. Information: if using a german keyboard, press ...

  • Page 445

    Software • power panel 300 with bios ch apte r 4 soft w are 445 power panel 300/400 user's manual v 2.10 1.5 bios default values the bios default values are the bios settings that were already configured when the ppc300 was delivered. The bios default values are identical in all variants (qvga, vga,...

  • Page 446

    446 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.5.2 memory and cache optimization 1.5.3 system clock/pll configuration 1.5.4 power management 1.5.5 device information this bios page is only provided for information purposes - therefore, no default bios values are ...

  • Page 447

    Software • power panel 300 with bios ch apte r 4 soft w are 447 power panel 300/400 user's manual v 2.10 1.5.6 miscellaneous configuration 1.5.7 boot order 1.5.8 restoring the default bios values in the event that the bios settings become incorrectly defined (e.G. Usb keyboard support disabled, cras...

  • Page 448

    448 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.6 software updates the following power panel device software and firmware can be updated: • bios (see page 456) • mtcx firmware (see page 459) • apci firmware (see page 461) • user boot logo (see page 462) current so...

  • Page 449

    Software • power panel 300 with bios ch apte r 4 soft w are 449 power panel 300/400 user's manual v 2.10 1.8 distribution of resources 1.8.1 ram address assignment 1.8.2 dma channel assignment ram address resource 00000000 - 000003ff interrupt vectors 00000400 - 000004ff bios data area 00000500 - 00...

  • Page 450

    450 software • power panel 300 with bios power panel 300/400 user's manual v 2.10 1.8.3 i/o address assignment in addition, the i/o addresses that were selected for additional functions (com, etc.) are assigned. I/o address resource 0000 - 000f dma controller channels 0-3 0020 - 0021 master programm...

  • Page 451

    Software • power panel 300 with bios ch apte r 4 soft w are 451 power panel 300/400 user's manual v 2.10 1.8.4 interrupt assignment interrupt resource irq 0 system timer irq 1 keyboard (legacy usb emulation) irq 2 2nd pic irq cascade irq 3 com2 1) 1) bios setup default setting irq 4 com1 1) irq 5 pc...

  • Page 452

    452 software • power panel 300/400 with automation runtime power panel 300/400 user's manual v 2.10 2. Power panel 300/400 with automation runtime 2.1 general information b&r automation runtime guarantees a uniform runtime environment for automation studio programs on all target systems. This ensure...

  • Page 453

    Software • power panel 300/400 with automation runtime ch apte r 4 soft w are 453 power panel 300/400 user's manual v 2.10 2.2 control and visualization with the power panel 300 device the visualization project runs on the power panel 300. Serial rs232 or ethernet tcp/ip provides the communication t...

  • Page 454

    454 software • power panel 300/400 with automation runtime power panel 300/400 user's manual v 2.10 2.3 power panel 400 with power panel 300 terminals control program and visualization run on the power panel 400. I/o peripherals and drives are connected via can, x2x and powerlink. Other power panel ...

  • Page 455

    Software • power panel 300/400 with automation runtime ch apte r 4 soft w are 455 power panel 300/400 user's manual v 2.10 2.4 software updates the following power panel automation runtime device software and firmware can be updated: • bios (see page 456) • mtcx firmware (see page 459) current softw...

  • Page 456: 3. Upgrade Information

    456 software • upgrade information power panel 300/400 user's manual v 2.10 3. Upgrade information 3.1 bios upgrade an upgrade might be necessary for the following reason: • to update implemented functions or to add newly implemented functions or components to the bios setup (information about chang...

  • Page 457: Information:

    Software • upgrade information ch apte r 4 soft w are 457 power panel 300/400 user's manual v 2.10 3.1.2 procedure the following steps should be carried out to upgrade or save bios: • create bootable media. • copy the contents of the *.Zip file to the bootable media. If the b&r upgrade was already a...

  • Page 458: Information:

    458 software • upgrade information power panel 300/400 user's manual v 2.10 • the system must be rebooted after a successful upgrade. Item menu item description 1 update bios all areas of bios are automatically upgraded (default after 5 seconds). Information: settings that have been changed in bios ...

  • Page 459: Information:

    Software • upgrade information ch apte r 4 soft w are 459 power panel 300/400 user's manual v 2.10 3.2 mtcx firmware upgrade (mtcx fpga, mtcx px32) a current mtcx firmware (mtcx fpga and mtcx px32) upgrade can be downloaded directly from the service portal on the b&r homepage ( www.Br-automation.Com...

  • Page 460: Warning!

    460 software • upgrade information power panel 300/400 user's manual v 2.10 concerning point 1: the mtcx firmware fpga and px32 is automatically updated (default after 5 sec). Concerning point 2: return to the shell (ms-dos). • select the desired action. • remove the bootable media and reboot the de...

  • Page 461: Information:

    Software • upgrade information ch apte r 4 soft w are 461 power panel 300/400 user's manual v 2.10 3.3 apci firmware upgrade disk a software tool for backing up or upgrading apci firmware can be downloaded directly from the service portal of the b&r homepage ( www.Br-automation.Com ). 3.3.1 procedur...

  • Page 462: Information:

    462 software • upgrade information power panel 300/400 user's manual v 2.10 • the system must be rebooted after a successful upgrade. 3.4 user boot logo upgrade disk a software tool for updating, backing up, or deleting the user boot logo can be downloaded directly from the service portal of the b&r...

  • Page 463: Information:

    Software • upgrade information ch apte r 4 soft w are 463 power panel 300/400 user's manual v 2.10 3.4.1 procedure the following steps should be taken to update, save or delete a user boot logo: • create bootable media. • copy the contents of the *.Zip file to the bootable media. If the b&r upgrade ...

  • Page 464: Information:

    464 software • upgrade information power panel 300/400 user's manual v 2.10 • the system must be rebooted after a successful upgrade. • in the bios cmos setup, the display of the boot logo must be set from "no" to "yes" (see section 1.3.9 "miscellaneous configuration" on page 416). 3.4.2 guidelines ...

  • Page 465

    Software • upgrade information ch apte r 4 soft w are 465 power panel 300/400 user's manual v 2.10 3.5 creating a dos boot diskette in windows xp • place an empty 1.44 mb hd diskette in the disk drive. • open windows explorer. • right-click on the 3½" floppy icon and select "format...". • then selec...

  • Page 466

    466 software • upgrade information power panel 300/400 user's manual v 2.10 after creating the startup disk, some of the files must be deleted because of the size of the update. When doing this, all files (hidden, system files, etc.) must be shown on the diskette. In explorer, go to the "tools" menu...

  • Page 467

    Software • upgrade information ch apte r 4 soft w are 467 power panel 300/400 user's manual v 2.10 3.6 creating a bootable usb flash drive for b&r upgrade files when used in connection with a b&r industrial pc, it is possible to upgrade bios from one of the usb flash drives available from b&r. To do...

  • Page 468

    468 software • upgrade information power panel 300/400 user's manual v 2.10 3.6.3 where do i get ms-dos? Information concerning creating an ms-dos boot diskette can be found in section 3.5 "creating a dos boot diskette in windows xp" on page 465. Then the files from the diskette are to be copied to ...

  • Page 469

    Software • upgrade information ch apte r 4 soft w are 469 power panel 300/400 user's manual v 2.10 3.7 creating a bootable compactflash card for b&r upgrade files when used in connection with a b&r industrial pc, it is possible to upgrade bios from one of the compactflash cards available from b&r. T...

  • Page 470

    470 software • upgrade information power panel 300/400 user's manual v 2.10 3.7.3 where do i get ms-dos? Information concerning creating an ms-dos boot diskette can be found in section 3.5 "creating a dos boot diskette in windows xp" on page 465. Then the files from the diskette are to be copied to ...

  • Page 471

    Software • power panel with windows ce ch apte r 4 soft w are 471 power panel 300/400 user's manual v 2.10 4. Power panel with windows ce 4.1 general information b&r windows ce is an operating system which is optimally tailored to b&r's devices. It includes only the functions and modules which are r...

  • Page 472

    472 software • power panel with windows ce power panel 300/400 user's manual v 2.10 4.2 windows ce 5.0 features detailed information about windows ce for b&r devices can be downloaded in the download area on the b&r homepage ( www.Br-automation.Com ). Features windows ce 5.0 supported screen resolut...

  • Page 473

    Software • power panel with windows ce ch apte r 4 soft w are 473 power panel 300/400 user's manual v 2.10 4.3 windows ce 6.0 features detailed information about windows ce for b&r devices can be downloaded in the download area on the b&r homepage ( www.Br-automation.Com ). 4.4 differences between w...

  • Page 474

    474 software • power panel with windows ce power panel 300/400 user's manual v 2.10 4.5 requirements the device must fulfill the following criteria to be able run the windows ce operating system. • at least 128 mb main memory. • at least one 128 mb compactflash card (size should be specified when or...

  • Page 475

    Software • power panel with windows xp embedded ch apte r 4 soft w are 475 power panel 300/400 user's manual v 2.10 5. Power panel with windows xp embedded 5.1 general information windows xp embedded is the modular version of the desktop operating system windows xp professional. Windows xp embedded ...

  • Page 476

    476 software • power panel with windows xp embedded power panel 300/400 user's manual v 2.10 5.3 installation windows xp embedded is usually preinstalled at b&r austria on a suitable compactflash card (at least 512 mb - must be specified when placing order). The system is then automatically configur...

  • Page 477

    Software • power panel with windows embedded standard 2009 ch apte r 4 soft w are 477 power panel 300/400 user's manual v 2.10 6. Power panel with windows embedded standard 2009 6.1 general information windows xp embedded standard 2009 is the modular version of the desktop operating system windows x...

  • Page 478

    478 software • power panel with windows embedded standard 2009 power panel 300/400 user's manual v 2.10 6.2 features with wes2009 (windows embedded standard 2009) the feature list shows the most important device functions in windows embedded standard 2009. Function present enhanced write filter (ewf...

  • Page 479: Information:

    Software • power panel with windows embedded standard 2009 ch apte r 4 soft w are 479 power panel 300/400 user's manual v 2.10 6.3 installation upon request, windows embedded standard 2009 can be preinstalled at b&r austria on a suitable compactflash card (min. 1gb). The pp300/400 system is then aut...

  • Page 480: 7. Vesa Mode Support

    480 software • vesa mode support power panel 300/400 user's manual v 2.10 7. Vesa mode support the following vesa standards (see www.Vesa.Org ) are supported. Vesa mode resolution 101h 640 x 480 x 8 103h 800 x 600 x 8 105h 1024 x 768 x 8 107h 1280 x 1024 x 8 110h 640 x 480 x 15 111h 640 x 480 x 16 1...

  • Page 481

    Software • b&r automation device interface (adi) driver - control center ch apte r 4 soft w are 481 power panel 300/400 user's manual v 2.10 8. B&r automation device interface (adi) driver - control center the adi (automation device interface) driver enables access to specific functions of b&r devic...

  • Page 482

    482 software • b&r automation device interface (adi) driver - control center power panel 300/400 user's manual v 2.10 supports following systems: a detailed description of the control center can be found in the integrated online help. The b&r automation device interface (adi) driver (also contains c...

  • Page 483

    Software • b&r automation device interface (adi) driver - control center ch apte r 4 soft w are 483 power panel 300/400 user's manual v 2.10 8.1 sdl equalizer setting the equalizer makes it possible to adjust the strength of the video signal to the sdl cable length. This allows you to improve the vi...

  • Page 484

    484 software • b&r automation device interface (adi) driver - control center power panel 300/400 user's manual v 2.10

  • Page 485: 2. Overview of Standards

    Standards and certifications • applicable european guidelines chap ter 5 sta nda rds a nd certi fica tion s 485 power panel 300/400 user's manual v 2.10 chapter 5 • standards and certifications 1. Applicable european guidelines • emc guidelines 2004/108/eg • low-voltage guidelines 2006/95/eg • machi...

  • Page 486

    486 standards and certifications • overview of standards power panel 300/400 user's manual v 2.10 en 61000-4-3 electromagnetic compatibility (emc) - part 4-3: testing and measuring techniques; radiated radio- frequency electromagnetic field immunity test en 61000-4-4 electromagnetic compatibility (e...

  • Page 487: 3. Emission Requirements

    Standards and certifications • emission requirements chap ter 5 sta nda rds a nd certi fica tion s 487 power panel 300/400 user's manual v 2.10 3. Emission requirements 3.1 network-related emissions emissions test carried out according to limits according to network-related emissions en 55011 / en 5...

  • Page 488

    488 standards and certifications • emission requirements power panel 300/400 user's manual v 2.10 3.2 emissions, electromagnetic emissions test carried out according to en 55011 / en 55022 limits according to en 61131-2 limits according to 47 cfr part 15 subpart b class a power mains connections 1) ...

  • Page 489

    Standards and certifications • requirements for immunity to disturbances chap ter 5 sta nda rds a nd certi fica tion s 489 power panel 300/400 user's manual v 2.10 4. Requirements for immunity to disturbances evaluation criteria according to en 61000-6-2 criteria a: the operating equipment must cont...

  • Page 490

    490 standards and certifications • requirements for immunity to disturbances power panel 300/400 user's manual v 2.10 criteria d: impairment or failure of the function, which can no longer be established (operating equipment destroyed). 4.1 electrostatic discharge (esd) 4.2 high-frequency electromag...

  • Page 491

    Standards and certifications • requirements for immunity to disturbances chap ter 5 sta nda rds a nd certi fica tion s 491 power panel 300/400 user's manual v 2.10 4.3 high-speed transient electrical disturbances (burst) 4.4 surges 4.5 conducted disturbances test carried out according to en 61000-4-...

  • Page 492

    492 standards and certifications • requirements for immunity to disturbances power panel 300/400 user's manual v 2.10 4.6 magnetic fields with electrical frequencies 4.7 voltage dips, fluctuations, and short-term interruptions dc power i/o 150 khz - 80 mhz, 10 v, 80% amplitude modulation with 1 khz,...

  • Page 493

    Standards and certifications • requirements for immunity to disturbances chap ter 5 sta nda rds a nd certi fica tion s 493 power panel 300/400 user's manual v 2.10 4.8 damped vibration test carried out according to en 61000-4-12 limits according to en 61131-2 power i/o, l to l ±1 kv, 1 mhz, repeat r...

  • Page 494: 5. Mechanical Conditions

    494 standards and certifications • mechanical conditions power panel 300/400 user's manual v 2.10 5. Mechanical conditions 5.1 vibration operation vibration test carried out according to limits according to vibration operation en 60068-2-6 en 61131-2: programmable logic controllers en 60721-3-3 clas...

  • Page 495

    Standards and certifications • mechanical conditions chap ter 5 sta nda rds a nd certi fica tion s 495 power panel 300/400 user's manual v 2.10 5.2 vibration during transport (packaged) 5.3 shock during operation 5.4 shock during transport (packaged) 5.5 toppling test carried out according to en 600...

  • Page 496

    496 standards and certifications • mechanical conditions power panel 300/400 user's manual v 2.10 5.6 free fall (packaged) test carried out according to en 60068-2-32 limits according to en 61131-2 limits according to en 60721-3-2 class 2m1 limits according to en 60721-3-2 class 2m2 limits according...

  • Page 497: 6. Climate Conditions

    Standards and certifications • climate conditions chap ter 5 sta nda rds a nd certi fica tion s 497 power panel 300/400 user's manual v 2.10 6. Climate conditions 6.1 worst case operation 6.2 dry heat 6.3 dry cold temperature / humidity test carried out according to limits according to worst case op...

  • Page 498

    498 standards and certifications • climate conditions power panel 300/400 user's manual v 2.10 6.4 large temperature fluctuations 6.5 temperature fluctuations in operation 6.6 humid heat, cyclic 6.7 humid heat, constant (storage) test carried out according to en 60068-2-14 limits according to en 611...

  • Page 499

    Standards and certifications • climate conditions chap ter 5 sta nda rds a nd certi fica tion s 499 power panel 300/400 user's manual v 2.10 6.8 sprayed water (front side) test carried out according to ul 50 limits according to nema 250 type 4x sprayed water (front side) spraying using a 25.4 mm (di...

  • Page 500: 7. Safety

    500 standards and certifications • safety power panel 300/400 user's manual v 2.10 7. Safety 7.1 ground resistance 7.2 insulation resistance safety test carried out according to limits according to ground resistance en 61131-2 en 60204-1: electrical equipment of machines en 61131-2: programmable log...

  • Page 501

    Standards and certifications • safety chap ter 5 sta nda rds a nd certi fica tion s 501 power panel 300/400 user's manual v 2.10 7.3 high voltage 7.4 voltage range test carried out according to en 60060-1 limits according to en 61131-2 1) 1) see en 61131-2:2003 page 104, table 59. Limits according t...

  • Page 502: 8. Other Tests

    502 standards and certifications • other tests power panel 300/400 user's manual v 2.10 8. Other tests 8.1 protection type other tests test carried out according to limits according to function test - - optical test - - hot spot measurement - - protection type - en 60529: degrees of protection provi...

  • Page 503

    Standards and certifications • international certifications chap ter 5 sta nda rds a nd certi fica tion s 503 power panel 300/400 user's manual v 2.10 9. International certifications b&r products and services comply with applicable standards. They are international standards from organizations such ...

  • Page 504

    504 standards and certifications • international certifications power panel 300/400 user's manual v 2.10

  • Page 505: Chapter 6 • Accessories

    Accessories • overview chapter 6 accessories 505 power panel 300/400 user's manual v 2.10 chapter 6 • accessories 1. Overview model number product id note 0ac201.91 lithium batteries, 4 pcs. Lithium batteries, 4 pcs., 3 v / 950 mah, button cell 4a0006.00-000 lithium battery (1x) lithium battery, 1 p...

  • Page 506

    506 accessories • overview power panel 300/400 user's manual v 2.10 5cfcrd.0128-03 compactflash 128 mb ssi compactflash card with 128 mb slc nand flash and ide/ata interface 5cfcrd.0256-03 compactflash 256 mb ssi compactflash card with 256 mb slc nand flash and ide/ata interface 5cfcrd.0512-03 compa...

  • Page 507: Information:

    Accessories • replacement cmos batteries chapter 6 accessories 507 power panel 300/400 user's manual v 2.10 2. Replacement cmos batteries the lithium battery is needed for buffering the bios cmos data, the real-time clock, and sram data. The battery is subject to wear and must be replaced when the b...

  • Page 508

    508 accessories • replacement cmos batteries power panel 300/400 user's manual v 2.10 2.3 contents of delivery amount component 1 or 4 lithium batteries table 230: contents of delivery - lithium batteries.

  • Page 509: Information:

    Accessories • tb103 3-pin supply voltage connector chapter 6 accessories 509 power panel 300/400 user's manual v 2.10 3. Tb103 3-pin supply voltage connector 3.1 general information this single row 3-pin terminal block is mainly used to connect the supply voltage. 3.2 order data 3.3 technical data m...

  • Page 510

    510 accessories • tb103 3-pin supply voltage connector power panel 300/400 user's manual v 2.10 3.4 contents of delivery name 0tb103.9 0tb103.91 number of pins 3 type of terminal screw clamps cage clamps distance between contacts 5.08 mm resistance between contacts ≤ 5 mΩ nominal voltage according t...

  • Page 511: 4. Legend Strip Templates

    Accessories • legend strip templates chapter 6 accessories 511 power panel 300/400 user's manual v 2.10 4. Legend strip templates power panel devices with keys are delivered with partially pre-labeled key legend strips (f1, f2, etc.). The key legend strip slots are accessible on the back of the powe...

  • Page 512

    512 accessories • legend strip templates power panel 300/400 user's manual v 2.10 4.1 order data model number description figure 5ac900.057x-00 legend strips 3x 5.7" vertical1 legend strip template for power panel 4pp451.0571-65. For 3 devices. Examples of legend strip templates 5ac900.057x-01 legen...

  • Page 513: Information:

    Accessories • compactflash cards 5cfcrd.Xxxx-04 chapter 6 accessories 513 power panel 300/400 user's manual v 2.10 5. Compactflash cards 5cfcrd.Xxxx-04 5.1 general information 5.2 order data information: the 5cfcrd.Xxxx-04 compactflash cards are supported on b&r devices with wince version ≥ 6.0 or h...

  • Page 514: Caution!

    514 accessories • compactflash cards 5cfcrd.Xxxx-04 power panel 300/400 user's manual v 2.10 5.3 technical data caution! A sudden loss of power can cause data to be lost! In very rare cases, the mass memory may also become damaged. To prevent damage and loss of data, it is recommended to use a ups d...

  • Page 515

    Accessories • compactflash cards 5cfcrd.Xxxx-04 chapter 6 accessories 515 power panel 300/400 user's manual v 2.10 support 5cfcrd.0512- 04 5cfcrd.1024- 04 5cfcrd.2048- 04 5cfcrd.4096- 04 5cfcrd.8192- 04 5cfcrd.016g -04 hardware pp300/400, ppc300, ppc700, ppc725, ppc800, apc620, apc810, apc820 window...

  • Page 516

    516 accessories • compactflash cards 5cfcrd.Xxxx-04 power panel 300/400 user's manual v 2.10 5.3.1 temperature humidity diagram - operation and storage 5.4 dimensions figure 330: temperature humidity diagram - compactflash cards 5cfcrd.Xxxx-04 figure 331: dimensions - compactflash card type i 0 0 10...

  • Page 517

    Accessories • compactflash cards 5cfcrd.Xxxx-04 chapter 6 accessories 517 power panel 300/400 user's manual v 2.10 5.5 benchmark figure 332: atto disk benchmark v2.34 comparison (reading) figure 333: atto disk benchmark v2.34 comparison (writing) 5 10 15 20 25 30 35 40 0.5 1 2 4 8 16 32 128 64 256 5...

  • Page 518: Information:

    518 accessories • compactflash cards 5cfcrd.Xxxx-03 power panel 300/400 user's manual v 2.10 6. Compactflash cards 5cfcrd.Xxxx-03 6.1 general information 6.2 order data information: on windows ce 5.0 devices, 5cfcrd.Xxxx-03 compactflash cards up to 1gb are supported. Model number description figure ...

  • Page 519: Caution!

    Accessories • compactflash cards 5cfcrd.Xxxx-03 chapter 6 accessories 519 power panel 300/400 user's manual v 2.10 6.3 technical data caution! A sudden loss of power can cause data to be lost! In very rare cases, the mass memory may also become damaged. To prevent damage and loss of data, b&r recomm...

  • Page 520

    520 accessories • compactflash cards 5cfcrd.Xxxx-03 power panel 300/400 user's manual v 2.10 6.3.1 temperature humidity diagram - operation and storage support 5cfcrd. 0064-03 5cfcrd. 0128-03 5cfcrd. 0256-03 5cfcrd. 0512-03 5cfcrd. 1024-03 5cfcrd. 2048-03 5cfcrd. 4096-03 5cfcrd. 8192-03 pvi transfer...

  • Page 521

    Accessories • compactflash cards 5cfcrd.Xxxx-03 chapter 6 accessories 521 power panel 300/400 user's manual v 2.10 6.4 dimensions figure 335: dimensions - compactflash card type i top 26 50 1 25 1.01 ±0.07 1.01 ±0.07 1.60 ±0.05 0.99 ±0.05 4 x r0.5 ±0.1 3.30 ±0.1 2x 12 ±0.10 2x 25.78 ±0.07 1.65 42.8 ...

  • Page 522: 7. Usb Flash Drive

    522 accessories • usb flash drive power panel 300/400 user's manual v 2.10 7. Usb flash drive 7.1 general information usb flash drives are easy-to-exchange storage media. Because of the fast data transfer (usb 2.0), the usb flash drives are ideal for use as a portable memory medium. Without requirin...

  • Page 523: Information:

    Accessories • usb flash drive chapter 6 accessories 523 power panel 300/400 user's manual v 2.10 7.3 technical data information: the following characteristics, features and limit values only apply to this accessory and can deviate those specified for the entire device. For the entire device where th...

  • Page 524

    524 accessories • usb flash drive power panel 300/400 user's manual v 2.10 7.3.1 temperature humidity diagram - operation and storage environmental characteristics 5mmusb.2048-00 shock operation bearings transport 40 g and 11 ms duration (all axes) 80 g and 11 ms duration (all axes) 80 g and 11 ms d...

  • Page 525

    Accessories • null modem cable 9a0017.0x chapter 6 accessories 525 power panel 300/400 user's manual v 2.10 8. Null modem cable 9a0017.0x 8.1 order data 8.2 technical data figure 337: null modem cable 9a0017.0x model number description note 9a0017.01 rs232 db9 null modem cable 0.6 m null modem cable...

  • Page 526

    526 accessories • null modem cable 9a0017.0x power panel 300/400 user's manual v 2.10 8.3 cable specifications figure 338: pin assignments - null modem cable 9 5 6 1 dsub (9-pin), male pin assignments 8 7 5 6 4 2 1 shield 3 7 8 5 1 6 3 4 shield 2 dsub female (9-pin), 9 5 6 1 dsub female (9-pin), dsu...

  • Page 527: 1. Cleaning

    Maintenance / servicing • cleaning ch apte r 7 ma inte nanc e / servic ing 527 power panel 300/400 user's manual v 2.10 chapter 7 • maintenance / servicing 1. Cleaning a moist towel should be used to clean the power panel device. When moistening the cloth, use only water with detergent, screen clean...

  • Page 528: 2. Changing The Battery

    528 maintenance / servicing • changing the battery power panel 300/400 user's manual v 2.10 2. Changing the battery 2.1 general information the battery guarantees buffering of the internal real-time clock (rtc), sram data, and individually saved bios settings. For more information about the batterie...

  • Page 529: Warning!

    Maintenance / servicing • changing the battery ch apte r 7 ma inte nanc e / servic ing 529 power panel 300/400 user's manual v 2.10 • carefully remove the used battery from the holder by pulling the removal strip. • do not touch the new battery with pliers or uninsulated tweezers ->risk of short cir...

  • Page 530

    530 maintenance / servicing • preventing after-image effect in lcd/tft monitors power panel 300/400 user's manual v 2.10 3. Preventing after-image effect in lcd/tft monitors burn-in effect (after images, display memory effect, image retention or also image sticking) occurs in lcd/tft monitors when a...

  • Page 531: Appendix A

    Appendix a • touch screen appen dix a 531 power panel 300/400 user's manual v 2.10 appendix a 1. Touch screen 1.1 elo accu touch information: the following characteristics, features, and limit values only apply to this individual component and can deviate from those specified for the entire device. ...

  • Page 532

    532 appendix a • touch screen power panel 300/400 user's manual v 2.10 1.1.1 temperature humidity diagram 1.1.2 cleaning the touch screen should be cleaned with a moist lint-free cloth. When moistening the cloth, use only water with detergent, screen cleaning agent, or alcohol (ethanol). The cleanin...

  • Page 533: Information:

    Appendix a • touch screen appen dix a 533 power panel 300/400 user's manual v 2.10 1.2 gunze touch information: the following characteristics, features, and limit values only apply to this individual component and can deviate from those specified for the entire device. For the entire device in which...

  • Page 534

    534 appendix a • touch screen power panel 300/400 user's manual v 2.10 1.2.1 temperature humidity diagram 1.2.2 cleaning the touch screen should be cleaned with a moist lint-free cloth. When moistening the cloth, use only water with detergent, screen cleaning agent, or alcohol (ethanol). The cleanin...

  • Page 535: 2. Décor Foil

    Appendix a • décor foil appen dix a 535 power panel 300/400 user's manual v 2.10 2. Décor foil the décor foil conforms to din 42115 (section 2). This means it is resistant to exposure to the following chemicals for a 24-hour period with no visible signs of damage: the décor foil conforms to din 4211...

  • Page 536: 3. Viewing Angles

    536 appendix a • viewing angles power panel 300/400 user's manual v 2.10 3. Viewing angles the perspective information (r,l,u,d) can be seen in the technical data for the individual components. Figure 342: viewing angles r l u d 6 o’clock direction.

  • Page 537: 4. Mounting Compatibilities

    Appendix a • mounting compatibilities appen dix a 537 power panel 300/400 user's manual v 2.10 4. Mounting compatibilities this section describes the compatibility of the installation dimensions for the power panel 100/200, power panel 300/400, automation panel 900 and panel pc 700 units according t...

  • Page 538

    538 appendix a • mounting compatibilities power panel 300/400 user's manual v 2.10 10.4“ horizontal1 outer dimensions ■ ■ ■ ■ installation dimensions ● ● ● ● horizontal2 outer dimensions ■ ■ ■ ■ installation dimensions ● ● ▲ ▲ vert ic al 1 outer dimensions ■ ■ ■ ■ installation dimensions ● ● ▲ ▲ 12....

  • Page 539

    Appendix a • mounting compatibilities appen dix a 539 power panel 300/400 user's manual v 2.10 4.2 compatibility details the measurement values (all in mm) in the following figures have the following meaning. 4.2.1 5.7" devices 5.7" power panel 100/200 and power panel 300/400 devices in horizontal1 ...

  • Page 540

    540 appendix a • mounting compatibilities power panel 300/400 user's manual v 2.10 5.7" power panel 100/200 and power panel 300/400 devices in vertical1 format are 100% mounting compatible. 5.7" power panel 100/200 and power panel 300/400 devices in vertical1 format are 100% mounting compatible. Fig...

  • Page 541

    Appendix a • mounting compatibilities appen dix a 541 power panel 300/400 user's manual v 2.10 4.2.2 10.4" devices 10.4" power panel 100/200, power panel 300/400, automation panel 900 and panel pc 700 devices in horizontal1 format are 100% mounting compatible. 10.4" power panel 100/200 and power pan...

  • Page 542

    542 appendix a • mounting compatibilities power panel 300/400 user's manual v 2.10 the larger cutout can can be conditionally used for all devices: • when mounting, make sure that the pp100/200/300/400 devices are placed and mounted as close to the center of the cutout as possible. Failure to do so ...

  • Page 543

    Appendix a • mounting compatibilities appen dix a 543 power panel 300/400 user's manual v 2.10 4.2.3 12.1" devices 12.1" power panel 100/200 and power panel 300/400 are not 100% mounting compatible with the horizontal1 format for the automation panel 900 and panel pc 700 devices. The power panel 100...

  • Page 544

    544 appendix a • mounting compatibilities power panel 300/400 user's manual v 2.10 4.2.4 15" devices 15" power panel 100/200, power panel 300/400, automation panel 900 and panel pc 700 devices in horizontal1 format are 100% mounting compatible. 15" power panel 100/200, power panel 300/400, automatio...

  • Page 545

    Appendix a • b&r key editor information appen dix a 545 power panel 300/400 user's manual v 2.10 5. B&r key editor information on display units, it is often necessary to adjust the function keys and leds for the application software being used. With the b&r key editor, it is possible to quickly and ...

  • Page 546

    546 appendix a • b&r key editor information power panel 300/400 user's manual v 2.10 supports following systems (version 3.00): • automation pc 820 • automation pc 800 • automation pc 620 (etx, xtx, embedded) • power panel 300/400 • power panel 100.200 • power panel 65 • panel pc 300 • panel pc 700 ...

  • Page 547

    Appendix a • b&r automation device interface (adi) development kit appen dix a 547 power panel 300/400 user's manual v 2.10 6. B&r automation device interface (adi) development kit the adi development kit can be used to activate functions in the b&r automation device interface (adi) from windows app...

  • Page 548

    548 appendix a • b&r automation device interface (adi) development kit power panel 300/400 user's manual v 2.10 supports following systems: • automation pc 620 • automation pc 810 • automation pc 820 • mobile panel 40/50 • mobile panel 100/200 • panel pc 300 • panel pc 700 • panel pc 800 • power pan...

  • Page 549: 7. Glossary

    Appendix a • glossary appen dix a 549 power panel 300/400 user's manual v 2.10 7. Glossary acpi abbreviation for "advanced configuration and power interface". Configuration interface that enables the operating system to control the power supply for each device connected to the pc. With acpi, the com...

  • Page 550

    550 appendix a • glossary power panel 300/400 user's manual v 2.10 cache background memory, also known as non-addressable memory or fast buffer memory. It is used to relieve the fast main memory of a computer. For example, data that should be output to slower components by the working memory (e.G. D...

  • Page 551

    Appendix a • glossary appen dix a 551 power panel 300/400 user's manual v 2.10 cpu an abbreviation for "central processing unit". Interprets and executes commands. It is also known as a "microprocessor" or "processor" for short. A processor is able to receive, decode and execute commands, as well as...

  • Page 552

    552 appendix a • glossary power panel 300/400 user's manual v 2.10 edid data abbreviation for "extended display identification data". Edid data contains the characteristics of monitors / tft displays transferred as 128 kb data blocks to the graphics card via the display data channel (ddc). This edid...

  • Page 553

    Appendix a • glossary appen dix a 553 power panel 300/400 user's manual v 2.10 firmware programs stored permanently in read-only memory. Firmware is software used to operate computer-controlled devices that generally stays in the device throughout its lifespan or over a long period of time. Such sof...

  • Page 554

    554 appendix a • glossary power panel 300/400 user's manual v 2.10 lcd an abbreviation for "liquid crystal display". A display type, based on liquid crystals that have a polarized molecular structure and are enclosed between two transparent electrodes as a thin layer. If an electrical field is appli...

  • Page 555

    Appendix a • glossary appen dix a 555 power panel 300/400 user's manual v 2.10 pnp an abbreviation for "plug and play". Specifications developed by intel. Using plug and play allows a pc to automatically configure itself so that it can communicate with peripheral devices (e.G. Monitors, modems, and ...

  • Page 556

    556 appendix a • glossary power panel 300/400 user's manual v 2.10 rs232 recommended standard number 232. Oldest and most widespread interface standard, also called a v.24 interface. All signals are referenced to ground making this an unbalanced interface. High level: -3 to -30 v, low level: +3 to +...

  • Page 557

    Appendix a • glossary appen dix a 557 power panel 300/400 user's manual v 2.10 tft display lcd (liquid crystal display) technology where the display consists of a large grid of lcd cells. Each pixel is represented by a cell, whereby electrical fields produced in the cells are supported by thin film ...

  • Page 558

    558 appendix a • glossary power panel 300/400 user's manual v 2.10 vga an abbreviation for "video graphics adapter". A video adapter which can handle all ega (enhanced graphics adapter) video modes and adds several new modes. Visual components integrated in b&r automation studio. Visual components c...

  • Page 559

    1 power panel 300/400 user's manual v 2.10 figu re in dex figure index figure 1: power panel 300 and power panel 400 devices ........................................... 39 figure 2: different plug and key positions (pp100/200 - pp300/400) ........................... 41 figure 3: supply voltage conne...

  • Page 560

    2 power panel 300/400 user's manual v 2.10 figure index figure 48: dimensions - 5pp320.1505-3b .................................................................... 100 figure 49: cutout installation - 5pp320.1505-3b .......................................................... 101 figure 50: supply vol...

  • Page 561

    3 power panel 300/400 user's manual v 2.10 figu re in dex figure index figure 95: dimensions - 4pp381.1043-31 .................................................................... 161 figure 96: cutout installation - 4pp381.1043-31........................................................... 162 figure...

  • Page 562

    4 power panel 300/400 user's manual v 2.10 figure index figure 142: temperature humidity diagram - 4pp420.1043-75 ...................................... 221 figure 143: dimensions - 4pp420.1043-75 .................................................................... 221 figure 144: cutout installatio...

  • Page 563

    5 power panel 300/400 user's manual v 2.10 figu re in dex figure index figure 189: cutout installation - 4pp451.1043-75........................................................... 278 figure 190: front view - 4pp451.1043-b5 ...................................................................... 279 fi...

  • Page 564

    6 power panel 300/400 user's manual v 2.10 figure index figure 236: rear view - 4pp481.1043-75 ....................................................................... 335 figure 237: temperature humidity diagram - 4pp481.1043-75 ...................................... 339 figure 238: dimensions - 4pp...

  • Page 565

    7 power panel 300/400 user's manual v 2.10 figu re in dex figure index figure 283: device information........................................................................................ 415 figure 284: miscellaneous configuration .....................................................................

  • Page 566

    8 power panel 300/400 user's manual v 2.10 figure index figure 330: temperature humidity diagram - compactflash cards 5cfcrd.Xxxx-04 ... 516 figure 331: dimensions - compactflash card type i ..................................................... 516 figure 332: atto disk benchmark v2.34 comparison (r...

  • Page 567

    Table index tabl e in dex 1 power panel 300/400 user's manual v 2.10 table 1: manual history ..................................................................................................... 21 table 2: environmentally-friendly separation of materials................................................

  • Page 568

    Table index 2 power panel 300/400 user's manual v 2.10 table 48: technical data - 4pp320.1043-31..................................................................... 127 table 49: contents of delivery - 4pp320.1043-31 ............................................................ 131 table 50: technic...

  • Page 569

    Table index tabl e in dex 3 power panel 300/400 user's manual v 2.10 table 95: technical data - 4pp451.0571-75..................................................................... 254 table 96: contents of delivery - 4pp451.0571-75 ............................................................ 259 tab...

  • Page 570

    Table index 4 power panel 300/400 user's manual v 2.10 table 142: bios super i/o configuration menu .................................................................. 406 table 143: bios video configuration menu ........................................................................ 407 table 144: ...

  • Page 571

    Table index tabl e in dex 5 power panel 300/400 user's manual v 2.10 table 189: system support - adi driver .............................................................................. 482 table 190: overview of standards ...............................................................................

  • Page 572

    Table index 6 power panel 300/400 user's manual v 2.10 table 236: technical data - compactflash cards 5cfcrd.Xxxx-04.................................. 514 table 237: order data - compactflash cards ..................................................................... 518 table 238: technical data - ...

  • Page 573

    M ode l nu mbe r ind ex model number index 1 power panel 300/400 user's manual v 2.10 0 0ac201.91................................. 37 , 505 , 507 0tb103.9 ................................... 37 , 505 , 509 0tb103.91 ................................. 37 , 505 , 509 4 4a0006.00-000 ......................

  • Page 574

    Model number index 2 power panel 300/400 user's manual v 2.10

  • Page 575

    Index ind ex 1 power panel 300/400 user's manual v 2.10 a acpi ........................................................549 adi ...........................................................481 development kit ....................................547 drivers .................................................

  • Page 576

    Index 2 power panel 300/400 user's manual v 2.10 f fact .......................................................452 fifo .........................................................552 firmware ..................................................553 fpga ......................................................

  • Page 577

    Index ind ex 3 power panel 300/400 user's manual v 2.10 programs ................................................28 protection against electrostatic discharges 25 touching electrical parts ........................27 transport and storage ............................26 viruses ..........................

  • Page 578

    Index 4 power panel 300/400 user's manual v 2.10