Baldor ID5601-BO Installation And Operating Manual

Manual is about: ADJUSTABLE SPEED DRIVE Series 5 Inverter

Summary of ID5601-BO

  • Page 1

    Adjustable speed drive series 5 inverter nema 4x, ip-65 8/01 mn781b installation & operating manual.

  • Page 2

    Table of contents section page i. Simplified operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ii. Safety warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 i. Introduction...

  • Page 3

    I. Simplified operating instructions warning! Disconnect main power when making connections to the control. A. Ac line connection – connect the ac line to l1 and l2 terminals of terminal block tb1 and the ground wire (earth) to the green ground screw as shown in figure 4, on page 6, and as described...

  • Page 4

    I. Introduction the baldor id5601-bo adjustable speed drive is a variable speed control in a nema-4x / ip- 65 and watertight enclosure. It is designed to operate 208 - 230 volt 3-phase ac induction motors through 3.6 amps rms. The sine wave coded pulse width modulated (pwm) output, which operates at...

  • Page 5

    3 violet white orange (back view) main speed potentiometer (back view) start/stop switch 1. 2. For optional id5si-2 signal isolator. Are used for optional r/f, b- and b+ terminals fwd-stop-rev switch. Rev terminal is used red black white cl boost comp accel decel min max p2 p1 p3 stop fwd run rev co...

  • Page 6

    4 po wer st a tus reverse for w ard st op st ar t po wer 50 40 0 60 70 80 90 100 on off 30 20 10 au t o manu a l st op % speed shown with optional auto/manual and forward-stop-reverse recommended mounting screw: 1/4" (m6) 2.53 [139.97] 5.51 [128.59] 5.06 [7.97] 0.31 5.86 9.53 [224.00] 8.82 [208.17] ...

  • Page 7

    5 ii. Wiring instructions warning! Read safety warning, on page 1, before using this control. Disconnect the ac line before wiring. Note: to avoid erratic operation, do not bundle ac line and motor wires with wires from sig- nal following, start/stop switch or any other signal wires. Use shielded ca...

  • Page 8

    A. Ac line connection – wire the ac line input to l1 and l2 terminals of terminal block tb1 as shown in figure 4. Be sure both jumpers j1 and j2 are set to the “115v” posi- tion for 115 volt ac line input or to the “230v” position for 208/230 volt ac line input. B. Ground connection – earth ground t...

  • Page 9

    Note: to eliminate the start/stop function, connect run and com terminals with the jumper that is provided. See figure 7, on page 6. Caution! Using a jumper to eliminate the start/stop function will cause the motor to run at the main speed potentiometer setting when the ac line is applied. F. Voltag...

  • Page 10

    8 fault). To set the control to automatically reset after a fault has been cleared, set jumper j3 to the "auto" position. See figure 12. (also see section vib, on page 9 and table 4, on page 10.) warning! The motor will automatically restart when the ac line is applied, if jumper j4 is set to the "a...

  • Page 11

    9 b. The hi-pot tester must have an automatic ramp-up to the test voltage and an automatic ramp-down to zero voltage. Note: if the hi-pot tester does not have automatic ramping, then the hi-pot output must be manually increased to the test voltage and then manually reduced to zero. This pro- cedure ...

  • Page 12

    10 warning! The motor will automatically start when the ac line is applied or a fault is cleared, if jumper j4 is set to the “auto” or “man” position and the start/stop switch is eliminated. Vii. Ac line fusing this control does not contain ac line fuses. Most electrical codes require that each ungr...

  • Page 13

    11 more rapid deceleration time, rotate the decel trimpot coun- terclockwise. For longer deceleration time, rotate the decel trimpot clockwise. See figure 20. Note: to provide increased resolution of the accel and decel trimpots, 50% rotation covers 0.3 - 5 seconds. Application note: on applications...

  • Page 14

    12 the cl trimpot is factory set for 160% of jumper j3 range setting. For a higher current limit setting, rotate the cl trimpot clockwise. For a lower current limit setting, rotate the cl trimpot counterclockwise. The current limit also contains i 2 t trip function. The control will trip according t...

  • Page 15

    Ix. Diagnostic leds the motor control is designed with leds mounted on the front cover to display the control’s operational status. A. Power on (on) – indicates the presence of bus voltage. B. Status (status) – the status led is a tricolor led that provides indication of the con- trol’s operational ...

  • Page 16

    (a40299) – rev. A – 3/2001 xi. Limited warranty for a period of 2 years from date of original purchase, baldor will repair or replace without charge controls which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unau...