Bard QW2S-QW5S Water-to-Air H Engineering Specification Manual

Summary of QW2S-QW5S Water-to-Air H

  • Page 1

    F1915 (2012 04) page 1 of 6 bard manufacturing company, inc. Qw2s-qw5s water-to-air h/p engineering specification guide 1.0 general furnish and install a self-contained, vertical, floor standing, heat pump to be manufactured by bard manufacturing company, inc. The unit shall be approved and listed b...

  • Page 2

    F1915 (2012 04) page 2 of 6 2.3 compressor all models shall use a high efficiency scroll compressor with step capacity providing 2 stages of control. The compressor shall be covered by a 5-year parts warranty. The refrigeration circuit shall be equipped with factory installed high and low-pressure c...

  • Page 3

    F1915 (2012 04) page 3 of 6 standard. One shall be used for fresh water applications, the other for protected (antifreeze) closed systems. The factory wired switch is for fresh water. Phase rotation protection and phase failure protection shall be standard factory installed features on all equipment...

  • Page 4

    F1915 (2012 04) page 4 of 6 the built-in commercial room ventilator (crv) is internally mounted and allows outside ventilation air, up to 50% of the total air flow rating of the unit, to be introduced through the air inlet openings. The crv shall be modular and easily added or removed from the unit ...

  • Page 5

    F1915 (2012 04) page 5 of 6 5.1 2” fiberglass – pleated – merv 8 6.0 hot gas reheat- (factory installed option) 6.1 the dehumidification circuit incorporates an independent heat exchanger coil in the supply air stream in addition to the standard evaporator coil. This coil reheats the supply air afte...

  • Page 6

    F1915 (2012 04) page 6 of 6 intake and exhaust. Louver shall have a powder coat finish. See our color chart for color selections. Louver required with sleeve with the use of any ventilation option. 10.4 air distribution – (select 1) 10.3.1 the q-tec shall have a discharge air plenum with double defl...