Bard WA7013B Installation Instructions Manual

Manual is about: WALL MOUNTED PACKAGE AIR CONDITIONERS

Summary of WA7013B

  • Page 1

    Installation instructions wall mounted package air conditioners models wl4822 wl4823 wl6022 wl6023 wl602n manual : 2100-351d supersedes: 2100-351c file: volume iii tab 16 date: 09-20-01 bard manufacturing company bryan, ohio 43506 since 1914...Moving ahead just as planned. © copyright 2001.

  • Page 2: Contents

    Contents figures figure 1 unit dimensions ..................................... 3 wa602n, wa6023, wa4823 figure 2 unit dimensions ..................................... 4 wa6022, wa4822 figure 3 mounting instructions ............................. 8 wa602n, wa6023, wa4823 figure 4 mounting instruction...

  • Page 3

    Manual 2100-351 page 1 getting other information and publications these publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National ele...

  • Page 4

    Manual 2100-351 page 2 wall mount general information air conditioning wall mount model nomenclature wl 60 2 3 a 10 x n x x x a note: all vent options are without exhaust capability. May require separate field supplied barometric relief in building. Table 1 electric heat table wl4822a, wl4822b, wl48...

  • Page 5

    Manual 2100-351 page 3 figure 1 unit dimensions wl602n, wl6023, wl4823 only mis-1451.

  • Page 6

    Manual 2100-351 page 4 figure 2 unit dimensions wl6022, wl4822 only mis-1452.

  • Page 7

    Manual 2100-351 page 5 table 2 electrical specifications j k l maximum size of the time delay fuse or hacr type circuit breaker for protection of field wiring conductors. Based on 75° c copper wire. All wiring must conform to nec and all local codes. These “minimum circuit ampacity” values are to be...

  • Page 8

    Manual 2100-351 page 6 a 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See wall mounting instructions and figures 3 and 3a for further details. Ducts through the walls must be insulated and all joints taped or sealed to prev...

  • Page 9: Installation Instructions

    Manual 2100-351 page 7 installation instructions wall mounting information 1. Two holes for the supply and return air openings must be cut through the wall as shown in figure 1 or 2. Figure 1 is for models wl4823, and wl6023. Figure 2 is for models wl822 and wl6022. 2. On wood frame walls, the wall ...

  • Page 10

    Manual 2100-351 page 8 figure 3 mounting instructions wl602n, wl6023, wl4823 only mis-1349.

  • Page 11

    Manual 2100-351 page 9 figure 4 mounting instructions wl6022, wl4822 only mis-1444.

  • Page 12: Warning

    Manual 2100-351 page 10 figure 5 electric heat clearance side section view of supply air duct for wall mounted unit showing 1/4 inch clearance to combustible surfaces. Mis-277 warning a minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is re...

  • Page 13

    Manual 2100-351 page 11 figure 6 wall mounting instructions figure 7 wall mounting instructions mis-548 mis-549 mis-948 see figure 3 – mounting instructions supply air opening return air opening return air opening supply air opening bottom mounting bracket. Mount on wall before installing unit. Retu...

  • Page 14

    Manual 2100-351 page 12 figure 8 common wall mounting installations mis-550

  • Page 15

    Manual 2100-351 page 13 wiring – main power refer to the unit rating plate for wire sizing information and maximum fuse or “hacr” type circuit breaker size. Each outdoor unit is marked with a “minimum circuit ampacity”. This means that the field wiring used must be sized to carry that amount of curr...

  • Page 16

    Manual 2100-351 page 14 figure 9 unit 24v terminal board mis-1373a.

  • Page 17: Start Up

    Manual 2100-351 page 15 start up important installer note for improved start up performance wash the indoor coil with a dish washing detergent. Crankcase heaters these units are not provided with crankcase heat. These units utilize scroll compressors which do not require crankcase heat in this appli...

  • Page 18

    Manual 2100-351 page 16 pressure service ports high and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the uni...

  • Page 19: Troubleshooting

    Manual 2100-351 page 17 the suction line temperatures in table above are based upon 80° f dry bulb / 67° f wet bulb (50% r.H.) temperature and rated airflow across the evaporator during cooling cycle. Removal of fan shroud 1. Disconnect all power to the unit. 2. Remove the screws holding both grille...

  • Page 20

    Manual 2100-351 page 18 table 9 maximum esp of operation electric heat only values shown are for units equipped with standard 1” throwaway filters or 1” washable filters. Derate esp by .15 for 2” pleated filters. S l e d o m p s e - 3 2 0 6 l w y l n o 5 0 a 0 1 a 9 0 b 4 . 3 . 3 . Low side pressure...

  • Page 21

    Manual 2100-351 page 19 table 11 optional accessories wl6023a. Wl6022a wl6023b, wl6022b wl4823a, wl4822a wl4823b, wl4822b t r a p r e b m u n n o i t p i r c s e d 5 1 - c m c t i k t r a t s x x a 9 0 - b c m w b 7 0 - b c m w a 8 0 - b c m w b 5 0 - b c m w t i k r e k a e r b t i u c r i c t i k ...