    3015-5609 rev 1 1 p/n: 3015-5609 revision 1 june 2012 bacnet ® protocol converter kit for use with bacharach multizone gas monitors installation manual 1. Scope the fieldserver™ protonode is a bacnet protocol converter accessory for use with bacharach’s multizone family of gas monitors. This manual ...

  • Page 2: 2.  Items Required

    Bacnet ® protocol converter kit 2 3015-5609 rev 1 2. Items required medium phillips head screwdriver medium flat head screwdriver small flat head screwdriver fieldserver protonode-rer protocol converter kit (3015-5705) p/n qty description 3015-5703 1 fieldserver protonode-rer protocol converter 3015...

  • Page 3

    Bacnet ® protocol converter kit 3015-5609 rev 1 3 figure 2. Mounting plate and hex nuts figure 3. Protonode and mounting plate.

  • Page 4

    Bacnet ® protocol converter kit 4 3015-5609 rev 1 figure 4. Protonode secured onto mounting plate (back view) figure 5. Protonode mounted inside mz door.

  • Page 5

    Bacnet ® protocol converter kit 3015-5609 rev 1 5 4. Connecting the power supply the protonode can be powered by 9-30 vdc or 12-24 vac. The protonode converter kit contains a power cable so that the protonode can be powered by the mz. The power cable that is supplied with the kit is meant to replace...

  • Page 6

    Bacnet ® protocol converter kit 6 3015-5609 rev 1 pin no silkscreen connector labels pin 4 + pwr pwr + pin 5 - pwr pwr - pin 6 frame gnd fg note: if you choose not to power the protonode from the mz, you must supply all necessary wiring and an appropriate power supply. 5. Rs-485 network wiring the r...

  • Page 7: 6.  Network Configuration

    Bacnet ® protocol converter kit 3015-5609 rev 1 7 6. Network configuration the protonode is factory-configured with the following defaults. • default ip address 192.168.1.24 • default subnet mask 255.255.255.0 if a different ip address or subnet mask is desired, or for other configuration settings, ...

  • Page 8

    Bacnet ® protocol converter kit 8 3015-5609 rev 1 bacnet object id bacnet object description ([#]=zone #) bacnet object type access (r=read, w=write) source modbus register number modbus register description 15 ppm [4] analog input r 0x1204 zone 4 data 16 refrig type [4] analog input r 17 refrig typ...

  • Page 9

    Bacnet ® protocol converter kit 3015-5609 rev 1 9 bacnet object id bacnet object description ([#]=zone #) bacnet object type access (r=read, w=write) source modbus register number modbus register description 43 ppm [11] analog input r 0x120b zone 11 data 44 refrig type [11] analog input r 45 refrig ...

  • Page 10

    Bacnet ® protocol converter kit 10 3015-5609 rev 1 8. Additional information for additional information on the fieldserver protonode, refer to the fieldserver documentation. You may also refer to the fieldserver website at www.Fieldserver.Com . For additional information on bacharach’s multizone gas...

  • Page 11

    Bacnet ® protocol converter kit 3015-5609 rev 1 11.

  • Page 12

    Bacnet ® protocol converter kit 12 3015-5609 rev 1 © 2012 bacharach, inc. All rights reserved. Bacnet is a registered trademark of ashrae. Fieldserver is a trademark of fieldserver technologies, a sierra monitor company. Protonode is a product of fieldserver technologies headquarters: 621 hunt valle...