INSTALLATION
WARNING: Before installing in a solid fuel burn-
ing fireplace, the chimney flue and firebox must be
cleaned of soot, creosote, ashes and loose paint by
a qualified chimney cleaner. Creosote will ignite if
highly heated. A dirty chimney flue may create and
distribute soot within the house. Inspect chimney
flue for damage.
NOTICE: Installation, service, and repair of this appli-
ance must be performed by a qualified installer,
service agency, company or gas supplier experi-
enced with this type of gas appliance. Only factory
authorized components listed in these instructions
may be used in accordance with the manufacturer’s
instructions and all codes and requirements of the
authority having jurisdiction. Any modifications to
this kit, or use of unauthorized components or acces-
sory items will void the manufacturer’s warranty, and
may result in a hazardous condition.
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, you must
install ON/OFF Safety Valve/Pilot Kit (see Accessories, page 22).
Call dealer where you bought log set.
If the fireplace does not have a gas supply shutoff valve, one must
be installed.
CAUTION: Do not remove the metal data plates
attached to the burner pan. The data plates contain
important warranty information.
FLUE OPENING SPECIFICATIONS
Note:
This vented appliance must be installed only in a solid-fuel
burning fireplace with a working flue and constructed of noncom-
bustible material.
The charts in Figure 4 indicate technical information regarding the
installation of your gas log set. Please make sure that all of the
specifications shown are applicable before installation is attempted.
The fireplace must include a working flue and venting system with
the minimum openings shown in the Figure 4.
MODEL
DESCRIPTION
BVTR18
18" Triple Burner
60,000
50,000
8" dia.
BVTR24
24" Triple Burner
70,000
60,000
8" dia.
Btu Input
Natural Gas
Btu Input
Propane Gas
Minimum
Vent Opening
MINIMUM FIREBOX SIZES
LOG
FRONT
BACK
SIZE WIDTH* WIDTH**
DEPTH HEIGHT
18"
28"
16"
14"
18"
24"
29
3
/
4
"
17"
15
1
/
2
"
18"
*Add 2" if safety valve/pilot is used **At depth indicated
FUEL INLET PRESSURE
SPECIFICATIONS ("W.C.)
Min.
Max.
NG
5.5
10.5
LP
11
13
Figure 4 - Technical Information Charts
VENTING SPECIFICATIONS FOR INSTALLATION
The fireplace chimney flue and vent must be drafting properly. To
check the vent for proper drafting: Light a tightly rolled newspaper
on one end and place it at the inside front edge of the fireplace.
Observe the smoke and be sure the vent is properly drawing it up the
chimney. If the smoke spills out into the room, extinguish the flame
and remove any obstruction until proper venting is achieved.
The chimney flue must remain open a minimum of 3" at all times
during the operation of this log set.
BURNER ORIFICE
LOG
NATURAL
PROPANE/LP
SIZE FRONT
REAR
FRONT
REAR
18"
.046
4x.064
.036
4x.043
24"
.064
4x.064
.036
4x.0465
INSTALLING DAMPER CLAMP
Secure the damper stop clamp provided to the leading edge of the
damper as shown in Figure 5. If for any reason this clamp doesn't
work on your fireplace, another suitable clamp or permanent stop
must be installed, or the damper blade must be cut or removed.
Damper Clamp
Damper Clamp
Damper
Manufactured
Fireplace
Masonry Fireplace
Damper
Damper
Figure 5 - Attaching Damper Clamp
INSTALLATION
Flue Opening Specifications
Check Gas Type
Venting Specifications for Installation
Installing Damper Clamp