Bacharach HGM-SZ Supplementary Manual

Manual is about: Single Zone Gas Monitors

Summary of HGM-SZ

  • Page 1

    New style hgmsz technical support notes for all serial number starting with nu xxx and above (july 2008) zero fault – ir voltage out of tolerance zero fault and gain set fault clipping fault – detector voltage out of tolerance for both zero fault and clipping fault – press the up arrow key to locate...

  • Page 2

    Gain set fault (code 200) hgmsz (3015-4200) gain set fault occurs when the digipot setting is outside of acceptable limits. For the agmsz (3015-4280) ammonia single zone monitor the digipot may be as low as 20. To increase the emitter power, go to the screen shown below by putting the curser on “ir”...

  • Page 3

    Reset to default settings press and hold the default button (located about one inch above the 4-20ma dc output connector), cycle power holding the default button in. A single long “beep” will be heard. – release the button after the “beep” stops. The screen will display purge. The next screen will s...

  • Page 4

    Pressure readings for the hgmsz codes 800, 1000 and 1800 first diagnostic screen zone pressure (0.06 psi below ambient) maximum 2.7 psia 4.26500v 24.5cd 14.00psi press left arrow key revised 6/5/08 p. M. Pape purge pressure (0.03 psi below ambient) maximum 2.7 psia 4.26500v 24.5cd * 14.3psi look for...

  • Page 5: Gas Leak Monitor Assistance

    Revised 6/5/08 p. M. Pape whom to call at the factory for refrigerant gas leak monitor assistance phone number: 800-888-6400 x 2478 fax number: 678-423-2479 e-mail: peter pape: x2478, peterp@bacharach-inc.Com bacharach, inc., help@bacharach-inc.Com shipping address: bacharach, inc. 621 hunt valley c...