Baldwin Boxall BVSMP Installation Manual

Summary of BVSMP

  • Page 1

    Baldwin boxall communications ltd. Wealden industrial estate, farningham road crowborough, east sussex, tn6 2jr telephone: 01892 664422 fax: 01892 663146 website: www.Baldwinboxall.Co.Uk email: mail@baldwinboxall.Co.Uk bvsmp/lt issue 3 05/12/2011 ecr 2544 bvsmp / bvsmplt firmware version smp v6.1 & ...

  • Page 2

    -2- bvsmp/lt issue 3 ecr 2544 bvsmp / bvsmplt power supply & charger introduction the bvsmp contains two independent psu modules and can power either two bv225, two bv125d or two bv050q power amplifier modules. The bvsmplt contains a single psu module and can power either one bv225, one bv125d or on...

  • Page 3

    -3- bvsmp/lt issue 3 ecr 2544 battery resistance monitoring the battery resistance monitoring function ensures the battery condition is continuously monitored, and is a more accurate method than simple voltage measurement. The bvsmp monitoring meets the requirements of bs en54-4. Monitoring is contr...

  • Page 4

    -4- bvsmp/lt issue 3 ecr 2544 bvsmp / bvsmplt specifications bvsmp bvsmplt ac supply input voltage 200v – 250v 50 – 60hz 200v – 250v 50 – 60hz maximum power consumption: 700va 350va maximum inrush current @ 230v: 18a 9a dc output 1 to amplifier 1: 31v @ 12a 31v @ 12a dc output 2 to amplifier 2: 31v ...

  • Page 5

    -5- bvsmp/lt issue 3 ecr 2544 front panel view bvsmp rear panel view bvsmplt rear panel view +ve -ve n e 24v battery input 20a max sync l ac fuse in fault cond. Relay shown must be earthed this apparatus warning! En1722 www.Baldwinboxall.Co.Uk ac fuse 3.15a(t) 3.15a(t) model bvsmp. Made in england 1...