Balluff BIS V-6106 Technical Reference

Manual is about: Ethernet/IP

Summary of BIS V-6106

  • Page 1

    Bis v-6106 ethernet/ip technical reference, operating manual english.

  • Page 2

    Www.Balluff.Com.

  • Page 3

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 3 1 user instructions 4 1.1 about this manual 4 1.2 typographical conventions 4 1.3 symbols 4 1.4 meaning of warnings 4 1.5 abbreviations 5 2 safety 6 2.1 intended use 6 2.2 general safety notes 6 3 basic knowledge 7 3.1 operating principle of i...

  • Page 4

    Bis v-6106 ethernet/ip™ processor unit 4 this manual describes the processor unit for bis v-6106 identification systems and startup instructions for immediate operation. The following conventions are used in this manual: action instructions are indicated by a preceding triangle. The result of an act...

  • Page 5

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 5 arp address resolution protocol bis balluff identification system cip common industrial protocol cp code present crc cyclic redundancy check dhcp dynamic host configuration protocol i/o port digital input and output port eds electronic data sh...

  • Page 6

    Bis v-6106 ethernet/ip™ processor unit 6 the bis v-6106 processor unit is a component of the bis v identification system. It is used for linking to a host computer (plc, pc) within the identification system. It may be used only for this purpose in an industrial environment corresponding to class a o...

  • Page 7

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 7 the bis v identification system is classified as a non-contact system with read and write capabilities. This makes it possible to not only convey information that is programmed permanently in the data carrier, but also to collect and pass on c...

  • Page 8

    Bis v-6106 ethernet/ip™ processor unit 8 the processor unit is the link between data carrier and host control system. It manages two-way data transfer between data carrier and r/w head and provides buffer storage. The processor unit uses the r/w head to write data from the host control system to the...

  • Page 9

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 9 for bis v-6106-034-c00_, read/write heads in the bis vm-3 _ _, bis vl-3 _ _, and bis vu-3 _ _ series can be connected to terminals h1...H4. Bis v-6106-034-c10_ also supports read/write heads in the bis c-3 _ _ series (adapter required). Note r...

  • Page 10

    Bis v-6106 ethernet/ip™ processor unit 10 io-link is defined as a standardized point-to-point connection between sensors/actuators and an i/o module. An io-link sensor/actuator can send additional communication data (e.G. Diagnostics signals) in addition to the binary process signals over the io-lin...

  • Page 11

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 11 included in the scope of delivery: – bis v-6106 – 5 × closure cap – safety precautions note visit www.Balluff.Com for more information on available software and accessories. Figure 1: mechanical connection (dimensions in mm) figure 2: install...

  • Page 12

    Bis v-6106 ethernet/ip™ processor unit 12 note make the ground connection either directly or using an rc combination to ground. Connections + (,3 3rzhu (,3 + + + 6huylfh ,2/lqn )( h1…h4 read/write heads service/io-link usb function service/io-link (master function) eip1 ethernet/ip port 1 eip2 ether...

  • Page 13

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 13 figure 1: dimensions in mm housing material zinc die-cast housing h1…h4 v s 24 v dc - m12 female, 5-pin, a-coded service/io-link (master function) m12 female, 5-pin, a-coded power 7/8" male, 5-pin eip port 2 m12 female, 4-pin, d-coded eip por...

  • Page 14

    Bis v-6106 ethernet/ip™ processor unit 14 ambient temperature 0 °c…+60 °c storage temperature 0 °c…+60 °c emc (bis v-6106-034-c00_) – en 61000-6-2 – en 61000-4-2/4/5/6 – severity level 2a/3a/2a/3a – en 61000-4-3 80 mhz – 1000 mhz – severity level 3a 1400 mhz – 2000 mhz – severity level 3a 2000 mhz –...

  • Page 15

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 15 the bis v-6106 processor unit and the controlling system communicate via ethernet/ip™ protocol. The ethernet/ip™ system consists of the following components: – ethernet/ip™ scanner – ethernet/ip™ adapter (the bis v-6106 processor unit in this...

  • Page 16

    Bis v-6106 ethernet/ip™ processor unit 16 assemblies instance id data length input 100 308 output 101 292 config 102 60 byte parameter description 00–01 device general configuration of the entire device 02–09 rfid head 1 configuration of read/write head 1 10–17 rfid head 2 configuration of read/writ...

  • Page 17

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 17 byte meaning 34+35 io-link port function 36 cycle time 37 validation type 38 iol vendor id 1 39 iol vendor id 2 40 iol device id 1 41 iol device id 2 42 iol device id 3 43 iol serial number 1 … … 58 iol serial number 16 59 parameter server if...

  • Page 18

    Bis v-6106 ethernet/ip™ processor unit 18 the crc check is a procedure for determining a check value for data in order to be able to recognize transmission errors. If the crc check is enabled, a status message will be sent when a crc error is detected. Note the crc check function is only supported b...

  • Page 19

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 19 the number of usable bytes thus decreases when using the checksum. Balluff data carrier type memory capacity usable bytes for crc_16 bis m-1_ _-01 752 byte 658 byte bis m-1_ _-02 2000 byte 1750 byte bis m-1_ _-03 112 byte 98 byte bis m-1_ _-0...

  • Page 20

    Bis v-6106 ethernet/ip™ processor unit 20 if this function is enabled, the type of the read/write head as well as the data carrier type and the serial number (uid = unique identifier) for the data carrier are output with the auto read function instead of data. The data is output as soon as the data ...

  • Page 21

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 21 the following data carriers are available for the bis v-6106 processor unit. Note the data carriers contain additional memory ranges for configuration and protected data. These ranges cannot be processed using the bis v-6106 processor unit. M...

  • Page 22

    Bis v-6106 ethernet/ip™ processor unit 22 note to achieve the read times specified on page 63 in dynamic operation, the tag type parameter has to be set to "bis c 32 byte" or "bis c 64 byte" on the respective head. For read/write heads bis vu: balluff data carrier type manufacturer memory capacity b...

  • Page 23

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 23 automatic upload (io-link slave ĺ io-link master) or download (io-link master ĺ io-link slave) can be switched on using this parameter. For automatic upload, the parameter configuration is read when an io-link device is plugged in. For automa...

  • Page 24

    Bis v-6106 ethernet/ip™ processor unit 24 two buffers are needed to exchange data and commands between the processor unit and the host control system (input buffer and output buffer). The buffer contents are exchanged using cyclical polling. The buffer content depends on the cycle in which it is wri...

  • Page 25

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 25 the control commands for the identification system and the data to be written to the data carrier are transmitted via the output buffer. Bit no. Subaddress 7 6 5 4 3 2 1 0 00 hex = bit header ti ka gr av 01 hex command identifier or data 02 h...

  • Page 26

    Bis v-6106 ethernet/ip™ processor unit 26 the input buffer is used to send the data read from the identification system, the designations, and the status codes to the host control system. Bit no. Subaddress 7 6 5 4 3 2 1 0 00 hex = bit header bb hf to mt af ae aa cp 01 hex status code or data 02 hex...

  • Page 27

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 27 status codes status code description of function 00 hex everything ok. 01 hex job cannot be run because there is no data carrier in range of the read/write head. 02 hex cannot read the data carrier. 03 hex data carrier was removed from the r/...

  • Page 28

    Bis v-6106 ethernet/ip™ processor unit 28 command designator 01 hex : read from data carrier reads user data from the specified start address. The data length is equal to the number of bytes. When using a data carrier with expanded memory, the read data carrier command can also be executed as a comm...

  • Page 29

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 29 command identifier 81 hex : read data carrier with 24-bit addresses when assigning addresses to data carriers with expanded memory, the start address and number of bytes can be specified as 24-bit values. Information about executing the comma...

  • Page 30

    Bis v-6106 ethernet/ip™ processor unit 30 command identifier 02 hex : write to data carrier writes user data at the specified start address. The data length is equal to the number of bytes. When using a data carrier with expanded memory, the write to data carrier command can also be executed as a co...

  • Page 31

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 31 command designator 82 hex : write to data carrier with 24-bit addresses when assigning addresses to data carriers with expanded memory, the start address and number of bytes can be specified as 24-bit values. Information about executing the c...

  • Page 32

    Bis v-6106 ethernet/ip™ processor unit 32 command designator 07 hex : store the start address for the "auto read" function configuring the start address after the data is read with the auto read function. For more details, see the “description of individual parameters” chapter on page 17. Subaddress...

  • Page 33

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 33 command designator 09 hex : type and serial number if a data carrier is recognized in the active read/write zone of the read/write head, this command will return the read-write head type as well as the data carrier type and serial number of t...

  • Page 34

    Bis v-6106 ethernet/ip™ processor unit 34 command designator 11 hex : copy data between data carriers copy data from one data carrier to another. The specified number of bytes will be copied from the source start address in the source data carrier to the target start address in the target data carri...

  • Page 35

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 35 command identifier 91 hex : copy data between data carriers with 24-bit addresses when assigning addresses to data carriers with expanded memory, the start address and number of bytes can be specified as 24-bit values. Information about execu...

  • Page 36

    Bis v-6106 ethernet/ip™ processor unit 36 command designator 12 hex : initialize crc_16 data check the memory area of the data carrier used is prepared for use with a crc data check. It is initialized by writing user data with a checksum. If the crc data check is enabled in the processor unit, then ...

  • Page 37

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 37 command identifier 92 hex : initialize crc_16 data check with 24-bit addresses when assigning addresses to data carriers with expanded memory, the start address and number of bytes can be specified as 24-bit values. Information about executin...

  • Page 38

    Bis v-6106 ethernet/ip™ processor unit 38 command designator 32 hex : write constant value to data carrier writes a constant value to the memory area, which is indicated with a start address and number of bytes. Subaddress meaning description of function 00 hex 1st bit header 01 hex command identifi...

  • Page 39

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 39 command identifier b2 hex : write constant value to data carrier with 24-bit addresses when assigning addresses to data carriers with expanded memory, the start address and number of bytes can be specified as 24-bit values. Information about ...

  • Page 40

    Bis v-6106 ethernet/ip™ processor unit 40 note details and more information about the available parameters as well as bis vu-specific commands can be found in the manual of the bis vu read/write head used (available at www.Balluff.Com). Command identifier 40 hex : select (select data carrier in mult...

  • Page 41

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 41 command identifier 41 hex : unselect (undo a data carrier selection) the unselect command undoes one data carrier selection that was carried out with the select command. If a selection is not active, the status will remain unchanged. Subaddre...

  • Page 42

    Bis v-6106 ethernet/ip™ processor unit 42 command identifier 42 hex : read from epc reads the epc memory area of a data carrier that was previously selected with the select command. In single-tag mode, that is, if only one data carrier is located in front of the active read/write zone antenna, then ...

  • Page 43

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 43 command identifier 43 hex : write to epc writes to the epc memory area of a data carrier that was previously selected with the select command. In single-tag mode, that is, if only one data carrier is located in front of the active read/write ...

  • Page 44

    Bis v-6106 ethernet/ip™ processor unit 44 7 device functions command identifier 44 hex : read from tid reads the tid memory area of a data carrier that was previously selected with the select command. In single-tag mode, that is, if only one data carrier is located in front of the active read/write ...

  • Page 45

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 45 command identifier 45 hex : configure the transmission power the transmission power for the antenna (erp or eirp), which is specified as a value in quarter dbm increments, affects the maximum range of the read/write range of the antenna. The ...

  • Page 46

    Bis v-6106 ethernet/ip™ processor unit 46 command identifier 46 hex : read out transmission power reads out the current transmission power (erp). The transmission power is returned as a value in the form of quarter dbm. Example: reading out the transmission power returns the value of 54 hex (= 84). ...

  • Page 47

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 47 command identifier 47 hex : read from multiple data carriers the read from multiple data carriers reads, depending on the configured type, the epc or the tid of all data carriers that are located in the active read/write area of the antenna. ...

  • Page 48

    Bis v-6106 ethernet/ip™ processor unit 48 note as circumstances require, the data must be transmitted over multiple bus cycles. Example of a received data frame with 2 epcs and 12 bytes per epc (illustration without bit headers).: epc 1: e2 ff 00 00 e2 11 90 22 e2 03 01 27 epc 2: e2 00 90 51 32 05 0...

  • Page 49

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 49 example of a received data frame with 2 epcs and 64 bytes per epc (illustration without bit headers): epc 1 length: 48 bytes (34 hex 38 hex ) epc: e2 ff 00 00 e2 11 90 22 e2 03 01 27 33 44 55 66 77 88 99 ac 01 02 03 04 05 06 07 08 09 0a 0b 0c...

  • Page 50

    Bis v-6106 ethernet/ip™ processor unit 50 command identifier 48 hex : write parameters the write parameters command transfers parameters to the bis vu read/write that affect its behavior. Subaddress meaning description of function 00 hex 1st bit header 01 hex command identifier 48 hex : write parame...

  • Page 51

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 51 7 device functions command identifier 49 hex : read parameters reads out the parameter values that are currently set in the read/write head. Subaddress meaning description of function 00 hex 1st bit header 01 hex command identifier 49 hex : r...

  • Page 52

    Bis v-6106 ethernet/ip™ processor unit 52 command identifier 50 hex : kill the kill command deactivates a data carrier previously selected with the select command. Note executing the kill command permanently deactivates the selected data carrier. The deactivation cannot be undone. Note in order to e...

  • Page 53

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 53 command identifier 53 hex : bulk read the bulk read command reads the data from a data carrier population. Optionally from all of the data carriers that are found in the active read/write zone of the antenna or from a subset that was previous...

  • Page 54

    Bis v-6106 ethernet/ip™ processor unit 54 if execution is successful, the response is passed to the input buffer in the following format: subaddress meaning description of function 00 hex 1st bit header 01 hex no. Of tags number of detected tags 02 hex number of bytes per tag bytes to be transmitted...

  • Page 55

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 55 command identifier 54 hex : bulk write the bulk write command writes data to a data carrier population. Optionally to all of the data carriers that are found in the active read/write zone of the antenna or from a subset that was previously se...

  • Page 56

    Bis v-6106 ethernet/ip™ processor unit 56 upon successful execution (ae = 1, af = 0), the number of written data carriers is transmitted into the input buffer in the following format: subaddress meaning description of function 00 hex 1st bit header ae = 1, af = 0: command finished. 01 hex no. Of tag...

  • Page 57

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 57 command identifier 55 hex : return number of tags this command returns the number of data carriers that were found in the active read/write zone of the antenna. Optionally, the total number of data carriers or the number of data carriers sele...

  • Page 58

    Bis v-6106 ethernet/ip™ processor unit 58 7 device functions command identifier 56 hex : get rssi (receive signal strength indicator) this command returns the rssi of a data carrier previously selected with the select command. The rssi is a value which is proportional to the signal strength of the r...

  • Page 59

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 59 57 hex : lock the lock command can block read or write access, as well as access of any kind, to memory areas (res, epc, tid, user) of a uhf data carrier. Depending on the level of security, the memory areas can be password protected or compl...

  • Page 60

    Bis v-6106 ethernet/ip™ processor unit 60 note the tid memory area is inherently read-only regardless of the lock status and can only be read. Lock status of the reserved memory area (access password and kill password) lock permalock lock status 0 0 read and write: no password 0 1 read and write: no...

  • Page 61

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 61 command identifier 58 hex : activate custom parameters places the bis v processor unit into the bis m-41_ compatibility mode for use of custom read/write commands in connection with bis m - 1_ _ - 07 type data carriers. Subaddress meaning des...

  • Page 62

    Bis v-6106 ethernet/ip™ processor unit 62 mifare: read times data carrier with 16 bytes per block data carrier detection ~ 20 ms read bytes 0 to 15 ~ 25 ms for each additional 16-byte block started ~ 10 ms write times data carrier with 16 bytes per block data carrier detection ~ 20 ms write bytes 0 ...

  • Page 63

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 63 read times: data carrier with 16 bytes per block bis l-1_ _ data carrier detection ~ 110 ms read bytes 0 to 15 ~ 175 ms for each additional 16-byte block started ~ 40 ms data carrier bis l-2_ _ data carrier detection + read data carrier ≤ 140...

  • Page 64

    Bis v-6106 ethernet/ip™ processor unit 64 example: 17 bytes should be written starting at address 187. Data carrier = 32 bytes per block. Blocks 5 and 6 are processed, since the start address 187 is in block 5 and end address 203 is in block 6. T = 2 * 120 + 17 * 10 = 410 read times within the first...

  • Page 65

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 65 the operating states of the identification system, the ethernet/ip interface and the io-link master are displayed using leds. Figure 7: function indicators 1 ready device (rd) 6 link/activity eip 1 (l/a) 2 module status (ms) 7 rd r/w head 3 n...

  • Page 66

    Bis v-6106 ethernet/ip™ processor unit 66 indicator function rd r/w head (green) com r/w head (yellow) off not ready no data carrier detected led lights up ready for operation data carrier detected (cp) led flashes cable break or r/w head not connected data carrier is being processed the io port is ...

  • Page 67

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 67 1. Reading 30 bytes at r/w head 1, start address 10 once enough data has been read during the execution of the read job to fill the input buffer for r/w head 1, the data will be transmitted to the input buffer. The ae bit is not set until the...

  • Page 68

    Bis v-6106 ethernet/ip™ processor unit 68 2. Reading 30 bytes at r/w head 1, start address 10, problem during reading note if a problem occurs, the af bit is set with the corresponding status number instead of the ae bit. Setting the af bit cancels the job and declares it as finished. Control identi...

  • Page 69

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 69 3. Reading 30 bytes at r/w head 1, start address 10, problem during reading note if a problem occurs after transmission of the data has started, the af bit is provided instead of the ae bit together with a corresponding status number. The af ...

  • Page 70

    Bis v-6106 ethernet/ip™ processor unit 70 4. Writing 30 bytes at r/w head 1, start address 20 control identification system 1. Process output buffer (note sequence): 2. Process input buffer (note sequence): 01 hex command designator 02 hex 00 hex /0f hex set aa bit, invert to bit 02 hex start addres...

  • Page 71

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 71 5. Copying data from one data carrier to another the data from one data carrier at a read/write head (source) is copied to a data carrier in front of another read/write head (target). The data carriers have to be in front of the read/write he...

  • Page 72

    Bis v-6106 ethernet/ip™ processor unit 72 6. Writing to a data carrier with a constant value a data carrier is to be written with 1000 bytes (constant value) starting from start address 80. Control identification system 1. Process output buffer (note sequence): 2. Process input buffer (note sequence...

  • Page 73

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 73 7. Initializing a data carrier for crc the sequence for crc initialization is similar to a write command. The start address and the number of bytes must correspond to the maximum amount of data used. In the example the complete memory area of...

  • Page 74

    Bis v-6106 ethernet/ip™ processor unit 74 8. Creating a basic state for a r/w head or switching off a r/w head the read/write heads for the identification system can be put into a basic state independently of each other and the respective read/write head can be shut off. Control identification syste...

  • Page 75

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 75 10 reading the epcs of multiple data carriers in front of the antenna (only bis vu) with a maximum number of 5, epc size of 12 bytes configured, 3 data carriers identified control identification system 1. Process output buffer (note sequence)...

  • Page 76

    Bis v-6106 ethernet/ip™ processor unit 76 11. Selecting a data carrier for further processing (only bis vu) for configuration with epc size of 12 bytes control identification system 1. Process output buffer (note sequence): 2. Process input buffer (note sequence): 01 hex command designator 40 hex 00...

  • Page 77

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 77 12. Bulk write (only bis vu) write to all data carriers that are located in front of the antenna. Write 16 bytes starting at data carrier address 3. Control identification system 1. Process output buffer (note sequence): 2. Process input buff...

  • Page 78

    Bis v-6106 ethernet/ip™ processor unit 78 13. Bulk read (only bis vu) read from all data carriers that are located in front of the antenna. Read 4 bytes starting at data carrier address 3. Control identification system 1. Process output buffer (note sequence): 2. Process input buffer (note sequence)...

  • Page 79

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 79 14. Reading the read/write head parameters (only bis vu) reading the parameter max epc length (parameter 0003 hex ) from one bis vu read/write head. Control identification system 1. Process output buffer (note sequence): 2. Process input buff...

  • Page 80

    Bis v-6106 ethernet/ip™ processor unit 80 16. Setting the read/write head parameters (only bis vu) setting an access password (parameter 1002 hex ) for accessing a password-protected data carrier. Password: 12345678 hex control identification system 1. Process output buffer (note sequence): 2. Proce...

  • Page 81: Balluff

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 81 the display provides functions for starting up the bis v. It can be used to set the ip and gateway address and the subnet mask. In addition, tag data and version information can be output for diagnostic purposes. It is controlled using a 2-bu...

  • Page 82: Balluff

    Bis v-6106 ethernet/ip™ processor unit 82 1 balluff cancel or enter 2 main setup info cancel (1 s) enter cancel 4 info tag id version enter (1 s) 3 main setup info cancel (1 s) enter cancel 5 info tag id version enter (1 s) 6 vers. Info fw: 1.00 iol: 010a cancel (1 s) two versions are displayed: the...

  • Page 83: Balluff

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 83 1 balluff cancel or enter 2 main ip set. Info cancel (1 s) enter (1 s) cancel (1 s) 4 ip config static dhcp enter (1 s) 3 ip setup ip conf. Ip addr. Cancel (1 s) Ź press enter/down to select the desired configuration. Ź pressing cancel (1 s) ...

  • Page 84

    Bis v-6106 ethernet/ip™ processor unit 84 1 cancel or enter 2 cancel (1 s) enter (1 s) cancel (1 s) 3 enter (1 s) cancel (1 s) 5 enter (1 s) 4 cancel (1 s) enter (1 s) cancel (1 s) 6 Ź you can switch through the positions (1st, 2nd, 3rd) by pressing enter/down. The current position starts flashing. ...

  • Page 85

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 85 1 cancel or enter 2 enter (1 s) 3 cancel (1 s) cancel (1 s) enter (1 s) cancel (1 s) 6 enter (1 s) 5 enter (1 s) 4 cancel (1 s) cancel (1 s) enter (1 s) cancel (1 s) 7 Ź you can switch through the positions (1st, 2nd, 3rd) by pressing enter/d...

  • Page 86

    Bis v-6106 ethernet/ip™ processor unit 86 7 device functions 1 cancel or enter 2 enter (1 s) 3 cancel (1 s) cancel (1 s) enter (1 s) cancel (1 s) 4 enter (1 s) cancel (1 s) 7 enter (1 s) 6 enter (1 s) 5 cancel (1 s) cancel (1 s) enter (1 s) cancel (1 s) 8 Ź you can switch through the positions (1st,...

  • Page 87

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 87 7 device functions the bis v ethernet/ip device includes an integrated webserver for retrieving detailed information on the current status. Additionally, this can be used for the configuration of the ip settings and for setting parameters for...

  • Page 88

    Bis v-6106 ethernet/ip™ processor unit 88 7 device functions information on the current process data and the port status of the device is visualized by leds on this page. If an rfid r/w head or an io-link-device is connected to the respective ports, then additional information on the connected modul...

  • Page 89

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 89 7 device functions the parameter settings of the selected module (r/w heads, io-link) are shown on this page. Every module can be selected individually (right side). Io-link modules can also be configured using this page. Note the connected i...

  • Page 90

    Bis v-6106 ethernet/ip™ processor unit 90 7 device functions this page shows the current status of the module and the network, as it appears on the module. Diagnostic module.

  • Page 91

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 91 7 device functions the module description and module position and the ip address can be edited on this page. The device settings can also be reset. This function can only be used after entering a username and password: username: balluff passw...

  • Page 92

    Bis v-6106 ethernet/ip™ processor unit 92 7 device functions contact information is shown on this page contact.

  • Page 93

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 93 bis v – 6 1 06 – 034 – c002 balluff identification system series v (v = variable) system component 6 = processor unit generation (design/material) 1 = generation 1, 2011 housing design, metal interface 02 = profibus dp 06 = ethernet/ip 08 = p...

  • Page 94

    Bis v-6106 ethernet/ip™ processor unit 94 decimal hex control code ascii decimal hex ascii decimal hex ascii 0 00 ctrl @ nul 43 2b + 86 56 v 1 01 ctrl a soh 44 2c , 87 57 w 2 02 ctrl b stx 45 2d - 88 58 x 3 03 ctrl c etx 46 2e . 89 59 y 4 04 ctrl d eot 47 2f / 90 5 a z 5 05 ctrl e enq 48 30 0 91 5b ...

  • Page 95

    Www.Balluff.Com bis v-6106 ethernet/ip™ processor unit 95 index a accessories 93 ascii table 94 auto read standard 20 c checksum 18 communication basic sequence 61 control bit code present 26 default state 25 head error 26 job 25, 61 job end 26, 61 job error 26 job start 26, 61 toggle bit in 25, 61 ...

  • Page 96

    Www.Balluff.Com www.Balluff.Com no. 911292-726 en · 03.122178 · d16; subject to change. Replaces k15. Balluff gmbh schurwaldstraße 9 73765 neuhausen a.D.F. Germany tel. +49 7158 173-0 fax +49 7158 5010 balluff@balluff.De.