Baldor Premier R Series Operator's Manual

Summary of Premier R Series

  • Page 1

    Operator's manual for your premier ‘r’ series generator baldor generators 3815 oregon street, oshkosh wi 54902 telephone 236-4200 • fax 920-236-4219 form#: s-psg-002-69 effective date: 10/1/97 series 'r' cover\msw'00 revision date: 03/12/03.

  • Page 2

    Forward this manual contains the information you need to safely and efficiently operate your generator set. During the preparation of this manual every effort was made to ensure the accuracy of its contents. Do not operate this generator set until you carefully read this manual and understand the sa...

  • Page 3

    ♦ place protective covers and guards over the rotating parts, if rotating parts such as the drive shaft, pulley, belt, etc. Are left exposed, they are potentially hazardous. ♦ when cleaning, repairing or inspecting, make sure all moving parts have stopped. ♦ prior to working on the generator set, di...

  • Page 4

    ♦ never permit anyone to operate the generator set without proper instructions. ♦ never allow children to operate the generator set. ♦ children and pets must be kept away from the area of operation due to the possibility of burns from hot engine components or injury from any equipment the generator ...

  • Page 5

    ♦ always treat the electrical circuits as if they were energized. ♦ disconnect all leads plugged into the unit prior to working on it. ♦ have the electrical circuits serviced only by qualified technicians. ♦ inspect wiring frequently and replace frayed, broken or poor leads. ♦ do not connect this un...

  • Page 6

    ○ ○ ○ ○ for gasoline or diesel powered generator sets ○ ○ ○ ○ ♦ check all fuel supply piping and their connections on a monthly basis for fuel leaks. ♦ use only approved piping and componentry in your fuel supply system. ♦ a professional, experienced technician should only install the fuel supply sy...

  • Page 7

    Table of contents section page basic location information……………………………………………………………………………………………….1 basic connection information………………………………………………………………………………………….2 basic engine information…………………………………………………………………………………………………….3 generator end maintenance………………………………………………………………………………………………….4 basic eng...

  • Page 8

    Location for best service from your portable generator set there are several factors which should be taken into consideration when choosing the best location in which to operate it: moisture: all electrical equipment should be protected from excessive moisture. Failure to do so will result in deteri...

  • Page 9

    Connections wiring: use sufficiently large insulated wire to connect the generator set to the load. The gauge of the wire will depend largely on the distance, the permissible voltage drop, and the size and type of load. If you are not sure of the gauge wire needed for your application, consult a com...

  • Page 10

    Engine information this operator's manual only covers basic day to day engine operating instructions. However, the engine manufacturer's manual is included with your generator set and should be referred to for any additional information you may need. Become familiar with and follow all the engine ma...

  • Page 11

    Maintenance maintenance should only be performed on the generator set after the engine has stopped and the generator set has cooled down. The battery and spark plug should also be disconnected prior to performing maintenance. Generator end maintenance generator end maintenance consists of cleaning t...

  • Page 12

    Adjustments: √ the engine should be checked for proper speed setting(s). √ prior to adjusting the engine speed, turn the auto idler off (if your generator set is equipped with this feature). Adjust the engine speed to 3720 rpm's (62 hertz) with no load applied to the generator set. √ adjust the auto...

  • Page 13

    Storage if you will not be using the generator set for a significant amount of time (3 months or longer) you should store the generator to prevent any problems that could arise from sitting idle. Please fully read the following guidelines prior to storing the unit. 1. Remove all fuel from the engine...

  • Page 14

    Use of electric motors electric motors require much more current (amperes) to start them than to run them. Some motors, particularly split-phase motors are very difficult to start and requires 5 to 7 times as much current to start them as it does to run them. Capacitor motors are a little easier to ...

  • Page 15: Service

    Ordering parts when generator repair parts are needed, they may be obtained by calling the parts department at baldor generators or the nearest local office of baldor electric motors and drives. Accurate information such as the following will assure that you receive accurate parts for your particula...

  • Page 16

    Operation prior to starting the unit: 1. Locate and set up the generator set in an open, dry, well ventilated and reasonably level location. Operating this unit in an area not suitable for it's proper use may cause damage to the unit, severe injury, or death. See "location information" section locat...

  • Page 17

    3. Pull lightly on the recoil grip until you feel significant resistance, then pull sharply. Do not allow the recoil rope to 'snap' back into the recoil housing. Allow the recoil to gently rewind into the recoil housing. See your engine manual for instructions specific to your unit. If the engine do...

  • Page 18

    Simple troubleshooting listed below are the more simple solutions to some of the more common problems that are reported to the service department at baldor generators. These troubleshooting solutions are meant to be an aid for a person who has minimal electrical knowledge and experience. More in- de...

  • Page 19

    5. Loss of residual magnetism. Loss of residual magnetism will not allow the generator's excitation system to build up and thus the generator set will not produce any power. To 'flash' the generator set, (restore residual magnetism) follow these steps: preferred method a. With the generator set stop...

  • Page 20

    Auto idler system not working properly (applies only to generator sets equipped with this feature) for the auto idler system to work, the generator set must be producing normal voltage output. If the generator set is not producing any power, the auto idler system will not work. 1. Generator set will...

  • Page 21: Control Panel

    Control panel for r30 a = nema 515r gfci duplex. This receptacle is a ground fault circuit interrupter duplex rated at 125 vac, 20 amps. This receptacle must be tested on a regular basis (monthly). B = standard duplex receptacle. This is your standard household duplex receptacle, it is rated for 120...

  • Page 22: Control Panel

    Control panel for the r45/r40 units a = the auto idler feature on/off switch. The auto idler feature allows the engine on the generator set to slow down to a "slow speed position" when there is no load being applied to the unit. When a load is applied to the unit, the auto idler circuitry allows the...

  • Page 23: Control Panel

    Control panel for the r60 generator a = the auto idler feature on/off switch. The auto idler feature allows the engine on the generator set to slow down to a "slow speed position" when there is no load being applied to the unit. When a load is applied to the unit, the auto idler circuitry allows the...

  • Page 24

    Generator-end componentry - 17 -.

  • Page 25

    Control box componentry - 18 -.

  • Page 26

    Parts breakdown for r30, r40, r45, r60, r60e units: ref ltr old part # new part # description a 46.00025b consult factory stator assembly for r30 gen sets (pre 6/95) a 46.10025b 61sa0019a00 stator assembly for r30 gen sets a 46.00045a consult factory stator assembly for r40/r45 gens (pre 6/95) a 46....

  • Page 27

    Ref ltr old part # new part # description ee 600.00020b oc3020f16sp capacitor, r30 ee 600.00030c oc6030f11* capacitor, r40/r45/r60 ff 610.00020 ck0070a02sp breaker, 20 amp ff 610.00025 ck0070a06sp breaker, 25 amp ff 610.00030 ck0070a03sp breaker, 30 amp ff 610.00040 ck0070a04sp breaker, 40 amp ff 61...

  • Page 28

    Connection diagram r30 - 21 -.

  • Page 29

    Connection diagram r40 / r45 - 22 -.

  • Page 30

    Connection diagram r60 - 23 -.

  • Page 31

    Connection diagram r60e - 24 -.

  • Page 32: Best

    Have joined forces to bring you the best engine/generator warranty in the industry! 3-year warranty on baldor generators and robin subaru engines see attached warranty statements for details: baldor generators 3815 oregon street oshkosh wi 54902 phone: (920) 236-4200 fax: (920) 236-4219 www.Baldor.C...

  • Page 33

    Robin subaru limited engine warranty for baldor generators (effective for original robin subaru engines powering baldor portable generators purchased after august 16, 2000) robin america, inc., a division of fuji heavy industries, ltd. (herein "robin"), warrants that each new engine sold by it will ...

  • Page 34

    Limited warranty effective august 1, 2003 unless otherwise provided, baldor generators are warranted against defects in baldor workmanship and materials for a period of time as set forth in the warranty period chart below. If a baldor product is defective due to baldor workmanship or materials and t...

  • Page 35

    *labor coverage for warrantable repairs is provided for the applicable period not to exceed published rates as contained in the baldor generators warranty policy. Mileage is allowed only for permanent installations not to exceed published rates as contained in the baldor generators warranty policy. ...

  • Page 36

    California proposition 65 warning engine exhaust from this product contains chemicals known to the state of california to cause cancer, birth defects, and other reproductive harm. California proposition 65 warning diesel engine exhaust and some constituents are known to the state of california to ca...

  • Page 37

    Service is just a phone call away: 800-872-7697 www.Baldor.Com/products/generators.Asp 3815 oregon street oshkosh wi 54902 phone: (920) 236-4200 fax: (920) 236-4219.