NOTE:
All RDM800 units must have their BMS function set to ENABLE. This function is found
in the RDM SETUP screen.
NOTE:
The BAUD rate should remain at 19200 unless the system is connected to a BMS system.
There is no appreciable gain in performance by increasing the BAUD rate.
NOTE:
Each RDM800 clock must be individually set. The HGM300 clock may be set from any
RDM800.
NOTE:
The clocks in the RDM800 and HGM300 DO NOT automatically adjust for Day Light
Savings Time.
NOTE:
All RDM800’s must be in either their SYSTEM or ZONE Screen in order to communicate
with the HGM300.
Set BMS to ENABLE in all
RDM800’s
BMS BAUD should remain
at 19200 unless
connected to a BMS
system
Set RDM clock and set
HGM clock from here